background image

FIGURE 7. MULTIPLE FAN SHUTDOWN 

(INTERCONNECTION OF DUCTSD240’S):

DETECTOR 1

240 VAC

DUCTSD240

DUCTSD240

C, AUX A

NC, AUX A

30

DET.   

MAX.

INT/AUX–

INT+

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

DETECTOR 2

240 VAC

C, AUX A

NC, AUX A

INT/AUX–

INT+

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

[10.1] IMPORTANT INTERCONNECTION NOTES:

•  When using the interconnect feature, all interconnected units must be 

powered using the same independent supply.

•   

Polarity must be maintained throughout the interconnect wiring. 
Connect the INT+ terminal on unit 1 to the INT+ terminal on unit 2 
and so on. Similarly, connect the INT/AUX- terminal on unit 1 to the 
INT/AUX- terminal on unit 2 and so on.

•  Up to 30 DUCTSD240 units may be interconnected.

•  A combination of DUCTSD240 and D4240 units may be interconnected 

up to a maximum of 30 units.

NOTE: Alarm can be reset only at the initiating device and not at the devices 
interconnected.

[11] VERIFICATION OF OPERATION

[11.1] POWERING THE UNIT

Apply 24 VDC power to 9 and 10 terminals on the power board or apply 240 
VAC on terminals named 240VAC. See Figure 7 and electrical specifications 
for details.

[11.2] PERFORM DETECTOR CHECK

VERIFY STANDBY AND TROUBLE TEST per Table 3 on page 7. The use of a 
remote accessory for visible indication of power and alarm is recommended.

[11.3] SENSITIVITY VERIFICATION

The sensitivity of the sensor is confirmed to be operating within its allowable 
range each time the sensor LEDs blink green every 5 seconds. Note in a main-
tenance condition, the sensor LEDs will blink red every 5 seconds as depicted 
in 

Table 3 

on page 7. The maintenance condition indicates that the sensor is 

operating outside its original factory preset sensitivity and shall be cleaned or 
replaced. Replacement 2D51 sensors are available as a separate item. See Sec-
tion 9 for reference. This is a valid UL test.

[11.4] DETECTOR TESTING AND MAINTENANCE PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service. Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[11.4.1] SMOKE RESPONSE TESTS

Option 1: Utilize smoke test port as described in Table 2 below.

Option 2: To determine if smoke is capable of entering the sensing chamber, 
visually identify any obstructions. Plug the exhaust and sampling tube holes 
to prevent ducted air from carrying smoke away from the detector head, then 
blow smoke such as cigarette, cotton wick, or punk directly at the head to 
cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR 
THE DETECTOR WILL NOT FUNCTION PROPERLY.

FIGURE 8. MULTIPLE FAN SHUTDOWN (INTERCONNECTION OF 

DUCTSD240 TO D4240):

D4240

D4240

DUCTSD240

DUCTSD240

DUCTSD240

H0640-01

H0639-01

ALARM TEST 

OPTIONS

TEST METHOD

DETECTOR RESET

Test/Reset 
Button

Press and hold test/reset button 
for at least 7 seconds

Press and release the 
test/reset button

Magnet Test 
(M02-04-00)

Place magnet on sensor cover in 
designated location for 5 seconds

Press and release the 
test/reset button

Remote Test 
Accessory

Red LED on sensor and ac-
cessory will latch on: verify 
control panel alarm status and 
execution of all intended aux-
iliary functions (i.e. fan shut-
down, damper control, etc.)

Reset at accessory, at 
system control panel, 
quick press and release 
the test/reset button

Smoke Test 
Port

1. Put detector into Speed-Up 
Test mode

Press and release the 
test/reset button

a. Press and hold Test/Reset 
button for 2 to 7 seconds

b. When in Speed-Up Test 
mode sensor LEDs will alter-
nately flash Red and Green

2.  Lift tethered plug sealing the 
smoke test port via pull tab

3.  Spray canned smoke into the 
test port

4.  After test complete, tethered 
plug MUST be reinserted

[11.4.2] SMOKE ENTRY USING AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described in Section 7.1.

Drill a 

1

4

 inch hole 3 feet upstream from the duct smoke detector. With the air 

handler on, measure the air velocity with an anemometer. Air speed must be 
at least 100 FPM. Spray aerosol smoke* into the duct through the 

1

4

 inch hole 

for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 
duct smoke detector alarms, air is flowing through the detector. Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 
chamber and reset the duct smoke detector. Use duct tape to seal the aerosol 
smoke entry hole.

*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke De-
tector Tester model CHEK02 and CHEK06 available from SDi.  When used 
properly, the canned smoke agent will cause the smoke detector to go into 
alarm.  Refer to the manufacturer’s published instructions for proper use of 
the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer.  Misuse or overuse to these products may have long term ad-
verse effects on the smoke detector.  Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.

[11.5] INSTALL THE COVER

Install the covers making sure that the cover fits into the base groove. Tighten 
the seven screws that are captured in the covers.

TABLE 2.

  

I56-4260-002R 

 

 06-10

Summary of Contents for DUCTSD240

Page 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Page 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Page 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Page 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Page 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Page 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Page 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Page 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Reviews: