D200-101-00
9
I56-3888-105
Either replace the filter assembly or carefully brush off the
accumulated dust.
Note:
If replacing the filter, remove the foam gasket from the old
filter and place onto the new filter. When placing the new filter into
the slot, ensure that the gasket is correctly aligned.
Refit the filter, close and secure the cabinet door. The unit will
initialise and restart.
Smoke Sensors
The smoke sensors are located under the sensor cover (see Figure
9 displayed earlier in the guide). To access the sensors, follow the
sequence below:
Do
NOT
interchange the devices and do
NOT
alter the rotary
address switch settings on the sensors. If replacing a sensor,
ensure that the address set on the new sensor is the same as on
the sensor being replaced.
LASER SAFETY INFORMATION
The detector contains a Class 1 laser product. Radiation emitted
inside the smoke sensor is completely contained within its housings
and protective covers during all phases of operation.
WARNING
Using compressed air to clean the pipe system
High pressure air flushed through the system could damage
the fan, ensure that the FAAST LT unit is sealed or detached
from the system before commencing this procedure.
USB CONNECTION
PC connectivity is provided by an on board USB
B
socket located
centrally between the filter and the sensor cover (see Figure 9
displayed earlier in the guide). The USB interface allows access to
a range of additional options via the PipeIQ 2 application software
running on a PC.
Configuring Other Options
To change any of the default options, it will be necessary to connect
the detector to a PC/laptop with the PipeIQ 2 software installed;
see the
FAAST LT Advanced Setup and Control Guide
for further
information.
Note: The USB connecting cable should be removed during
normal operation
.
1
2
3
System Sensor Europe
Pittway Tecnologica S.r.l.
Via Caboto 19/3
34147 TRIESTE
Italy
EN54-20 : 2006
Class A B & C
Aspirating Smoke Detectors
0832 12
FL0111E: DOP-ASP006
FL0112E: DOP-ASP007
FL0122E: DOP-ASP008
System Sensor Europe
Pittway Tecnologica S.r.l.
Via Caboto 19/3,
34147 Trieste, Italy
DoP Ref:
4