Current Requirements (using no accessories)

Power supply voltage

20-30 VDC

24 VAC, 50-60HZ

120VAC, 50-60Hz

220/240 VAC, 50-60Hz

Max. standby current

26 mA

65 mA RMS

44 mA RMS

25 mA RMS

Max. alarm current

87 mA

182 mA RMS

52 mA RMS

30 mA RMS

Alarm response time

3 to 17 sec.

3 to 17 sec.

3 to 17 sec.

3 to 17 sec.

Power up time

2 sec.

2 sec.

2 sec.

2 sec.

Device

Standby

Alarm

PA400

0 mA

15 mA Max.

RA400Z

0 mA

12 mA Max.

RTS451/RTS451KEY

0 mA

10 mA Max.

Wiring diagram for DH200RP Duct Smoke Detector with optional RA400Z  

Wiring diagram for DH200RP Duct Smoke

Detector with RTS451/RTS451KEY 

Wiring diagram for DH200RP Duct Smoke Detector with optional PA400 

Wiring diagram for DH200RP Duct Smoke Detector using a UL listed control panel 

NOTE: Jumper J1 shunt must be installed for non-relay applications. J1 shunt must be removed for power super vision. 

DH200RP Specifications 

Alarm auxiliar y contacts* (DPDT)

10 A @ 30 VDC

10 A @ 277 VAC (0.75 power factor)

240 VA @ 249 VAC (0.4 power factor)

1/8 HP @ 120 VAC

1/4 HP @ 240 VAC

Super visor y contact (SPST)

2.0 A @ 30 VDC (resistive)

*Minimum switching current for auxiliaty contact
must be 500 mA DC minimum @ 24 VDC.

Contact Ratings

Accessor y Current Loads at 24 VDC

+

COM (+)

COM (-)

COM (+)

COM (-)

COMMUNICATION
LINE

UL LISTED CONTROL
PANEL

1ST DETECTOR
IN LOOP

2ND DETECTOR
IN LOOP

1

2

1

2

J1 JUMPER

J1 JUMPER

5 7

RA400Z

5 = Alarm Signal
7 = Aux. Power (—)

DO NOT BREAK TAB ON RA400Z

ALARM SIGNAL

AUX. POWER (—)

TEST +

TEST —

ALARM SIGNAL

NOT USED

NOT USED

CIRCUIT
REFERENCE

TEST
SWITCH

FOR RTS451, TERMINAL 3 IS NOT
USED. (RTS451 DOES NOT HAVE
A TERMINAL 6.) FOR RTS451KEY,
TERMINALS 3 AND 6 ARE NOT USED.

RTS 451/RTS451KEY

5

7

4

3

1

3

6

2

4

5

5 7

PA400

5 = Alarm Signal
7 = Aux. Power (—)

NOTE: External power of 24V AC/DC

or 120/220 VAC must be connected in

order to power all remote horn or

strobe accessories.

Summary of Contents for Innovair 200 Series

Page 1: ... the UL recognized power and sensor boards WARNING Duct smoke detectors have specific limitations DUCT SMOKE DETECTORS ARE NOT a substitute for an open area smoke detector NOT a substitute for early warning detection and NOT a replacement for a building s regular fire detection system Refer to NFPA 72 and 90A for additional duct smoke detector application information Air velocity rating from 500 t...

Page 2: ...uct by passing through the duct housing Terminal connections shall be of the strip and clamp method suitable for 12 18 AWG wiring Architect Engineer Specifications Voltage Range 15 to 32 VDC Standby Current 300µA 24 VDC one communication every 5 seconds with LED blink enabled Wiring diagram for DH200P Duct Smoke Detector with optional RA400Z Must break tab on back of RA400Z when used with DH200P W...

Page 3: ...ns J1 shunt must be removed for power supervision DH200RP Specifications Alarm auxiliary contacts DPDT 10 A 30 VDC 10 A 277 VAC 0 75 power factor 240 VA 249 VAC 0 4 power factor 1 8 HP 120 VAC 1 4 HP 240 VAC Supervisory contact SPST 2 0 A 30 VDC resistive Minimum switching current for auxiliaty contact must be 500 mA DC minimum 24 VDC Contact Ratings Accessory Current Loads at 24 VDC COM COM COM C...

Page 4: ...1KEY Remote test station w key see below RA400Z Remote LED see below PA400 Mini Alert Sounder see below F36 09 11 Replacement filters M02 04 00 Test magnet P48 21 00 End cap for metal sampling tube P48 55 00 End cap for plastic sampling tube S08 39 01 Replacement photo insect screen T80 71 00 Replacement plastic sampling tube RTS451 Remote Test Station UL S2522 RTS451KEY Remote Test Station with K...

Reviews: