Symmons Maxline 8210CK Operation & Maintenance Manual Download Page 3

3

Installation

Sizing Valve

For assistance in sizing and selection of the proper
valve, consult your local representative or Symmons
Customer Service.

Installing Valve

1) Flush piping thoroughly prior to installing.

2) Install valve so as to allow clearance for replacing 
    cartridge. Valve can be installed in any orientation.

VALVE 

CLEARANCE

Safety Cap

Retaining Nut

Cartridge

Valve Body

3-1/2”

(89 mm)

3) Connect valve input/ouput to supply ports.
    a. Hot port marked (H)
    b. Cold port marked (C)
    c. Mixed output port marked (M)

Setting Valve Temperature

1) Turn hot and cold water supply on.

2) Open faucet to allow hot water to flow for a
    minimum of one minute. For two handle faucets
    turn on hot water only. For single handle faucets
    turn on to the hot position.

3) Remove screw and cap.

4) Place thermometer in the outlet stream.  Measure
    and accurately set temperature.  Inlet temperature
    must be ± 10°F (5.55°C) of desired output.

5) To 

increase 

temperature  turn  stem  counter-clock-     

    wise. To 

decrease

 temperature turn stem clock-

    wise.

     For single temperature applications adjust valve 
     outlet temperature with full flow of tempered
     water from fitting.

     For dual temperature applications open 
     approximately 50% of all faucets to their full hot
     position to ensure proper operating temperature
     at peak demand.

6) Replace cap and screw once desired tempurature 
has been met

Note:

  Once the safety cap and screw have been 

installed the outlet temperature cannot be changed 
without repeating steps 2-6.

Warning:  Water temperatures in excess of
110°F (43°C) may cause scalding, or
severe injury!