Either  replace  the  filter  assembly  or  carefully  brush  off  the 

accumulated dust.

Note:

 If replacing the filter, remove the foam gasket from the old 

filter and place onto the new filter. When placing the new filter into 

the slot, ensure that the gasket is correctly aligned.

Refit  the  filter,  close  and  secure  the  cabinet  door.  The  unit  will 

initialise and restart.

Smoke Sensors

The smoke sensors are located under the sensor cover (see Figure 

9 displayed earlier in the guide). To access the sensors, follow the 

sequence below:

Do 

NOT

 interchange the devices and do 

NOT

 alter the rotary 

address  switch  settings  on  the  sensors.    If  replacing  a  sensor, 

ensure that the address set on the new sensor is the same as on 

the sensor being replaced. 

LASER SAFETY INFORMATION

The detector contains a Class 1 laser product. Radiation emitted 

inside the smoke sensor is completely contained within its housings 

and protective covers during all phases of operation.

WARNING

Using compressed air to clean the pipe system

High pressure air flushed through the system could damage 

the fan, ensure that the FAAST LT unit is sealed or detached 

from the system before commencing this procedure.

 

USB CONNECTION

PC connectivity is provided by an on board USB 

B

 socket located 

centrally  between  the  filter  and  the  sensor  cover  (see  Figure  9 

displayed earlier in the guide). The USB interface allows access to 

a range of additional options via the PipeIQ 2 application software 

running on a PC.

Configuring Other Options

To change any of the default options, it will be necessary to connect 

the detector to a PC/laptop with the PipeIQ 2 software installed; 

see the 

FAAST LT Advanced Setup and Control Guide

 for further 

information.

Note: The USB connecting cable should be removed during 

normal operation

.

1

2

3

System Sensor Europe

Pittway Tecnologica S.r.l. 

Via Caboto 19/3

34147 TRIESTE

Italy

EN54-20 : 2006

Class A B & C

Aspirating Smoke Detectors

0832  12

FL0111E:  DOP-ASP006

FL0112E:  DOP-ASP007

FL0122E:  DOP-ASP008

System Sensor Europe

Pittway Tecnologica S.r.l. 

Via Caboto 19/3,

34147 Trieste, Italy

DoP Ref:

4

Summary of Contents for FAAST LT FL01 Series

Page 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Page 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Page 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Page 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Page 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Page 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Page 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Page 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Page 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...