4451HTA Plug-in Fixed 

Intermediate Temperature 

Thermal Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Before Installing

This detector must be installed in compliance with the con-

trol panel installation manual and meet the requirements 

of the authority having jurisdiction. In addition, the National 

Fire  Protection  Association  has  published  codes,  stan-

dards, and recommended practices for the installation and 

use of the above appliances (NFPA 72). Please also refer 

to  CAN/ULC-S524  and  CEC  Part  ,  Sec.  32. Therefore, 

the installer must be familiar with these requirements, with 

local codes, and any special requirements of the authority 

having jurisdiction.

NOTICE: 

This manual should be left with the owner/user 

of this equipment.

IMPORTANT: 

This detector must be tested and maintained 

regularly following CAN/ULC-S536 requirements. The de-

tector should be cleaned at least once a year.

General Description

The  4451HTA  detector  is  a  fixed  intermediate  tempera

-

ture alarm thermal detector utilizing a state-of-the-art dual 

thermistor sensing circuit. This detector is designed to be 

used with compatible control panels only.

Specifications

Diameter: 

 

4. inches (04 mm)

Height: 

 

2. inches (53 mm)

Weight: 

 

5 ounces (50 g)

Installation Temperatures: 

 

32° to 50°F (0° to 66°C)

Operating Humidity Range: 

 

0% to 93% Relative Humidity

Latching Alarm: 

 

Reset by momentary power interruption

Sensitivity: 

 

90°F (88°C) 

Operating Voltage: 

 

5-35 VDC

Standby Current: 

 

00 µA

Two LEDs on each detector light to provide 360° visibility 

of the detector indication. Remote LED annunciator capa-

bility  is  provided  as  standard,  and  the  RA400ZA  remote 

LED annunciator is available as an optional accessory.

Base Selection And Wiring Guide

Refer to the installation instructions for the plug-in detector 

bases for base selection and wiring instructions. System 

Sensor has available a variety of detector bases for these 

heat detectors, including 2-wire applications with and with-

out relays and/or current limiting resistors for use with con-

trol panels that require one. These detectors are only to be 

used with 400 and 400B series bases.

Install the System Sensor  plug-in base to be used with the 

detector following the instructions in the base manual.

Installation

NOTE: 

All  wiring  must  conform  to  applicable  installation 

codes and regulations.

658  Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5

-800-SENSOR2, FAX: 905-82-077

www.systemsensor.ca

Summary of Contents for 4451HTA

Page 1: ...d with compatible control panels only Specifications Diameter 4 1 inches 104 mm Height 2 1 inches 53 mm Weight 5 ounces 150 g Installation Temperatures 32 to 150 F 0 to 66 C Operating Humidity Range 10 to 93 Relative Humidity Latching Alarm Reset by momentary power interruption Sensitivity 190 F 88 C Operating Voltage 15 35 VDC Standby Current 100 µA Two LEDs on each detector light to provide 360 ...

Page 2: ...til the detector drops into place c Continue turning detector clockwise to lock it in place Tamper Resistance Feature The detector bases include a feature that when activated prevents removal of the detector without the use of a tool Refer to the installation instruction manual of the detector base to make use of this capability 2 After all detectors have been installed apply power to the control ...

Page 3: ...ded periods of extreme heat can melt the plastic and damage the cover NOTE If a detector goes into alarm it will reset only if the detector has cooled and if its power is momentarily interrupted Check the control panel being used to determine whether the RESET switch or some other auxiliary device or control momentarily cuts off power to the detector loop Detectors that fail these tests should be ...

Page 4: ...bove limitation or exclusion may not apply to you This Warranty gives you spe cif ic legal rights and you may also have other rights under common law WARNING The Limitations of Property Protection Heat Detectors Heat detectors do not always detect fires because the fire may be a slow smoldering low heat type producing smoke or because they may not be near where the fire occurs or because the heat ...

Reviews: