System air 316293 Installation Manual Download Page 10

9

7.8   Network address set

1) Network address is set by communication of indoor and 

outdoor unit; the address is the same as indoor address, 

there is no need to set separately.

The system together have  64units(0-63),everyone has only 

system addresscode,If two addresses are the  same in one 

system  , the abnormal operation will occur.

Please switch off the power before setting,otherwise the 

unexpected error will occur.

CAUTION

7.9 Main board Code designation

Table 7-3

J1

 Not wire jumper means has power-off 

   memory

● 

Has wire jumper means no power-off 

   memory 

 00 means the time of stopping TERMAL 

fan is 4 minutes (default)

● 

01 means the time of stopping TERMAL 

fan is 8 minutes 

● 

10 means the time of stopping TERMAL 

fan is 12 

minutes 

● 

11 means the time of stopping TERMAL 

fan is 16 

minutes 

 00 means temp. compensation value is 

   6°C under heat mode (default)

● 

01 means temp. compensation value is 

   2°C under heat mode

● 

10 means temp. compensation value is 

   4°C under heat mode

● 

11 means temp. compensation value is 

   0°C under heat mode(follow me)

12

SW1

ON

12

SW1

ON

12

SW3

ON

SW7

12

ON

SW7

12

ON

12

SW3

ON

12

SW2

ON

SW4

12

ON

SW5

12

ON

SW6

12

ON

 0 means auto addressing mode (default)

● 

1 means clear indoor unit address

 0 means cooling mode temperature 

   compensation is 0°C (default)

 1 means cooling mode temperature 

   compensation is 2°C

 0 means EXV positions 96 (steps) in 

   standby heating mode (default)

 1 means EXV positions 72 (steps) in 

   standby heating mode

 00 means shutting down the unit to 

   "stop cold air" at 15

(default)

● 

01 means shutting down the unit to 

   "stop cold air" at 20

● 

10 means shutting down the unit to 

   "stop cold air" at 24

● 

11 means shutting down the unit to 

   "stop cold air" at 26

12

SW2

ON

Reserved 

(Default 0)

Reserved 

(Default 0)

Reserved 

(Default 0)

Reserved 

(Default 0)

means 0

means 1

ON

ON

0/1 definition of each dial code switch: 

Reserved 

(Default 0)

Summary of Contents for 316293

Page 1: ...SYSVRF2 FLOOR Floor VRF indoor unit INSTALLATION MANUAL GB...

Page 2: ...rated by 3 mm in all poles and connected with fixed wiring Children and the elderly should not operate this unit unless supervised by an adult When carrying out piping connection do not let materials...

Page 3: ...After completing installation make sure that refrigerant does not leak The appliance must be installed in accordance with national wiring regulations To install properly please read this installation...

Page 4: ...technological improvement without further notices Version I Vertical unit with casing with air intake from front and air outlet on top for installation on a wall or on feet on the floor Fig 4 2 Fig 4...

Page 5: ...e square timber traversely over the roof beam then install the hanging screw bolts Fig 4 6 NEW CONCRETE BRICKS Inlaying or embedding the screw bolts FOR ORIGINAL CONCRETE BRICKS Install the hanging ho...

Page 6: ...asurements given in Table 4 2 2 Secure the unit by driving the four fixing screws into suitable masonry plugs Connecting point of refrigerant pipe Liquid side A Connecting point of refrigerant pipe Ga...

Page 7: ...ndoor unit and the outdoor unit Then fasten the nuts at the repair points Notices For Benable pipe The bending angle should not exceed 90 Bending position is preferably in the bendable pipe The larger...

Page 8: ...not let air in which will cause water leakage by condensation 3 Pass the bound connecting pipe through the wall conduit from outside Be careful of the pipe allocation to do no damage to the tubing 3 C...

Page 9: ...or set horsepower 7100W 2 5HP 8000W 3 0HP 5 6 Note The horse power has been set before leaving the factory anyone can t modify it except the maintenance person 7 5 Terminal Board Diagram Please refer...

Page 10: ...is 6 C under heat mode default 01 means temp compensation value is 2 C under heat mode 10 means temp compensation value is 4 C under heat mode 11 means temp compensation value is 0 C under heat mode f...

Page 11: ...ting in the Owner s Manual 1 The indoor unit a Whether the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves norm...

Page 12: ...16126000002887 V4 0...

Reviews: