6.4 Time-based leakage

 (flow rate)

Press  the    key  until  the  time-based  leakage 

(flow rate) menu is displayed. 

If  the  flow  rate  exceeds  3500  l/h,  a  leakage 

problem is supected → Message A4 is displayed.

The standard value of 1 minute can be changed 

with this parameter. 

When the flow rate remains under 3500 l/h before 

the time has expired, the time is reset.  

When the flow rate has been exceeded, the time 

starts again.  

Press the   key again and use the   or   key 

to set how long (number of minutes) the device 

shall wait before closing the water supply when 

the flow rate exceeds 3500 l/h. 

Save the change by pressing the   key.

6.5 Unlocking the device

The next step leads to the menu allowing to un-

lock the device.  

When the SYR Safe-T has isolated the system 

after  an  unintended  volume-based  leakage, 

the device allows to determine whether it shall 

re-open  after  30  seconds  without  water  being 

drawn off. 

Press the   or   key to activate or deactivate 

the function. 

Press the   key to save the change.

This parameter cannot be switched off or 

reset to „0“. 

6.6 External alarm 

contact

The  menu  offers  settings  for  a  potential  free 

contact.

This  contact  offers  various  possibilities  to  dis-

play or signal an alarm. 

Use  the    or    key  to  set  how  the  Safe-T‘s 

alarm contact is to be programmed. 

Save the change by pressing the   key.

This function is only available in conjunction with 

the mains plug. 

Summary of Contents for SYR-Safe-T

Page 1: ...Instructions of use...

Page 2: ...ge protection 4 5 3 Deactivating the leak protection 5 5 4 Vacation leakage protection 5 5 5 Setting the vacation leakage protection 6 5 6 Deactivating the vacation leakage protection 6 5 7 Stop valve...

Page 3: ...into the normal operation mode Make sure that the battery block is correctly po sitioned in the compartment against the internal back wall Close the battery door As an option you can also connect the...

Page 4: ...of the following criteria be exceeded the device suspects a leakage problem and closes the main isolating valve In case the water quantity flown without interruption exceeds the set limit for the volu...

Page 5: ...lows for the following settings Press the key to validate and save the changes Press the key to display the current setting Set the desired value by means of the or key Press the key to save the setti...

Page 6: ...key to save the settings Press the key again to display the current setting of the vacation leakage protection Press the key until the vacation leakage protection is displayed 5 6 Deactivating the vac...

Page 7: ...play the current sta tus of the leakage protection s stop valve Press the key to display the menu of the lea kage protection s stop valve 5 7 Stop valve In order to change the stop valve s position un...

Page 8: ...e vacation supervision use the following function When no water is drawn off during 48 hours the main stop valve isolates the system for 3 minutes When the stop valve opens again after 3 minutes the d...

Page 9: ...ply when the flow rate exceeds 3500 l h Save the change by pressing the key 6 5 Unlocking the device The next step leads to the menu allowing to un lock the device When the SYR Safe T has isolated the...

Page 10: ...ired status by means of the or key and save the change by pressing the key 6 9 Contact 2 The contact 2 offers many connection possibilities You can connect for instance floor sensors or temperature pr...

Page 11: ...ise the installation with full Hc or re stricted only floor sensor Hd supervision Save the change by pressing the key Press the or key to define the conditions When selecting the restricted supervisio...

Page 12: ...e display 8 Emergency unlock function The emergency unlock function is designed to unlock the system manually in case the SYR Safe T isolates the installation and a power fai lure occurs at the same t...

Page 13: ...s to restart the device 8 1 page 11 Mount the control unit and secure it with the clamp Put the two insulating covers back into place As the position has been changed manually with the emergency unloc...

Page 14: ...alified installers are authorised to install and service the device Do not clean synthetic parts with solvent based detergents Protect the device and the electronic system against frost When submitted...

Page 15: ...Type SYR Safe T Leakage protection module Nominal size DN 20 32 Dimensions T 108 mm t 24 mm T1 105 mm t1 76 mm H 307 mm h 174 mm B 120 mm 15 12 Dimensions...

Page 16: ...has been exceeded Press the key to open the stop valve and eliminate the leakage problem The system has identified a leakage problem at contact IN1 floor sensor Press the key to open the stop valve an...

Reviews: