background image

The System Sensor Innovair

DH200 Series photoelectric air duct smoke detectors are

capable of sensing smoke in air velocities from 500 to 4,000 feet per minute (2.54 to
20.32 m/sec).

The DH200 Series Detector samples air currents passing through a duct and gives
dependable performance for shutdown of fans, blowers, and air conditioning systems,
preventing the spread of toxic smoke and fire gases through the protected area.

These intelligent sensors communicate and are continuously monitored through the com-
munication line. Detector sensitivity changes caused by dirt, temperature, or humidity
are reported to the panel, allowing compensation algorithms to maintain the sensor’s set
sensitivity. An advance indication at the panel specifies the sensor address, allowing for
selected maintenance to be performed as needed.

Remote alarm annunciation can be accomplished by using the RA400Z Remote
Annunciator or the RTS451 or RTS451KEY Remote Test Station. Both these devices
allow testing of the detector from a remote location.

The Innovair family is designed for simplified installation and easy maintenance. The
modular construction allows for easy cleaning and uncomplicated field replacement of the
UL recognized power and sensor board

s.

WARNING:

Duct smoke detectors have specific limitations.

DUCT SMOKE DETECTORS ARE:

NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection system.

Refer to NFPA 72 and 90A for additional duct smoke detector application information.

Air velocity rating from 

500 to 4000

feet per minute 

(2.54 to 20.32 m/sec.)

Patented telescopic sampling tube

Easily accessible code wheels

Outside mounting tabs 

Easy and quick mounting to round
or rectangular ducts from 1

–12

(0.3–3.7 meters) wide

Easy to clean

UL recognized field-replaceable 
power and sensor boards

Transparent cover for convenient 
visual inspection

UL 268A listed

3-year warranty

DH200P (non-relay)

Has outputs for remote LED display,
remote test

Incorporates zener diodes to conserve
power for communications to other
devices

Com line power only

DH200RP (with relay) 

Powered outputs for remote LED, remote
test and sounder

Two form “C” auxiliary contacts

Can be configured as a relay version or
jumpered to mimic a non-relay version

Patented cover tamper trouble signal

Requires both com line power and one of
the following: 24VAC/DC or
120/220VAC for operation

Intelligent Models Available

DH200P (non-relay)

DH200RP (with relay)

Product Overview 

Innovair

200 Series

Intelligent 
Duct Smoke Detectors

DH200P

DH200RP

®

Summary of Contents for Innovair 200 Series

Page 1: ... the UL recognized power and sensor boards WARNING Duct smoke detectors have specific limitations DUCT SMOKE DETECTORS ARE NOT a substitute for an open area smoke detector NOT a substitute for early warning detection and NOT a replacement for a building s regular fire detection system Refer to NFPA 72 and 90A for additional duct smoke detector application information Air velocity rating from 500 t...

Page 2: ...uct by passing through the duct housing Terminal connections shall be of the strip and clamp method suitable for 12 18 AWG wiring Architect Engineer Specifications Voltage Range 15 to 32 VDC Standby Current 300µA 24 VDC one communication every 5 seconds with LED blink enabled Wiring diagram for DH200P Duct Smoke Detector with optional RA400Z Must break tab on back of RA400Z when used with DH200P W...

Page 3: ...ns J1 shunt must be removed for power supervision DH200RP Specifications Alarm auxiliary contacts DPDT 10 A 30 VDC 10 A 277 VAC 0 75 power factor 240 VA 249 VAC 0 4 power factor 1 8 HP 120 VAC 1 4 HP 240 VAC Supervisory contact SPST 2 0 A 30 VDC resistive Minimum switching current for auxiliaty contact must be 500 mA DC minimum 24 VDC Contact Ratings Accessory Current Loads at 24 VDC COM COM COM C...

Page 4: ...1KEY Remote test station w key see below RA400Z Remote LED see below PA400 Mini Alert Sounder see below F36 09 11 Replacement filters M02 04 00 Test magnet P48 21 00 End cap for metal sampling tube P48 55 00 End cap for plastic sampling tube S08 39 01 Replacement photo insect screen T80 71 00 Replacement plastic sampling tube RTS451 Remote Test Station UL S2522 RTS451KEY Remote Test Station with K...

Reviews: