background image

2. 

 For  tubes  longer  than  the  width  of  the  air  duct,  the  tube  should  extend 
out  of  the  opposite  side  of  the  duct.  Drill  a  1.9  cm  hole  in  the  duct  op-
posite  the  hole  already  cut  for  the  sampling  tube.  Ensure  that  the  sam-
pling  tube  is  angled  downward  from  the  duct  smoke  detector  to  allow 
for moisture drainage away from the detector.  The sampling tube should 
be  angled  at  least  .63  cm  downward  for  every  30.5  cm  of  duct  width 
per  Figure  4.  There  should  be  10  to  12  holes  spaced  as  evenly  as  pos-
sible  across  the  width  of  the  duct.  If  there  are  more  than  2  holes  in  the 
section of the tube extending out of the duct, select a shorter tube using 
Table  1.  Otherwise,  trim  the  tube  to  leave  approximately  2.54-5.08cm 
extending  outside  the  duct.  Plug  the  end  with  the  end  cap  and  tape 
closed any holes in the protruding section of the tube. Be sure to seal the 
duct where the tube protrudes.

figURe 4:

DETECT O R

1.9 cm

HOLE

30.5 cm

.63 cm

.5 cm

H0215-01

NOTE:  Air  currents  inside  the  duct  may  cause  excessive  vibration,  especially 
when  the  longer  sampling  tubes  are  used.  In  these  cases,  a  7.6  cm  floor  flange 
(available  at  most  plumbing  supply  stores)  may  be  used  to  fasten  the  sam-
pling  tube  to  the  other  side  of  the  duct.  When  using  the  flange/connector 
mounting technique, drill a 2.5 to 3.2 cm hole where the flange will be used.

[6.3] MoDificationS of SaMpLing tUBeS

There  may  be  applications  where  duct  widths  are  not  what  is  specified  for  the 
installation.  In  such  cases,  it  is  permissible  to  modify  a  sampling  tube  that  is 
longer than necessary to span the duct width.
Use  a  4.9  mm  drill  and  add  the  appropriate  number  of  holes  so  that  the  total 
number  of  holes  exposed  to  the  air  flow  in  the  duct  is  10  to  12.  Space  the  ad-
ditional holes as evenly as possible over the length of the tube.
NOTE:  This  procedure  should  only  be  used  as  a  temporary  fix.  It  is  not  in-
tended as a permanent substitute for ordering the correct length tubes.

[6.4] ReMote SaMpLing tUBe inStaLLation

The  detector  arrangement  can  also  incorporate  the  remote  mounting  of  the 
sampling  tube  and/or  exhaust  tube.  In  this  case  both  the  detector,  sampling 
tube  and  exhaust  tube  (if  included)  should  be  rigidly  mounted  to  withstand 
the  pressure  and  vibrations  caused  by  the  air  velocity.  The  location  of  the 
detector’s  sampling  tube  should  be  such  that  there  is  uniform  airflow  in  the 
cross section area. 
The  pressure  differential  across  the  sampling  and  exhaust  ports  in  the  detec-
tor  housing  shall  be  verified  to  be  between  .25  and  28.2  mm  of  water.  Do  so 
by  measuring  the  pressure  difference  between  the  inlet  and  outlet  ports  on 
the  detector  housing  using  a  manometer  as  described  in  Section  10.4.4  of  this 
manual.

[7] MeaSUReMent teStS

[7.1] aiR fLow

The  D2E  is  designed  to  operate  over  an  extended  air  speed  range  of  1.5  to  20.3 
m/sec.  To  verify  sufficient  sampling  of  ducted  air,  turn  the  air  handler  on  and 
use  a  manometer  to  measure  the  differential  pressure  between  the  two  sam-
pling  tubes.  The  differential  pressure  should  measure  at  least  .25  mm  of  water 
and  no  more  than  28.2  mm  of  water.  Because  most  commercially  available 
manometers  cannot  accurately  measure  very  low  pressure  differentials,  ap-
plications  with  less  than  2.54  m/sec  of  duct  air  speed  may  require  one  of  the 
following:  1)  the  use  of  a  current-sourcing  pressure  transmitter  (per  Section 
7.2; or 2) the use of aerosol smoke per section 10.4.4.

[6] SaMpLing tUBe inStaLLation 

[6.1] SaMpLing tUBe SeLection

The  sampling  tube  must  be  purchased  separately.  Order  the  correct  length, 
as  specified  in  Table  1,  for  width  of  the  duct  where  it  will  be  installed.  It  is 
recommended that the sampling tube length extend at least 

2

/

3

 across the duct 

width for optimal performance.

taBLe 1. SaMpLing tUBeS RecoMMenDeD foR 

DiffeRent DUct wiDthS:

Outside Duct Width

Sampling Tube 

Recommended*

Up to 30.5 cm

DST1

30.5 to61 cm

DST1.5

61 to 122 cm

DST3

122 to 244 cm

DST5

244 to 366 cm

DST10 (2-piece)

*Must extend a minimum of 

2

/

3

 the duct width

The  sampling  tube  is  always  installed  with  the  air  inlet  holes  facing  into  the 
air  flow.  To  assist  proper  installation,  the  tube’s  connector  is  marked  with  an 
arrow.  Make  sure  the  sampling  tube  is  mounted  so  that  the  arrow  points  into 
the  airflow  as  shown  in  Figure  3.  Mounting  the  detector  housing  in  a  vertical 
orientation  is  acceptable  provided  that  the  air  flows  directly  into  the  sampling 
tube  holes  as  indicated  in  Figure  3.  The  sampling  tube  and  exhaust  tube 
can  be  mounted  in  either  housing  connection  as  long  as  the  exhaust  tube  is 
mounted downstream from the sampling tube.

figURe 3. aiR DUct DetectoR SaMpLing tUBe:

SAMPLING TUBE ENDCAP

ARROW MUST FACE 

INTO AIR FLOW

AIR FLOW 

DIRECTION

H0551-00

CAUTION:  The  sampling  tube  end  cap,  included  with  the  detector,  is  criti-
cal  to  proper  operation  of  the  duct  smoke  detector. The  end  cap  is  needed  to 
create  the  proper  air  flow  to  the  sensor  of  the  duct  smoke  detector.  Once  any 
sampling tube length adjustments are made, plug the end of the sampling tube 
with the provided end cap.

A  plastic  exhaust  tube  is  included  with  the  unit  to  be  installed  if  needed.  In-
stall  into  the  housing  connection  that  is  downstream  from  the  sampling  tube 
connection.  The  exhaust  tube  can  be  installed  from  the  front  of  the  detector 
or  the  back.  A  longer  30.5  cm  exhaust  tube,  model  ETX  is  available  as  an  ac-
cessory in cases where the molded exhaust tube does not extend at least 5 cm 
into the duct.

[6.2] SaMpLing tUBe inStaLLation

1. 

 For  tubes  shorter  than  the  width  of  the  duct,  slide  the  sampling  tube, 
with  installed  end  cap,  into  the  housing  connection  that  meets  the  air-
flow  first.  Position  the  tube  so  that  the  arrow  points  into  the  airflow  as 
shown  in  Figure  3.  Sampling  tubes  over  91.4  cm  long  should  be  sup-
ported  at  the  end  opposite  of  the  duct  detector.  In  ducts  wider  than 
244cm,  work  must  be  performed  inside  the  duct  to  couple  the  other  sec-
tion  of  the  sampling  tube  to  the  section  already  installed  using  the  4  cm 
conduit fitting supplied. Make sure that the holes on both sections of the 
air inlet sampling tube are lined up and facing into the airflow.

SS-300-020 

I56-3536-003R

Summary of Contents for Innovair Flex D2E

Page 1: ...g in a building s regular fire detection system This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialist This device will not sense smoke unless the ventilation system is operating and the cover is installed For this detector to function properly it MUST be installed...

Page 2: ...e 2 REMOVE SCREW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target cent...

Page 3: ...two sam pling tubes The differential pressure should measure at least 25 mm of water and no more than 28 2 mm of water Because most commercially available manometers cannot accurately measure very low pressure differentials ap plications with less than 2 54 m sec of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter per Section 7 2 or 2 the use of ...

Page 4: ...lor coded to prevent wiring mistakes Improper connections can prevent a system from responding properly in the event of a fire For signal wiring the wiring between interconnected detectors or from detec tors to auxiliary devices it is recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12gauge Smoke detectors and alarm s...

Page 5: ...low out the residual aerosol smoke from the chamber and reset the duct smoke detector Use duct tape to seal the aero sol smoke entry hole CAUTION Canned aerosol simulated smoke canned smoke agent formulas will vary by manufacturer Misuse or overuse to these products may have long term adverse effects on the smoke detector Consult the canned smoke agent man ufacturer s published instructions for an...

Page 6: ...thorization number send defective units to Returns Department RA __________ Pittway Tecnologica Srl Via Caboto 19 3 34147Trieste Italy Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufactu...

Reviews: