background image

Light  sources  of  extreme  intensity  such  as  sunlight  and  hal-
ogen  lamps,  if  directed  at  the  receiver,  can  cause  a  dramatic 
signal change resulting in fault and alarm signals. To prevent 
this  problem  direct  sunlight  into  the  transmitter/receiver 
unit  should  be  avoided.  There  should  be  a  minimum  of  10° 
between  the  pathway  of  the  light  source  and  detector  and 
the line of sight between detector and reflector.

Operation  of  the  detector  through  panes  of  glass  should 
be  avoided.  Since  single  ended  beam  detectors  operate  on 
a  reflection  principle,  a  pane  of  glass  perpendicular  to  the 
line  of  sight  between  the  detector  and  the  reflector  can 
reflect  the  light  beam  from  the  transmitter  to  the  receiver. 
If  this  occurs,  the  detector  will  not  be  able  to  distinguish 
these  reflections  from  those  of  the  reflector  and  the  pro-
tected space will be compromised. 

Panes  of  glass  will  also  absorb  some  of  the  light  as  it  passes 
through it. This absorption of light will reduce the acceptable 
installed distance between the detector and the reflector.

In  cases  where  operation  through  panes  of  glass  cannot  be 
avoided  some  specific  installation  practices  can  help  to  mini-
mize  the  effects  of  the  glass.  These  practices  include:  avoid 
penetration  of  multiple  panes  of  glass,  position  the  glass  so 
that  it  is  not  perpendicular  to  the  line  of  sight  between  the 
detector  and  the  reflector,  (A  minimum  of  10°  off  perpen-
dicular  should  be  considered),  and  make  certain  that  the 
glass  is  smooth,  clear  and  mounted  securely.  The  complete 
reflector  blockage  test  can  be  used  to  determine  if  the  instal-
lation  is  acceptable.  See  Testing  and  Maintenance  Section  of 
this manual.

Where  high  ceilings  (in  excess  of  30  feet  or  9.1  meters)  are 
present  additional  beams  may  be  required  to  detect  smoke  at 
lower  levels.  See  System  Sensor’s  Projected  Beam  Detector 
Applications Guide for futher explanation.

Wiring Installation Guidelines

Always install all wiring in compliance with the Canadian Electrical 
Code, and/or the applicable local codes, and any special require-
ments of the local authority having jurisdiction. Proper wire gauges 
and suitable means for strain relief should be used. The conduc-
tors used to connect beam smoke detectors to control panels and 
accessory devices should be color-coded to reduce the likelihood 
of wiring errors. Improper connections can prevent a system from 
responding properly in the event of a fire.

Installation wire used for the beam detector shall be no smaller 
than  22  AWG  (1.0  mm

2

).  For  best  system  performance,  all  wir-

ing  should  be  twisted  pair  and  installed  in  separate  grounded 
conduit.  Do  NOT  mix  fire  system  wiring  in  the  same  conduit 
as  any  other  electrical  wiring.  Shielded  cable  may  be  used  to 
provide additional protection against electrical interference.

When installing the beam smoke detector in applications where 
the  head  unit  will  be  mounted  to  either  a  wall  or  the  ceiling 
using  the  multi-mount  kit  (BEAMMMK)  flexible  conduit  will  be 
used.  The  surface  mount  kit  (BEAMSMK)  and  multi-mount  kit 
(BEAMMMK) must be installed with the cable before wring the 
unit, according to the instructions supplied with the kit.

When the detector has been mounted over a recessed junction 
box,  all  wiring  should  be  routed  out  of  the  box  and  behind 
the detector to the bottom of the detector where the terminal 
blocks  are  located.  When  installing  the  wiring  in  the  junction 
box be sure to leave enough wire in the box to connect to the 
terminal  blocks.  (Approximately  9″  [23cm)  of  wire  outside  of 
the  junction  box  will  be  required  for  proper  installation).  All 
wiring  to  the  detector  is  done  via  pluggable  terminal  blocks. 
In  order  to  properly  make  electrical  connections  strip  approxi-
mately 

1

/

4

″  (6mm)  of  insulation  from  the  end  of  the  wire,  slid-

ing the bare end of the wire under the clamping plate screw. 

Figure 6 shows all the wiring connections to the transmitter/receiver 
unit. Figure 7 shows the proper wiring diagram for either class A or 
class B operation. Figure 8 shows the connections that are neces-
sary when using one of the optional remote test stations (RTS451 
or RTS451KEYA). Figure 9 shows the remote outputs for trouble 
and alarm.

Figure 6. Wiring Connections at Detector

POWER OUT (

–)

POWER OUT (+)

POWER IN (

–)

POWER IN (+)

RESET I NPUT

TEST INPUT

AUX (

–)

REMOTE ALARM OUT

Not used

REMOTE TROUBLE OUT

TROUBLE COM

TROUBLE N.C.

ALARM COM

ALARM N.O.

ALARM COM

ALARM N.O.

T3

T2

T1

T4

C0271-00

D400-73-00 

I56-2541-00R

Summary of Contents for BEAM1224A

Page 1: ... Remote Test and Reset Switch Capability compatible with RTS451 RTS451KEYA Indicators Alarm Remote Output Local LED red Trouble Remote Output Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green once every 5 sec Alignment Aids Optical Gunsight coarse adjustment 00 to 99 Digital Display fine adjustment Relays Alarm Trouble Sensitivity Digital Displa...

Page 2: ...atches and can be reset by a momentary power interruption by using the remote reset input to the detector if using the remote test reset station model RTS451 or with the local reset button located on the detector The local reset button is accessible by removing the outer paintable trim ring The yellow LED will blink in specific patterns to provide a diagnostic aid when diagnosing the cause of a tr...

Page 3: ...r additional alignment range in cases where the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits ar...

Page 4: ...is 30 ft 9 1m See Figure 2 Figure 1 Spacing for smooth ceiling side view 1 2 S S 12 18 in 0 3 0 46m WAL L C0254 00 Figure 2 Spacing for smooth ceiling top view 16 ft 5m Mini mum 328 ft 100m Maximum Tx Rx Reflector S Tx Rx Reflector 1 2 S Maximum 1 4 S Max C0255 00 In the case of peaked or sloped ceilings codes may specify spacing of detectors by using horizontal spacing from the peak of the roof o...

Page 5: ...ould be used to provide a secure mounting The reflector must be mounted such that it is within 10 in both the X and Y planes of the transmitter receiver unit See Figure 5a The reflector must also be mounted such that plane of the reflector is perpendicular to the optical line of sight to the transmitter receiver unit The maximum tolerance for non perpendicular mounting locations is 10 See Figure 5...

Page 6: ...gauges and suitable means for strain relief should be used The conduc torsusedtoconnectbeamsmokedetectorstocontrolpanelsand accessory devices should be color coded to reduce the likelihood of wiring errors Improper connections can prevent a system from responding properly in the event of a fire Installation wire used for the beam detector shall be no smaller than 22 AWG 1 0 mm2 For best system per...

Page 7: ...BEAM1224 SA Alarm Signal Circuit Note 1 T2 1 T3 3 T2 2 Yel low Note 1 See electrical r atings section of this manual f or circuit output r atings Power In Power In Red Tro uble Signal Circuit Note 1 C0319 00 WARNING Disable the zone or system before applying power tothebeamdetectortopreventunwantedalarms Whenapplyingpowertothebeamdetectorbefore the alignment procedure has been completed the detect...

Page 8: ...here are no external gain settings on the detector that must be set by the operator Periodically throughout the fine adjustment step the detector will need to re adjust its electronic amplifier gain setting When this occurs it will be indicated by the dual digital readout as When this occurs cease any further adjustment until the display again reads a number value 1 Insure that neither you nor any...

Page 9: ...in to blink This indicates that the detector is adjusting the electronic gain setting Once complete the yellow LED will stop blinking and the green LED will begin blinking This indicates that the gain adjustment was successful Note Use caution not to block the line of sight between the detector and reflector in this step 4 Install the outer aesthetic ring by snapping it onto the outer housing Note...

Page 10: ...torisnot inthefineadjustmentstepofthealignmentmode indicatedby the illumination of the dual digital display To set the sensitiv ity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read thecurrentsensitivitysettinginpercentobscuration Tochange the sensitivity continue to depress the sensitivity switch until the desired setting...

Page 11: ...an be tested using an opaque material to cover the reflector by an amount indi cated by the graduated scale on the reflector Due to the high optical efficiency of the reflector the selection of the opaque material used to block the reflector is not critical Acceptable materials include but aren t limited to this manual or the cardboard packaging inserts Refer to Figure 14 for this procedure 1 Veri...

Page 12: ...n of beam type detectors For the BEAM1224SA this test in conjunction with the complete reflec tor blockage test see step 4 of the Installation Alignment pro cedure in this manual does satisfy the requirements of NFPA72 and orULCforperiodicmaintenanceandsensitivityverification of beam type detectors Ifthedetectorfailsthistestseveralstepsshouldbetakentodeter mine if the detector is faulty or simply ...

Page 13: ...d Signal Open OFF Open ON Inspect line of sight between detector and reflector for reflective objects in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Off Off Beam Blockage Open OFF Open ON Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Off Off Beam Blockage Close OFF Open ON Remove blockage Faulty unit Initialization Power on Off Bli...

Page 14: ...D400 73 00 14 I56 2541 00R ...

Page 15: ...Appendix II Detector Drilling Template 4 345 6 190 Scale 1 1 D400 73 00 15 I56 2541 00R ...

Page 16: ...D400 73 00 16 I56 2541 00R ...

Page 17: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 73 00 17 I56 2541 00R ...

Page 18: ...ssordamageiscausedbytheCompany snegligenceorfault Somestates donotallowtheexclusionorlimitationofincidentalorconsequentialdamages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operati...

Reviews: