D100-101-00C 2 I56-6476-000
4.
Test the detector as described in the TESTING section of this manual.
5.
Reset the detector at the system control panel.
6.
Notify the proper authorities the system is in operation.
TESTING
NOTE: Before testing, notify the proper authorities that the thermal detector
system is undergoing maintenance and will temporarily be out of service.
Disable the zone or system undergoing maintenance to prevent unwanted
alarms.
Detectors must be tested after installation as well as after each time
maintenance is performed.
Test the 885-WP as follows:
A.
Test Magnet:
1.
Place the magnet against the cover in the magnet test area as
shown in Figure 4 to activate the test feature.
2.
The LED should latch ON within 10 seconds, indicating alarm and
annunciating the panel.
3.
Reset the detector at the system control panel.
B.
Direct Heat Method
You need a hair dryer. From the side of the detector, direct the heat
toward the sensor. Hold the heat source about 15 cm away to prevent
damage and apply heat to the cover during testing until it alarms.
A detector that fails these tests should first be cleaned as outlined in the
Maintenance section which follows. If the detector still fails, it should be
returned for repair.
Notify the proper authorities when the system is back on line.
MAINTENANCE
NOTE: Before removing the detector, notify the proper authorities that the
smoke detector system is undergoing maintenance and will temporarily be
out of service. Disable the zone or system undergoing maintenance to
prevent unwanted alarms.
1.
Disconnect the wires from power wiring in junction box, see Figure 3.
2.
Remove the detector from the mounting bracket by rotating it
counter-clockwise.
3.
Vacuum the surrounding of the thermistor.
4.
Clean the surface of the detector.
5.
Reinstall the detector.
6.
Test the detector as described in Testing.
7.
Notify the proper authorities the system is back in operation.
Figure 3. Field Wiring Diagram
Figure 4
Figure 5.
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed smoke detector to be free from defects in
materials and workmanship under normal use and service for a period of
three years from date of manufacture. System Sensor makes no other express
warranty for this smoke detector. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter the
obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
smoke detector which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing with
the date of manufacture. Contact your local System Sensor representative for
issuing of a Return Authorization Number (RA#) before returning the
defective units. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair or
replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of
manufacture. In no case shall the Company be liable for any consequential or
incidental damages for breach of this or any other Warranty, expressed or
implied whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault.
Ver. B
Please refer to insert for the Limitations of Fire Alarm Systems
A5665‐116
A5665‐115
Wiring connections Terminal
Strip or connectors
Junction box
PVC Conduit
Ceiling or Roof
The wiring hole
Detector
Adapter
PVC Conduit
A5665‐114
Mounting
bracket