Mounting Brackets

Install a ceiling or wall bracket for both the receiver and
transmitter so that when mounted, the receiver and the
transmitter will be at approximately the same height. Each
ceiling bracket is composed of two parts that should be as-
sembled with inside part between the ceiling and outside
part as shown in Figure 5. The brackets should be mounted
so that the slot in the front of each bracket is facing the
other bracket. Mount the brackets only on solid structures
of the building. To avoid unwanted alarms due to wall
movement, do not mount to flexible walls, such as sheet
metal walls (see MOUNTING LOCATIONS). Mount brack-
ets with a separation of at least 30 feet but not more than
330 feet.

Figure 6. Ceiling mouting bracket assembly:

CEILING
SCREWS

SLOT IN FRONT
OF BRACKET

OUTSIDE
PART

INSIDE
PART

CEILING

A78-2041-01

;

;

Concrete
or Brick

Good Mounting
Surface

Poor Mounting

Surface

Sheet
Metal

Poor Mounting
Surface

Good Mounting
Surface

Figure 5. Good and poor mounting surfaces:

A78-2652-00

Wiring Installation Guidelines

Always install all wiring in compliance with the National
Electrical Code, and/or the applicable local codes, and any
special requirements of the local authority having jurisdic-
tion. Proper wire gauges and suitable means for strain relief
should be used. The conductors used to connect beam
smoke detectors to control panels and accessory devices
should be color-coded to reduce the likelihood of wiring er-
rors. Improper connections can prevent a system from re-
sponding properly in the event of a fire.

Installation wire used for the beam detector shall be no
smaller than 18 gauge (1.0 square mm). For best system
performance, all wiring should be twisted pair and in-
stalled in separate grounded conduit. Do NOT mix fire sys-
tem wiring in the same conduit as any other electrical
wiring. Shielded cable may be used to provide additional
protection against electrical interference.

When installing the beam smoke detector in applications
where flexible conduit will be used the BMB Beam Mount-
ing Bracket kit must be installed with the cable before wir-
ing the unit, as per the instructions supplied with the kit.
For applications that require flexible conduit to be mounted
to the beam smoke detector, the model BMB kit can be or-
dered separately.
In those applications where the model BMB kit is not used,
the two connectors with attached cable (6 conductor for
the transmitter and 16 conductor for the receiver) can be
wired before the detector is mounted.

For wiring, first remove the pre-cut insulation from the con-
ductor to be connected, then use a wire nut to connect the
detector wire to the field wire. If the insulation has been re-
moved from any unused conductors, make sure they are
terminated properly to avoid short circuits. The transmitter
can be wired in one of two ways. Figure 7 shows the trans-
mitter permanently connected to the receiver. In this case
the transmitter receives its power along with communica-
tion for the alignment aid through the connecting pair of

D400-18-00

4

I56-494-10R

Summary of Contents for 6424

Page 1: ...put Local LED yellow Normal Operation Local LED flashing green Alignment Aid LED Bar Graph 4 red LEDs Relays Alarm Trouble Environmental Temperature 30 C to 55 C 22 F to 131 F Humidity 10 to 93 RH Noncondensing Mechanical Weight Receiver 1 5 lbs 663 g Transmitter 1 3 lbs 598 g Mounting Ceiling or Wall Separate Mounting Brackets Provided Wiring Plug with Attached Cable Adjustment Angle Ceiling 30 H...

Page 2: ...ectors the EOL Power Supervisory Module is energized The relay contacts along with the detector s trouble relay contacts can provide a closed series circuit in the control panel s alarm initiating loop A loss in power or a trouble condition at the detector causes the respective EOL or trouble relay to open resulting in a trouble signal at the control panel Parts List Description Quantity Receiver ...

Page 3: ...roof or ceiling Figures 3 and 4 show the spac ing for both the shed type and peaked type sloped ceilings Figure 3 Sloped ceiling shed type S 3 FT MAX S 1 2 S MAX Tx Rx A78 2036 01 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT MAX 3 FT MAX MOUNT DETECTOR ANYWHERE IN THIS AREA Tx Rx A78 2035 01 Mounting Locations Beam detectors require a stable mounting surface for proper operation A surf...

Page 4: ...he likelihood of wiring er rors Improper connections can prevent a system from re sponding properly in the event of a fire Installation wire used for the beam detector shall be no smaller than 18 gauge 1 0 square mm For best system performance all wiring should be twisted pair and in stalled in separate grounded conduit Do NOT mix fire sys tem wiring in the same conduit as any other electrical wir...

Page 5: ...nsmitter permanently wired to receiver A78 2043 00 CLASS A RETURN LOOP INITIATING LOOP POWER TO DETECTORS LISTED PANEL LISTED REMOTE POWER SOURCE POWER INPUTS TO TRANSMITTER ARE NONPOLAR TRANSMITTER BLUE GREEN WHITE BROWN BLACK RED ORANGE GREEN BLACK RED WHITE STRIPE WHITE WHITE BLACK STRIPE GRAY VIOLET WHITE VIOLET STRIPE BROWN WHITE YELLOW STRIPE WHITE RED STRIPE TRANSMITTER BLUE GREEN BLACK RED...

Page 6: ...ve In any applications where the BMB Beam Mounting Bracket kit is used the kit should be installed before the detector is mounted Instructions for mount ing the BMB are included in the BMB kit 3 Insert the flange of the detector mounting bracket into the keyed hole of the wall or ceiling mounting bracket Slide the detector forward into position The detector should now hang from the bracket 4 Inser...

Page 7: ...NT SCREWS 2 U BRACKET WALL MOUNTING BRACKET MOUNTING HOLE PLASTIC WASHER A78 2034 01 Figure 13 Ceiling mounting MOUNTING HUB MOUNTING HUB ALIGNMENT LEDs STATUS LEDs RECEIVER ONLY BEAM LENS HOLE PLUG ALIGNMENT ADJUST POTENTIOMETER RECEIVER ONLY CABLE EGRESS HOLE PLUG USED TO PLUG UNUSED HOLE VERTICAL ADJUSTMENT SCREWS 2 U BRACKET HORIZONTAL ADJUSTMENT SCREW 10 24 x 2 1 4 in CEILING MOUNTING BRACKET...

Page 8: ...CTOR CABLE RESET SWITCH 30 55 SENSITIVITY SELECT SWITCH N A ALIGNMENT MODE SWITCH A78 2032 01 Figure 15 Rear view transmitter ACCESS DOOR CONNECTOR 6 CONDUCTOR CABLE A N ALIGNMENT MODE SWITCH SW1 L S RANGE SELECT SWITCH SW2 A78 2031 01 D400 18 00 8 I56 494 10R ...

Page 9: ...ge L 100 to 330 feet 2 If the transmitter is directly wired to the receiver Figure 7 slide the alignment switch SW1 on the transmitter to the A align position see Figure 15 Point the trans mitter directly at the receiver then go to step 5 3 If the transmitter is wired directly to a power supply it should be temporarily wired to the receiver if pos sible see Figure 8 NOTE Temporarily wiring the tra...

Page 10: ...this 3 When it is impossible to get more than three LEDs to light carefully tighten the horizontal adjustment screws and then the vertical adjustment screws on the transmitter bracket making sure all three alignment LEDs stay lit 4 Slide the alignment switch on the transmitter to the NORMAL MODE N position see figure 15 and dis connect any temporary wiring Carefully close the door on the transmitt...

Page 11: ... Units that alarm during the non alarm test step 3 should be cleaned and tested again before being returned Follow the maintenance instructions for cleaning B Remote Test Switch The remote test station RTS451 can be used with the 6424 beam smoke detector Follow instructions included with the test station for proper use See Figure 9 Remote Test Station for wiring diagram If the detector is not in t...

Page 12: ...ence or fault Some states do not allow the exclusion or limitation of incidental or conse quential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...