Current Requirements (using no accessories)
Power supply voltage
20-30 VDC
24 VAC, 50-60HZ
120VAC, 50-60Hz
220/240 VAC, 50-60Hz
Max. standby current
26 mA
65 mA RMS
44 mA RMS
25 mA RMS
Max. alarm current
87 mA
182 mA RMS
52 mA RMS
30 mA RMS
Alarm response time
3 to 17 sec.
3 to 17 sec.
3 to 17 sec.
3 to 17 sec.
Power up time
2 sec.
2 sec.
2 sec.
2 sec.
Device
Standby
Alarm
PA400
0 mA
15 mA Max.
RA400Z
0 mA
12 mA Max.
RTS451/RTS451KEY
0 mA
10 mA Max.
Wiring diagram for DH200RP Duct Smoke Detector with optional RA400Z
Wiring diagram for DH200RP Duct Smoke
Detector with RTS451/RTS451KEY
Wiring diagram for DH200RP Duct Smoke Detector with optional PA400
Wiring diagram for DH200RP Duct Smoke Detector using a UL listed control panel
NOTE: Jumper J1 shunt must be installed for non-relay applications. J1 shunt must be removed for power super vision.
DH200RP Specifications
Alarm auxiliar y contacts* (DPDT)
10 A @ 30 VDC
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1/8 HP @ 120 VAC
1/4 HP @ 240 VAC
Super visor y contact (SPST)
2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliaty contact
must be 500 mA DC minimum @ 24 VDC.
Contact Ratings
Accessor y Current Loads at 24 VDC
+
–
COM (+)
COM (-)
COM (+)
COM (-)
COMMUNICATION
LINE
UL LISTED CONTROL
PANEL
1ST DETECTOR
IN LOOP
2ND DETECTOR
IN LOOP
1
2
1
2
J1 JUMPER
J1 JUMPER
5 7
RA400Z
5 = Alarm Signal
7 = Aux. Power (—)
DO NOT BREAK TAB ON RA400Z
ALARM SIGNAL
AUX. POWER (—)
TEST +
TEST —
ALARM SIGNAL
NOT USED
NOT USED
CIRCUIT
REFERENCE
TEST
SWITCH
FOR RTS451, TERMINAL 3 IS NOT
USED. (RTS451 DOES NOT HAVE
A TERMINAL 6.) FOR RTS451KEY,
TERMINALS 3 AND 6 ARE NOT USED.
RTS 451/RTS451KEY
5
7
4
3
1
3
6
2
4
5
5 7
PA400
5 = Alarm Signal
7 = Aux. Power (—)
NOTE: External power of 24V AC/DC
or 120/220 VAC must be connected in
order to power all remote horn or
strobe accessories.