background image

FIGURE 3. AIR DUCT DETECTOR SAMPLING TUBE

SAMPLING TUBE ENDCAP

ARROW MUST FACE 

INTO AIR FLOW

AIR FLOW 

DIRECTION

H0551-00

CAUTION:

 The sampling tube end cap, included with the detector, is criti-

cal to proper operation of the duct smoke detector. The end cap is needed to 
create the proper air flow to the sensor of the duct smoke detector. Once any 
sampling tube length adjustments are made, plug the end of the sampling tube 
with the provided end cap.

A plastic exhaust tube is included with the unit. Install into the housing con-
nection that is downstream from the sampling tube connection. The exhaust 
tube can be installed from the front of the detector or the back. A longer 1 
foot exhaust tube, model ETX, is available as an accessory in cases where the 
molded exhaust tube does not extend at least 2 inches into the duct.

[5.2] SAMPLING TUBE INSTALLATION

1.   For tubes shorter than the width of the duct, slide the sampling tube, 

with installed end cap, into the housing connection that meets the air-
flow first. Position the tube so that the arrow points into the airflow as 
shown in Figure 3. Per NFPA sampling tubes over 3 feet long should be 
supported at the end opposite of the duct detector. In ducts wider than 8 
feet, work must be performed inside the duct to couple the other section 
of the sampling tube to the section already installed using the ½-inch 
conduit fitting supplied. Make sure that the holes on both sections of the 
air inlet sampling tube are lined up and facing into the airflow.

2.   For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct. Drill a ¾-inch hole in the duct op-
posite the hole already cut for the sampling tube. Ensure that the sam-
pling tube is angled downward from the duct smoke detector to allow for 
moisture drainage away from the detector. The sampling tube should be 
angled at least ¼˝ downward for every 12˝ of duct width per Figure 4. 
There should be 10 to 12 holes spaced as evenly as possible across the 
width of the duct. If there are more than 2 holes in the section of the tube 
extending out of the duct, select a shorter tube using Table 1. Otherwise, 
trim the tube to leave approximately 1 to 2 inches extending outside the 
duct. Plug the end with the end cap and tape closed any holes in the 
protruding section of the tube. Be sure to seal the duct where the tube 
protrudes.

FIGURE 4.

DETECTOR

3

/

4

˝

HOLE

12˝

1

/

4

˝

H0215-00

NOTE: Air currents inside the duct may cause excessive vibration, especially 
when the longer sampling tubes are used. In these cases, a 3-inch floor flange 
(available at most plumbing supply stores) may be used to fasten the sam-
pling tube to the other side of the duct. When using the flange/connector 
mounting technique, drill a 1 to 1¼-inch hole where the flange will be used.

[5.3] MODIFICATIONS OF SAMPLING TUBES

There may be applications where duct widths are not what is specified for the 
installation. In such cases, it is permissible to modify a sampling tube that is 
longer than necessary to span the duct width.

Use a 0.193 inch diameter (#10) drill and add the appropriate number of holes 
so that the total number of holes exposed to the air flow in the duct is 10 to 12. 
Space the additional holes as evenly as possible over the length of the tube.

CAUTION:

 This procedure should only be used as a temporary fix. It is not 

intended as a permanent substitute for ordering the correct length tubes.

[5.4] REMOTE SAMPLING TUBE INSTALLATION

The detector arrangement can also incorporate the remote mounting of the 
sampling tube and/or exhaust tube. In this case both the detector, sampling 
tube and exhaust tube (if included) should be rigidly mounted to withstand 
the pressure and vibrations caused by the air velocity. The location of the 
detector’s sampling tube should be such that there is uniform airflow in the 
cross section area. 

Pressure differential across the sampling and exhaust ports in the detector 
housing shall be verified to be between 0.01 and 1.11 inches of water. Do so 
by measuring the pressure difference between the inlet and outlet ports on the 
detector housing using a manometer as described in Section 6 Measurement 
Tests.

[6] MEASUREMENT TESTS

[6.1] AIR FLOW

The DNRA is designed to operate over an extended air speed range of 100 to 
4000 FPM. To verify sufficient sampling of ducted air, turn the air handler on 
and use a manometer to measure the differential pressure between the two 
sampling tubes. The differential pressure should measure at least 0.01 inches 
of water and no more than 1.11 inches of water. Because most commercially 
available manometers cannot accurately measure very low pressure differen-
tials, applications with less than 500 FPM of duct air speed may require one 
of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer 
Series 607) or 2) the use of aerosol smoke, see below for test descriptions.

FIGURE 5. PROCEDURE FOR VERIFYING AIR FLOW

 

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE
TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

 

H0163-01

[6.2] LOW FLOW AIR FLOW TEST USING DWYER SERIES 607 

DIFFERENTIAL PRESSURE TRANSMITTER 

Verify the air speed of the duct using an anemometer. Air speed must be 
at least 100 FPM. Wire the Dwyer transmitter as shown in Figure 5. Con-
nect the leads of the meter to either side of the 1000

Ω

 resistor. Allow unit to 

warm up for 15 seconds. With both HIGH and LOW pressure ports open to 
ambient air, measure and record the voltage drop across the 1000

Ω

 resistor 

(measurement 1), 4.00 volts is typical. Using flexible tubing and rubber stop-
pers, connect the HIGH side of the transmitter to the sampling tube of the duct 
smoke detector housing, and the LOW side of the transmitter to the exhaust 
tube of the duct smoke detector housing. Measure and record the voltage drop 
across the 1000

Ω

 resistor (measurement 2). Subtract the voltage recorded in 

measurement 1 from the voltage recorded in measurement 2. If the difference 
is greater than 0.15 volts, there is enough air flow through the duct smoke 
detector for proper operation.

  

I56-3104-004 

 

 4/18/2019

Summary of Contents for DNRA

Page 1: ...detector head installation manual for electrical specifications To determine applicable sensor head use the Base Sensor Cross Reference chart at www systemsensor com available on the Tools menu TABLE OF CONTENTS PAGE 1 Limitations of Duct Smoke Detectors 1 2 General Description 1 3 Contents of the Duct Smoke Detector Kit 1 4 Detector Installation 2 6 Measurement Tests 3 7 Field Wiring Installation...

Page 2: ...e saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 3 2 FOR SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at four target centers two A for sampling tubes and two C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes us ing a 13 8 inch hole saw or punc...

Page 3: ...than necessary to span the duct width Use a 0 193 inch diameter 10 drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube CAUTION This procedure should only be used as a temporary fix It is not intended as a permanent substitute for ordering the corr...

Page 4: ...repair 8 4 DUCT SMOKE DETECTOR TEST MAINTENANCE PROCEDURES Test and maintain duct smoke detectors as recommended in CAN ULC S536 The tests contained in this manual were devised to assist maintenance person nel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone o...

Page 5: ...RA REMOTE ALARM LED OPTION 1 PER UNIT H0570 05CDN Note Remove jumper when using RA100ZA with the intelligent duct smoke detector The RTS151 RTS151KEY A Remote Test Station facilitates test of the alarm ca pability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The DNRA duct smoke detector must be reset by the system control panel 11...

Page 6: ...of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss or damage is caused by the C...

Reviews: