TimeSource 3000
Installation
097-72000-02 Issue 6: October 2003
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
3
Power
Warning:
This equipment is intended for installation in a restricted access location.
Power source protective fusing must be provided as part of the installation.
Caution:
Ensure the fuses in the fuse panel which will be used to power the TimeSource
3000 Shelf are removed before connecting power.
Note:
Input power is reverse polarity protected; there are no user replaceable fuses.
Power connections are made on power terminal blocks TB1 and TB2. Refer to Figure 11 for
the location of the terminals on the rear of the shelf, and refer to Figure 12 for the terminal
connections.
Ensure the power wires are long enough to go from the shelf rear panel to the office battery
source connection.
Use 18 AWG stranded wire to connect -48 volts from office battery A to the -48V A
terminal on TB1. Connect office battery A return to the RTN A terminal on TB1.
Use 18 AWG stranded wire to connect -48 volts from office battery B to the -48V B
terminal on TB2. Connect office battery B return to the RTN B terminal on TB2.
Replace the protective covers on the terminal blocks.
Caution:
Do not apply the office battery to the TimeSource 3000 at this time.
Note:
Two separate office battery supplies (battery A and battery B) are recommended. If
separate office battery supplies are not available, connect a single office battery to both inputs
(TB1 and TB2) to avoid a standing battery-failure alarm.
Summary of Contents for TimeSource 3000
Page 1: ...TimeSource 3000 GPS Primary Reference Source 097 72000 02 Issue 6 October 2003 ...
Page 47: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Page 107: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Page 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...