background image

UL LISTED

ALARM

CONTROL

PANEL

AUX (+)

PGM 2

PGM 1

+

AUX

AUX

DSC POWER 832

PURPLE

YELLOW

ORANGE

RED

BLACK

BROWN

WHITE

EOL

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

5.6

K

*

*NOTE:

 5.6K

 resistor must be rated for 1/4W or greater. Must be present for panel to reset.

D500-44-00 4 

I56-2203-003 

 

 

© System Sensor 2006

System Sensor warrants its enclosed product to be free from defects in 
materials and workmanship under normal use and service for a period 
of three years from date of manufacture. System Sensor makes no other 
express warranty for the enclosed product. No agent, representative, 
dealer, or employee of the Company has the authority to increase or alter 
the obligations or limitations of this Warranty. The Company’s obliga-
tion of this Warranty shall be limited to the replacement of any part of 
the product which is found to be defective in materials or workman-
ship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s 
toll free number 800-SENSOR2 (736-7672) for a Return Authorization 
number, send defective units postage prepaid to: System Sensor, Returns 

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. 
Please include a note describing the malfunction and suspected cause 
of failure. The Company shall not be obligated to replace units which 
are found to be defective because of damage, unreasonable use, modi-
fications, or alterations occurring after the date of manufacture. In no 
case shall the Company be liable for any consequential or incidental 
damages for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s 
negligence or fault. Some states do not allow the exclusion or limita-
tion of incidental or consequential damages, so the above limitation or 
exclusion may not apply to you. This Warranty gives you specific legal 
rights, and you may also have other rights which vary from state to state.

Three-Year Limited Warranty

Testing

Before testing, notify the proper authorities that the system is 
undergoing maintenance and will temporarily be out of service.

Test in accordance with NFPA 72 test methods, inspections, 
and testing frequency.

1.  Confirm that all smoke detectors connected to the RRS-

MOD module(s) contain a sounder and the sounders are 
activated upon power reversal.

2.  Initiate an alarm with one of the smoke detectors con-

nected to the RRS-MOD module using any approved test 
method. In the alarm state, all the detectors connected to 
the RRS-MOD module must be sounding their sounders.

3.  Reset the system from the control panel. All smoke de-

tector sounders should be silent.

4.  

If the fire alarm panel also functions in burglary, initiate a bur-
glary alarm and ensure the smoke detectors do not sound.

S0108-02

Figure 8. Connecting 2WTA-B smoke detectors to DSC Power 832 con-

trols using RRS-MOD module with PGM output:

Figure 7. Connecting 4WTA-B, 4WTAR-B, and 4WITAR-B smoke detectors 

to DSC Power 832 controls using RRS-MOD module with PGM output:

UL LISTED

ALARM

CONTROL

PANEL

AUX (+)

PGM 2

PGM 1

+

AUX

AUX

ZONE

ZONE (COM)

+

DSC POWER 832

PURPLE

YELLOW

ORANGE

RED

BLACK

BROWN

WHITE

EOL

EOL RELAY

(SHOWN ENERGIZED)

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

5.6

K *

*NOTE:

 5.6K  resistor must be rated for 1/4W or greater. Must be present for panel to reset.

All smoke detectors on the 4-wire fire 
zone will be synchronized in alarm 
and will sound 1 sec ON, 1 sec OFF 
only from a fire alarm event.

NOTE:

•   Program zone section attributes 

for bell output to be pulsing.

•   PGM2 must be programmed for 

sensor reset.

•   PGM1 must be programmed as 

Burglary and Fire Bell Output (01) 
with ON, ON, OFF attributes.

•  

RRS-MOD switch must be set to 
OFF (factory default setting).

All smoke detectors on the 2-wire fire 
zone will be synchronized in alarm, 
and will sound 1 sec ON, 1 sec OFF 
only from a fire alarm event.

NOTE:

•  

Program zone section attributes 
for bell output to be pulsing.

•   PGM2 must be programmed for 

2-wire smoke zone (04). Jumper 
J1 on the main board must be 
removed.

•   PGM1 must be programmed as 

Burglary and Fire Bell Output (01) 
with ON, ON, OFF attributes.

•   RRS-MOD switch must be set to 

OFF (factory default setting).

Connection diagrams with DSC Power 832 Panels

S0107-02

Summary of Contents for i3 Series

Page 1: ...ohol mixture 50 50 to clean the mounting surface Allow surface to dry and remove paper backing from the Velcro and catch Stick the Velcro in the panel and the catch on the back of the module then mount the module inside the control panel Route terminals to the appropriate termi nals as noted below WARNING When calculating total current draw of the control panel remember to add current consumption ...

Page 2: ...UX POWER OR DETECTOR POWER INITIATING DEVICE CIRCUIT BELL ALARM CIRCUIT positive signal in alarm state PURPLE T YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT 1 IN 2 OUT 3 IN OUT 4 N O 5 C 1 IN 2 OUT 3 IN OUT 4 N O 5 C ALARM RELAY NO Contact UL LISTED ALARM CONTROL PANEL 2 WIRE INITIATING DEVICE CIRCUIT PURPLE T AUX POWER YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT EOL OPT...

Page 3: ...T 4 RA 5 C 470Ω 1 2 WATT RESISTOR NEEDED FOR PANEL TO RESET D500 44 00 3 I56 2203 003 S0104 00 Figure 4 4 Wire system triggered from alarm relay contact UL LISTED ALARM CONTROL PANEL DETECTOR POWER AUX POWER OR DETECTOR POWER INITIATING DEVICE CIRCUIT ALARM RELAY NO Contact PURPLE T YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT EOL EOL RELAY SHOWN ENERGIZED 1 IN 2 OUT 3 IN OUT 4 N O 5 ...

Page 4: ...efore testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Test in accordance with NFPA 72 test methods inspections and testing frequency 1 Confirm that all smoke detectors connected to the RRS MOD module s contain a sounder and the sounders are activated upon power reversal 2 Initiate an alarm with one of the smoke detectors con nec...

Reviews: