INSTALLATION AND MAINTENANCE INSTRUCTIONS  

  

 
 

Model 885WP-B Weatherproof Heat Detector 
with Fixed Temperature Alarm    

 

Specifications  

        Diameter: 

Height (including base):  
Weight (including base): 

Operating Temperature Range:  
IP Rating:  
Sensitivity: 
Operating Voltage: 
Standby Current: 
Alarm Current: 
 
Latching Alarm: 
Max .Air Velocity 

 
10.2 cm (4") 
4.8 cm (1.8") 
170g (6.0 ounce) 

-1

5

q

to 

50

q

C (

5

q

F to 1

22

q

F)   

IP67 
63

q

C (145.4

q

F) Fixed Temperature     

8.5 to 30VDC 

İ

50

嘕$

 

Min. 2mA 

#

3.1VDC 

Max. 80mA 

#

6.5VDC 

Reset by momentary power interruption 
20m/s 

 

Before installing  

Please thoroughly read System Sensor manual which 
provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of 
this manual are available at no charge from System 
Sensor. 
 

NOTICE

: This manual shall be left with the owner/user 

of this equipment. 
 

IMPORTANT: 

This detector must be tested and main-

tained regularly in accordance with the requirements of 
the local standards and regulations. The detector should be 
cleaned at least once a year. 

 
 

Figure1.   Surface mounting of the 885WP-B  weatherproof  

heat detector into a 50 /60 mm junction 
box.  

 
 
 
 
 

 

 

General Description 

Model 885WP-B is a 2-wire fixed temperature (63

q

C) heat 

detector. This detector is designed to provide open area 
protection in areas subject to moisture. This detector is 
sealed against the entry of moisture to a rating of IP67. 
The LED will latch on when the detector is in alarm. 

 
Mounting 

Each 885WP-B detector is used with a mounting base that 
permits the detector to be mounted directly to a 50 mm or 
60 mm junction box.  
 

Tamper-resistant Feature 

This detector includes a tamper-resistant feature that 
prevents its removal from the mounting base without the 
use of a key. To make the detector tamper-resistant, 
remove the tab from the tamper arm on the mounting base 
using a cutting tool. Remove the tamper key from the 
center of the mounting base by twisting it back and forth 
several times (see 

Figure2

). Once the detector is installed, 

it may be removed from the mounting base by inserting 
the T-shaped end of the key into the slot on the side of the 
unit and rotating the detector counter-clockwise. 

 
Wiring Installation Guidelines  

This detector provides six wires which are divided into 
three groups, separately two red, two white and two black 
wires. Refer to 

Figure 3.

 . 

 

Terminal Notes: 

Red wire:       Power / Detector Circuit 

+

ve 

Black wire     Power / Detector Circuit 

-

ve (the power and 

the LED uses the same cathode) 

White wire     Remote LED 

+

ve 

Wiring Diagram refers to 

Figure 4.

 

 

Alignment when the detector

 is 

mounted into the base 

 
 
 

Three-Year Limited W

ear Limited Warranty 

Please refer to insert for the Limitations of Fire Alarm Systems (I56-1558-00)

 

System Sensor warrants its enclosed heat detector to be free 
from defects in materials and workmanship under normal use 
and service for a period of three years from date of 
manufacture. System Sensor makes no other express warranty 
for this HEAT detector. No agent, representative, dealer, or 
employee of the Company has the authority to increase or alter 
the obligations or limitations of this Warranty. The Company’s  
obligation  of  this  Warranty shall be limited to the repair or  
replacement  of  any  part  of  the  smoke  detector  which  is 
found to be defective in materials or workmanship under 
normal use and service  during  the  three  year  period  

commencing  with  the date of manufacture. After phoning System 
Sensor for a Return Authorization Number, return defective units 
postage prepaid to the Company. Please include a note describing 
the malfunction and suspected cause of failure. The Company shall 
not be obligated to repair or replace units which are found to be 
defective because of damage, unreasonable use, modifications, or 
alterations occurring after the date of manufacture. In no case shall 
the Company be liable for any consequential or incidental damages 
for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s 
negligence or fault. 



Reviews: