background image

Before Installing

Please thoroughly read this manual and applicable sections
of System Sensor’s Manual I56-506, 

Guide for Proper Use of

Projected Beam Detectors

. Copies of this manual are avail-

able from System Sensor.

General Description

System Sensor Model 6424 is a long range projected beam
smoke detector designed to provide open area protection. It
is to be used with UL-listed, separately supplied power (4-
wire) control panels only. The detector consists of a sepa-
rate transmitter and receiver. Smoke entering the area
between the transmitter and receiver causes a reduction in
signal at the receiver. When the obscuration reaches one of
two predetermined thresholds (chosen with a switch in the
receiver), the detector generates an alarm signal. Complete
blockage of the beam causes a trouble signal to avoid false
alarms. Slow changes in obscuration due to a build up of
dirt or dust on the lens of the detector are compensated for
by a microcontroller which continuously monitors the sig-
nal strength and periodically updates the alarm and trouble
thresholds. When the self-compensation circuit reaches its
limit, the detector generates a trouble signal, indicating the
need for service.

Three LEDs at the receiver indicate the status of the detec-
tor: a red LED for alarm, a yellow LED for trouble, and a
pulsed green LED for standby operation. The alarm signal
latches and can be reset by a momentary power interrup-
tion, by using the remote reset input to the receiver if using
the remote test/reset station model RTS451, or with the lo-
cal reset button located behind the rear door in the receiver.
A trouble signal automatically resets upon removing the
cause of trouble. In addition to these indicators, there are
four LEDs on both the receiver and the transmitter which
are used as a beam alignment aid. No additional equipment
is needed for alignment of the beam.

Each detector contains one Form A (normally open) con-
tact for alarm signals and one Form B (normally closed)
contact for trouble signals. Supervision of power is accom-
plished by installing a Power Supervisory End-of-Line Relay
Module (model A77-716) at the end of the detector power
loop. When power is applied to and through the detectors,
the EOL Power Supervisory Module is energized. The relay
contacts, along with the detector’s trouble relay contacts,
can provide a closed series circuit in the control panel’s
alarm-initiating loop. A loss in power or a trouble condition
at the detector causes the respective EOL or trouble relay to
open, resulting in a trouble signal at the control panel.

Parts List

Description

Quantity

Receiver Unit

1

Transmitter Unit

1

Receiver Wiring Cable

1

Transmitter Wiring Cable

1

Wall Mounting Bracket

2

Ceiling Mounting Bracket (inside part)

2

Ceiling Mounting Bracket (outside part)

2

Wall Bracket Screw

2

Ceiling Bracket Screw

2

Washers

4

Allen Wrench

1

Instruction Manual

1

Test Filter

1

Cable Exit Plug

1

Hole Plug

1

Detector Placement

This section of the manual discusses the placement of pro-
jected beam detectors. Though this information is based
upon industry expertise, it is intended to be used only as a
technical guide. Always comply with the requirements of
applicable codes and standards such as, NFPA 72, National
Fire Alarm Code, as well as directives of the Authority Hav-
ing Jurisdiction (AHJ).  For general information on the
placement of detectors, read System Sensor’s Manual I56-
506, 

Guide for Proper Use of Projected Beam Detectors

.

Projected beam detectors are usually located with their
beams parallel to the ceiling. However, they can be
mounted vertically or at any angle to protect the area in-
volved. Since beam detectors sense the smoke buildup over
a distance, they are ideal for locations with high ceilings.
They can also be mounted on a wall or ceiling below the
level of a spot type detector, reducing the effects of air
stratification. Some typical locations would include large
areas with high ceilings such as atriums, warehouses, and
factories.

NOTE:

Projected beam smoke detectors should always be
mounted to stable mounting surfaces. See the
MOUNTING LOCATION section for details.

Some fire codes specify spacing on a given center-to-center
distance between detectors under ideal conditions. These
spacings are based on rooms with smooth ceilings and no
physical obstructions between the contents being protected
and the detectors. Moreover, they are also based on a maxi-
mum ceiling height, and on the assumption that the value
and the combustible nature of the contents of the room be-
ing protected do not warrant greater protection or closer
spacing.

D400-18-00

2

I56-494-10R

Summary of Contents for 6424

Page 1: ...put Local LED yellow Normal Operation Local LED flashing green Alignment Aid LED Bar Graph 4 red LEDs Relays Alarm Trouble Environmental Temperature 30 C to 55 C 22 F to 131 F Humidity 10 to 93 RH Noncondensing Mechanical Weight Receiver 1 5 lbs 663 g Transmitter 1 3 lbs 598 g Mounting Ceiling or Wall Separate Mounting Brackets Provided Wiring Plug with Attached Cable Adjustment Angle Ceiling 30 H...

Page 2: ...ectors the EOL Power Supervisory Module is energized The relay contacts along with the detector s trouble relay contacts can provide a closed series circuit in the control panel s alarm initiating loop A loss in power or a trouble condition at the detector causes the respective EOL or trouble relay to open resulting in a trouble signal at the control panel Parts List Description Quantity Receiver ...

Page 3: ...roof or ceiling Figures 3 and 4 show the spac ing for both the shed type and peaked type sloped ceilings Figure 3 Sloped ceiling shed type S 3 FT MAX S 1 2 S MAX Tx Rx A78 2036 01 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT MAX 3 FT MAX MOUNT DETECTOR ANYWHERE IN THIS AREA Tx Rx A78 2035 01 Mounting Locations Beam detectors require a stable mounting surface for proper operation A surf...

Page 4: ...he likelihood of wiring er rors Improper connections can prevent a system from re sponding properly in the event of a fire Installation wire used for the beam detector shall be no smaller than 18 gauge 1 0 square mm For best system performance all wiring should be twisted pair and in stalled in separate grounded conduit Do NOT mix fire sys tem wiring in the same conduit as any other electrical wir...

Page 5: ...nsmitter permanently wired to receiver A78 2043 00 CLASS A RETURN LOOP INITIATING LOOP POWER TO DETECTORS LISTED PANEL LISTED REMOTE POWER SOURCE POWER INPUTS TO TRANSMITTER ARE NONPOLAR TRANSMITTER BLUE GREEN WHITE BROWN BLACK RED ORANGE GREEN BLACK RED WHITE STRIPE WHITE WHITE BLACK STRIPE GRAY VIOLET WHITE VIOLET STRIPE BROWN WHITE YELLOW STRIPE WHITE RED STRIPE TRANSMITTER BLUE GREEN BLACK RED...

Page 6: ...ve In any applications where the BMB Beam Mounting Bracket kit is used the kit should be installed before the detector is mounted Instructions for mount ing the BMB are included in the BMB kit 3 Insert the flange of the detector mounting bracket into the keyed hole of the wall or ceiling mounting bracket Slide the detector forward into position The detector should now hang from the bracket 4 Inser...

Page 7: ...NT SCREWS 2 U BRACKET WALL MOUNTING BRACKET MOUNTING HOLE PLASTIC WASHER A78 2034 01 Figure 13 Ceiling mounting MOUNTING HUB MOUNTING HUB ALIGNMENT LEDs STATUS LEDs RECEIVER ONLY BEAM LENS HOLE PLUG ALIGNMENT ADJUST POTENTIOMETER RECEIVER ONLY CABLE EGRESS HOLE PLUG USED TO PLUG UNUSED HOLE VERTICAL ADJUSTMENT SCREWS 2 U BRACKET HORIZONTAL ADJUSTMENT SCREW 10 24 x 2 1 4 in CEILING MOUNTING BRACKET...

Page 8: ...CTOR CABLE RESET SWITCH 30 55 SENSITIVITY SELECT SWITCH N A ALIGNMENT MODE SWITCH A78 2032 01 Figure 15 Rear view transmitter ACCESS DOOR CONNECTOR 6 CONDUCTOR CABLE A N ALIGNMENT MODE SWITCH SW1 L S RANGE SELECT SWITCH SW2 A78 2031 01 D400 18 00 8 I56 494 10R ...

Page 9: ...ge L 100 to 330 feet 2 If the transmitter is directly wired to the receiver Figure 7 slide the alignment switch SW1 on the transmitter to the A align position see Figure 15 Point the trans mitter directly at the receiver then go to step 5 3 If the transmitter is wired directly to a power supply it should be temporarily wired to the receiver if pos sible see Figure 8 NOTE Temporarily wiring the tra...

Page 10: ...this 3 When it is impossible to get more than three LEDs to light carefully tighten the horizontal adjustment screws and then the vertical adjustment screws on the transmitter bracket making sure all three alignment LEDs stay lit 4 Slide the alignment switch on the transmitter to the NORMAL MODE N position see figure 15 and dis connect any temporary wiring Carefully close the door on the transmitt...

Page 11: ... Units that alarm during the non alarm test step 3 should be cleaned and tested again before being returned Follow the maintenance instructions for cleaning B Remote Test Switch The remote test station RTS451 can be used with the 6424 beam smoke detector Follow instructions included with the test station for proper use See Figure 9 Remote Test Station for wiring diagram If the detector is not in t...

Page 12: ...ence or fault Some states do not allow the exclusion or limitation of incidental or conse quential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...

Reviews: