background image

D150-05-00               REV #: 003 

I56-1028-000

ate  correctly  if  system  components  have  incompatible 

allowable  loop  resistances.Therefore,  before  beginning 

installation, refer to the control panel manufacturer’s loop 

resistance specification to ensure that it is listed as com

-

patible with the System Sensor base and smoke detector 

being installed.

Connect detectors only to ULC compatible control units.

All wiring must be installed in compliance with the National 

Electrical Code and all applicable local codes and any spe-

cial  requirements  of  the  authority  having  jurisdiction,  us-

ing the proper wire size. The conductors used to connect 

smoke detectors to control panels and accessory devices 

should  be  color-coded  to  reduce  the  likelihood  of  wiring 

errors. Improper connections can prevent a system from 

responding properly in the event of a fire.

For  signal  wiring  (the  wiring  between  interconnected  de-

tectors),  it  is  recommended  that  the  wire  be  no  smaller 

than AWG  18.  However,  the  screws  and  clamping  plate 

in the base can accommodate wire sizes up to AWG 12. 

The use of twisted pair wiring for the power (+ and -) loop 

is recommended to minimize the effects of electrical inter-

ference.

NOTE:

  To  ensure  that  electrical  connections  are  super-

vised, do NOT loop wires under terminals 2, 3, and 

5 - break the wire at each terminal.

To make electrical connections, strip approximately 3/8" (1 

cm) insulation from the end of each wire. Slide the wires 

under the clamp plate and tighten the terminal screw.

Check the zone wiring before installing the smoke detec-

tor head. The built-in shorting spring makes it convenient 

to do this. After the detector base is wired and attached to 

the electrical box, position the shorting spring against ter-

minal 3. Use the slot in the retaining clip to hold the spring 

against the terminal, as shown in Figure 1. This shorts the 

negative-in and negative-out leads so that loop wiring can 

be tested for continuity.

The shorting spring in the base will disengage automati-

cally when the detector head is removed from the base. 

DO NOT remove the shorting spring since it reengages as 

the detector head is turned into the base, completing the 

circuit.

Tamper-resistance Feature

NOTE:

 DO NOT use the tamper-resistance feature if the 

System Sensor XR2 Removal Tool will be used to 

remove detectors from the base.

This detector base can be made tamper resistant so that 

the detector cannot be detached without the use of a tool. 

To make the base tamper-resistant, break off the smaller 

tab at the scribed line on the tamper-resistance tab, on the 

detector mounting bracket (see Figure 3A), before install-

ing the detector. 

To  remove  the  detector  from  the  base  after  it  has  been 

made  tamper  resistant,  remove  the  decorative  ring  by 

rotating it in either direction and pulling it away from the 

base.

 Then, insert a small screwdriver into the notch (see Fig-

ure 3B), and press the plastic lever toward the mounting 

surface  before  rotating  the  detector  counterclockwise  for 

removal.

SNAP ON 

DECORATIVE

RING

SCREWS (NOT

SUPPLIED)

DETECTOR

BASE

BOX (NOT

SUPPLIED)

SHORTING

SPRING

Figure 1. Mounting base to box:

A78-1175-01

Summary of Contents for B110LPA

Page 1: ...age 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Maximum at 100 mA Alarm current must be limited to 100 mA by the control panel If it is used the RA400ZA Remote Annunciator operates within the specified detector alarm currents Reset Voltage 2 5 ...

Page 2: ...tighten the terminal screw Check the zone wiring before installing the smoke detec tor head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electrical box position the shorting spring against ter minal 3 Use the slot in the retaining clip to hold the spring against the terminal as shown in Figure 1 This shorts the negative in and neg...

Page 3: ...2 WIRE CONTROL PANEL E O L CLASS A OPTIONAL WIRING A78 1175 04 Figure 2 Wiring diagram for a typical 2 wire detector system Figure 3A Activating the tamper resistance feature PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE USE SMALL BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW A78 1175 03 Figure 3B Removing detector head from base ...

Page 4: ... the smoke detector is usually located For this reason there may be large delays in detecting a smoldering fire with either an ionization type detec tor or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed do...

Reviews: