4 I56-885-00CW
Rev.1
1 I56-885-00CW
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model 885WP-B Weatherproof Heat Detector
with Fixed Temperature Alarm
Specifications
Diameter:
Height (including base):
Weight (including base):
Operating Temperature Range:
IP Rating:
Sensitivity:
Operating Voltage:
Standby Current:
Alarm Current:
Latching Alarm:
Max .Air Velocity
10.2 cm (4")
4.8 cm (1.8")
170g (6.0 ounce)
-1
5
q
to
50
q
C (
5
q
F to 1
22
q
F)
IP67
63
q
C (145.4
q
F) Fixed Temperature
8.5 to 30VDC
İ
50
嘕$
Min. 2mA
#
3.1VDC
Max. 80mA
#
6.5VDC
Reset by momentary power interruption
20m/s
Before installing
Please thoroughly read System Sensor manual which
provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System
Sensor.
NOTICE
: This manual shall be left with the owner/user
of this equipment.
IMPORTANT:
This detector must be tested and main-
tained regularly in accordance with the requirements of
the local standards and regulations. The detector should be
cleaned at least once a year.
Figure1. Surface mounting of the 885WP-B weatherproof
heat detector into a 50 /60 mm junction
box.
General Description
Model 885WP-B is a 2-wire fixed temperature (63
q
C) heat
detector. This detector is designed to provide open area
protection in areas subject to moisture. This detector is
sealed against the entry of moisture to a rating of IP67.
The LED will latch on when the detector is in alarm.
Mounting
Each 885WP-B detector is used with a mounting base that
permits the detector to be mounted directly to a 50 mm or
60 mm junction box.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that
prevents its removal from the mounting base without the
use of a key. To make the detector tamper-resistant,
remove the tab from the tamper arm on the mounting base
using a cutting tool. Remove the tamper key from the
center of the mounting base by twisting it back and forth
several times (see
Figure2
). Once the detector is installed,
it may be removed from the mounting base by inserting
the T-shaped end of the key into the slot on the side of the
unit and rotating the detector counter-clockwise.
Wiring Installation Guidelines
This detector provides six wires which are divided into
three groups, separately two red, two white and two black
wires. Refer to
Figure 3.
.
Terminal Notes:
Red wire: Power / Detector Circuit
+
ve
Black wire Power / Detector Circuit
-
ve (the power and
the LED uses the same cathode)
White wire Remote LED
+
ve
Wiring Diagram refers to
Figure 4.
Alignment when the detector
is
mounted into the base
Three-Year Limited W
ear Limited Warranty
Please refer to insert for the Limitations of Fire Alarm Systems (I56-1558-00)
System Sensor warrants its enclosed heat detector to be free
from defects in materials and workmanship under normal use
and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty
for this HEAT detector. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or
replacement of any part of the smoke detector which is
found to be defective in materials or workmanship under
normal use and service during the three year period
commencing with the date of manufacture. After phoning System
Sensor for a Return Authorization Number, return defective units
postage prepaid to the Company. Please include a note describing
the malfunction and suspected cause of failure. The Company shall
not be obligated to repair or replace units which are found to be
defective because of damage, unreasonable use, modifications, or
alterations occurring after the date of manufacture. In no case shall
the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied