background image

D150-05-00               REV #: 003 

I56-1028-000

NOTE:

  IF  A  REMOTE  AN-

NUNCIATOR  IS  NOT 

USED, POLARITY OF 

THESE  TERMINALS 

MAY BE REVERSED.

2

3

4

1

REMOTE

ANNUNCIATOR

2

3

4

1

REMOTE

ANNUNCIATOR

2-WIRE CONTROL PANEL

E

O

L

CLASS A OPTIONAL WIRING

 A78-1175-04

Figure 2. Wiring diagram for a typical 2-wire detector system:

Figure 3A. Activating the tamper-resistance feature:

PLASTIC LEVER

BREAK TAB AT

DOTTED LINE BY

TWISTING TOWARD

CENTER OF BASE.

USE SMALL-BLADED

SCREWDRIVER TO

PUSH PLASTIC LEVER

IN DIRECTION OF

ARROW.

A78-1175-03

Figure 3B. Removing detector head from base:

Summary of Contents for B110LPA

Page 1: ...age 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Maximum at 100 mA Alarm current must be limited to 100 mA by the control panel If it is used the RA400ZA Remote Annunciator operates within the specified detector alarm currents Reset Voltage 2 5 ...

Page 2: ...tighten the terminal screw Check the zone wiring before installing the smoke detec tor head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electrical box position the shorting spring against ter minal 3 Use the slot in the retaining clip to hold the spring against the terminal as shown in Figure 1 This shorts the negative in and neg...

Page 3: ...2 WIRE CONTROL PANEL E O L CLASS A OPTIONAL WIRING A78 1175 04 Figure 2 Wiring diagram for a typical 2 wire detector system Figure 3A Activating the tamper resistance feature PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE USE SMALL BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW A78 1175 03 Figure 3B Removing detector head from base ...

Page 4: ... the smoke detector is usually located For this reason there may be large delays in detecting a smoldering fire with either an ionization type detec tor or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed do...

Reviews: