background image

D200-101-00

3

I56-3888-105

Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket

Pipe Installation

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1

7 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

99 mm

41

1

2

mm

90 mm

4

3

0.00

o

5

329 mm

6

7

7a

7b

7c

7d

8

9

2

1

Pipe Hole Configuration

Figure 8

 below shows the pipe holes available on the unit. Each 

unit has 2 pipe holes per channel connected together like a T-Piece. 

If using a 1 channel unit, holes 3 and 4 do not function. Use 

Table 

1

 to locate the holes required for the installation:

Figure 8: Pipe Holes

FAAST LT MODEL 

INLET PIPE HOLE 

OUTLET PIPE HOLE 

FL0111E 

1 and / or 2 

FL0112E 

1 and / or 2 

FL0122E 

Channel 1 ‐ 1 and / or 2 

Channel 2 – 3 and / or 4 

 

Table 1: Pipe Holes Used for Each FAAST LT Model

Note 1:

 Pipe holes not used should be kept sealed.

Note 2:

 Do 

NOT

 glue pipes into the pipe holes.

Table 1a: Maximum Number of Pipe Holes Allowed Per Channel 

All figures quoted using highest (level 1) sensitivity

1

2

3

4

5

6

CHANNEL 1

CHANNEL 2 (ONLY FUNCTION 

ON 2 CHANNEL UNITS)

CHANNEL 1 (NOT 

USED FOR COMMON 

CHAMBER UNIT) 

CHANNEL 2 (ONLY 

FUNCTIONS ON 2 

CHANNEL AND COMMON 

CHAMBER UNITS)

CLASS  PIPE LENGTH 

(m) 

MAX NUMBER OF HOLES PER 

CHANNEL 

100 

18 (5 x 2mm, 6 x 2.5mm, 3 x 3mm, 

3 x 3.5mm and 1 x 4mm) + 4mm 

non sensing end hole 

160 (2 x 80) 

Using T‐Piece 

9 holes per branch (3 x 2.5mm, 6 x 

3mm) + 3mm non sensing end hole 

100 

6 (2 x 3.5mm, 2 x 4mm, 2 x 5mm 

inc end hole) 

80 

3 (1 x 5mm, 2 x 6mm inc end hole) 

 

Summary of Contents for FAAST LT FL01 Series

Page 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Page 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Page 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Page 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Page 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Page 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Page 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Page 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Page 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...

Reviews: