Installation 

NOTE: 

All wiring must conform to applicable local 

codes, ordinances and regulations. 

 

NOTE: 

Verify that all detector bases are installed, that the 

initiating-device circuits have been tested, and 
that the wiring is correct. 

 

WARNING 

 

Remove power from initiating-device circuits before in-
stalling detectors. 

 

1.

 

Place the detector on the mounting base and rotate 
clockwise until it drops into place. 

2.

 

Turn the detector clockwise in the mounting base until 
it clicks into place. 

3.

 

After all detectors have been installed, apply power to 
the control unit or initiating-device circuits. 

4.

 

Test the detector as described in

 Te

Testing

5.

 

Reset the detector at the system control panel. 

6.

 

Notify the proper authorities the system is  in 
operation. 

 
 

Figure2. Module 885WP-B weatherproof Heat

Module 885WP-B weatherproof Heat Detector 

  Mounting Bracket 
 

 

 
Testing  

NOTE: 

Before testing, notify the proper authorities that 

the thermal detector system is undergoing mainte-
nance and will temporarily be out of service. 
Disable the zone or system undergoing mainte-
nance to prevent unwanted alarms. 

Detectors must be tested after installation as well as after 
each time maintenance is performed.  
Test the  885WP-B as follows: 

 

To test the 885WP-B you need a hair dryer. From the 
side of the detector, direct the heat toward the  sensor. 
Hold the heat source about 15 cm away to prevent 
damage and apply heat to the cover during testing  
until it alarms.

      

A detector that fails these tests should first be cleaned as 
outlined in the 

Maintenance

 

section which follows. If 

the detector still fails , it should be returned for repair. 
 
Notify the proper authorities the system is back on line.

 

 
 
 
 
Figure 3. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Metal heat Collector

   

RED (+

ve

  2 wires)

BLACK (-

ve

   2 wires)

WHITE   (Remote LED   +

ve

  2 wires)

 3                                                                                                                  I56-885-00CW 

 
Maintenance 

NOTE: 

Before removing the detector, notify the proper 

authorities that the fire detection system is 
undergoing maintenance and will temporarily be 
out of service. Disable the zone or system 
undergoing maintenance to prevent unwanted 
alarms. 

 

1.

 

Remove the detector from the mounting base by  
rotating it counter-clockwise. 

2.

 

Vacuum the metal heat collector and surrounding area.

3.

 

Clean the surface of the detector. 

4.

 

Reinstall the detector. 

5.

 

Test the detector as described in 

Testing

.

 

6.   Notify the proper authorities the system is back in 

operation.

 

 

 Figure 4.  Detector Wiring Diagram  

RED wires

 

BLACK wires 

WHITE wire

 

KEY

TAMPER

(CUT OFF SMALL TAB TO ACTUATE TAMPER-RESIST 

TEMPER

 

ARM

REMOVE DETECTOR)

FEATURE-DEPRESS ARM WITH KEY TO

ALIGNMENT

NOTCHES