[5] DetectoR inStaLLation

[5.1] VeRify DUct aiR fLow DiRection anD VeLocity

Model  D2E  detectors  are  designed  to  be  used  in  air  handling  systems  having 
air  velocities  of  1.5  to  20.3  m/sec.  Duct  widths  from  15.3  to  30.5cm  can  be 
accommodated.  Be  sure  to  check  engineering  specifications  to  ensure  that  the 
air  velocity  in  the  duct  falls  within  these  parameters.  If  necessary,  use  a  veloc-
ity meter (anemometer) to check the air velocity in the duct.

[5.2] DeteRMine MoUnting Location 

anD configURation

On  ducts  wider  than  45.7cm  it  is  recommended  that  the  detector  be  mounted 
downstream  of  a  bend,  obstruction  in  the  duct,  or  the  supply  or  return  air 
inlet. 
Exception:  Installation  of  duct  detectors  can  be  on  or  within  a  commercial 
packaged  rooftop  heating  and  air-conditioning  system,  fire/smoke  dampers 
and  economizers. They  may  be  mounted  in  either  the  supply  and/or  return  air 
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted 
in  a  side-by-side  “rectangular”  configuration  or  a  top-over-bottom  “square” 
configuration  as  shown  in  Figure  2.  If  mounting  in  the  square  configuration, 
remove  the  rear  attachment  screw,  rotate  the  unit  at  hinge,  and  replace  the 
screw  into  the  new  attachment  hole  as  shown  in  Figure  2.  Do  NOT  remove 
the  hinge  screw  during  this  process.  Final  installation  approval  shall  be  based 
upon passing section 10.4.2 and 10.4.4 tests.

figURe 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[5.3] DRiLL the MoUnting hoLeS

Remove  the  paper  backing  from  the  mounting  template  supplied.  Affix  the  tem-
plate  to  the  duct  at  the  desired  mounting  location.  Make  sure  the  template  lies 
flat and smooth on the duct. 

[5.3.1] foR RectangULaR SiDe-By-SiDe MoUnting configURation:

Center  punch  at  (4)  target  centers:  (2)  “A”  for  sampling  tubes  and  (2)  “B”  for 
the  rectangular  configuration  mounting  tabs  as  shown  on  mounting  template. 
Drill  pilot  holes  at  target  “A”  centers  and  cut  two  3.5cm  diameter  holes  using 
a  3.5cm  hole  saw  or  punch.  Drill  4mm  diameter  holes  using  a  4mm  drill  at 
target “B” centers.

[5.3.2] foR SqUaRe top-oVeR-BottoM MoUnting configURation:

Center  punch  at  (4)  target  centers:  (2)  “A”  for  sampling  tubes  and  (2)  “C” 
for  the  square  configuration  mounting  tabs  as  shown  on  mounting  template. 
Drill  pilot  holes  at  target  “A”  centers  and  cut  two  3.5cm  diameter  holes  using 
a  3.5cm  hole  saw  or  punch.  Drill  4mm  diameter  holes  using  a  4mm  drill  at 
target  “C”  centers.  If  desired,  drill  an  additional  4mm  hole  at  the  location  of 
one of the mounting tabs on the lower housing.

[5.4] SecURe the DUct DetectoR to the DUct

Use  two  (rectangular  configuration)  or  three  (square  configuration)  of  the  pro-
vided sheet metal screws to screw the duct detector to the duct.
CAUTION: Do not overtighten the screws.

SS-300-020 

I56-3536-003R

[4] figURe 1. expLoDeD View of DUct SMoke DetectoR coMponentS:

MAGNET TEST LOCATION

SENSOR MODULE COVER

TERMINAL HOUSING 

MODULE COVER

SAMPLING TUBE

EXHAUST TUBE

SENSOR HEAD

WIRING TERMINALS

(sold seperately)

H0574-02

Summary of Contents for Innovair Flex D2E

Page 1: ...g in a building s regular fire detection system This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialist This device will not sense smoke unless the ventilation system is operating and the cover is installed For this detector to function properly it MUST be installed...

Page 2: ...e 2 REMOVE SCREW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target cent...

Page 3: ...two sam pling tubes The differential pressure should measure at least 25 mm of water and no more than 28 2 mm of water Because most commercially available manometers cannot accurately measure very low pressure differentials ap plications with less than 2 54 m sec of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter per Section 7 2 or 2 the use of ...

Page 4: ...lor coded to prevent wiring mistakes Improper connections can prevent a system from responding properly in the event of a fire For signal wiring the wiring between interconnected detectors or from detec tors to auxiliary devices it is recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12gauge Smoke detectors and alarm s...

Page 5: ...low out the residual aerosol smoke from the chamber and reset the duct smoke detector Use duct tape to seal the aero sol smoke entry hole CAUTION Canned aerosol simulated smoke canned smoke agent formulas will vary by manufacturer Misuse or overuse to these products may have long term adverse effects on the smoke detector Consult the canned smoke agent man ufacturer s published instructions for an...

Page 6: ...thorization number send defective units to Returns Department RA __________ Pittway Tecnologica Srl Via Caboto 19 3 34147Trieste Italy Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufactu...