background image

D150-05-00               REV #: 003 

I56-1028-000

 

 

 © System Sensor 1997

Three-Year Limited Warranty

System  Sensor  warrants  its  enclosed  smoke  detector  base  to  be  free 
from defects in materials and workmanship under normal use and 
service for a period of three years from date of manufacture. System Sen-
sor makes no other express warranty for this smoke detector 
base. No agent, representative, dealer, or employee of the Company has 
the authority to increase or alter the obligations or limitations of this War-
ranty. The Company’s obligation of this Warranty shall be limited to the 
repair or replacement of any part of the smoke detector base which is 
found to be defective in materials or work
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll 
free number 800-SENSOR2 (736-7672) for a Return Authorization num-
ber, send defective units postage prepaid to: System Sensor, Repair De-

partment, RA #__________, 6581 Kitimat Rd., Unit #6, Mississauga, ON, 
L5N 3T5. Please include a note describing the malfunction and suspected 
cause of failure. The Company shall not be obligated to repair or replace 
units which are found to be defective because of damage, unreasonable 

use, modifications, or alterations occurring after the date of manufacture. 

In no case shall the Company be liable for any consequential or incidental 
damages for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s neg-
ligence or fault. Some legislations do not allow the exclusion or limitation 
of incidental or consequential damages, so the above limitation or exclu-

sion may not apply to you. This Warranty gives you specific legal rights, 

and you may also have other rights which vary under common law.

The smoke detector used with this base is designed to 

activate and ini-

tiate

 emergency action, but will do so only when it is used in conjunction 

with an authorized fire alarm system. This detector must be installed in 

accordance with CAN/ULC-S524.

Smoke  detectors  will  not  work  without  power. 

AC  or  DC  powered 

smoke detectors will not work if the power supply is cut off.

Smoke detectors will not sense fires which start where smoke does 
not reach the detectors.

 Smoldering fires typically do not generate a lot 

of heat which is needed to drive the smoke up to the ceiling where the 
smoke detector is usually located. For this reason, there may be large 

delays in detecting a smoldering fire with either an ionization type detec

-

tor or a photoelectric type detector. Either one of them may alarm only 

after flaming has initiated which will generate the heat needed to drive the 

smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs or on the other side of a 

closed door(s) may not reach the smoke detector and alarm it. A detector 

cannot detect a fire developing on another level of a building quickly or at 

all. For these reasons, detectors 

shall be located on every level and in 

every bedroom within a building.

Smoke detectors have sensing limitations, too.

 Ionization detectors 

and photoelectric detectors are required to pass fire tests of the flaming 

and smoldering type. This is to ensure that both can detect a wide range 

of types of fires. Ionization detectors offer a broad range of fire sensing 
capability but they are somewhat better at detecting fast flaming fires than 
slow smoldering fires. Photoelectric detectors sense smoldering fires bet

-

ter than flaming fires which have little, if any, visible smoke. Because fires 

develop in different ways and are often unpredictable in their growth, nei-
ther type of detector is always best, and a given detector may not always 

provide early warning of a specific type of fire.

In  general,  detectors  cannot  be  expected  to  provide  warnings  for  fires 
resulting  from  inadequate  fire  protection  practices,  violent  explosions, 
escaping gases which ignite, improper storage of flammable liquids like 

cleaning solvents which ignite, other similar safety hazards, arson, smok-
ing in bed, children playing with matches or lighters, etc. Smoke detectors 
used  in  high  air  velocity  conditions  may  have  a  delay  in  alarm  due  to 
dilution of smoke densities created by frequent and rapid air exchanges. 
Additionally,  high  air  velocity  environments  may  create  increased  dust 
contamination, demanding more frequent maintenance.

To keep your equipment in excellent working order, ongoing mainte-
nance is required per the manufacturer’s recommendations and ULC 
standards.  At a minimum, the requirements of the National Fire Alarm 
Code, shall be followed.  A preventative maintenance agreement should 
be arranged through the local manufacturer’s representative.  Though 
smoke detectors are designed for long life, they may fail at any time.  

Any smoke detector, fire alarm equipment or any component of that 

system which fails shall be repaired or replaced as soon as possible.

WARNING

The Limitations of Property Protection Smoke Detectors

Summary of Contents for B110LPA

Page 1: ...age 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Maximum at 100 mA Alarm current must be limited to 100 mA by the control panel If it is used the RA400ZA Remote Annunciator operates within the specified detector alarm currents Reset Voltage 2 5 ...

Page 2: ...tighten the terminal screw Check the zone wiring before installing the smoke detec tor head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electrical box position the shorting spring against ter minal 3 Use the slot in the retaining clip to hold the spring against the terminal as shown in Figure 1 This shorts the negative in and neg...

Page 3: ...2 WIRE CONTROL PANEL E O L CLASS A OPTIONAL WIRING A78 1175 04 Figure 2 Wiring diagram for a typical 2 wire detector system Figure 3A Activating the tamper resistance feature PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE USE SMALL BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW A78 1175 03 Figure 3B Removing detector head from base ...

Page 4: ... the smoke detector is usually located For this reason there may be large delays in detecting a smoldering fire with either an ionization type detec tor or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed do...

Reviews: