Chart 8: MAX NUMBER OF ALARMS

DIP 7

NUMBER OF ALARMS DURING 24 HOURS OFTER FIRST ALARM

ON 

(default setting)

Infinite alarms

OFF

Limitation to 4 daily (24 hours) alarms of sounder activation ( T. 5 resets the counter to zero)

Chart 9: SOUNDER TONES

DIP 8

SOUND

FREQUENCY LIMITS (Hz)

dB (A) at 1m

ON 

(default setting)

Increasing-Continuous-Decreasing

1.200–1.750

116

OFF

Increasing-Decreasing (NFC 48-265)

1.400–1.600

115

Chart 6: CONTROL PANEL ON/OFF INDICATION

Chart 10: ANOMALIES

ANOMALY

RED LED LD7

OUTPUT T.6

Speaker interruption (test performed every 10s)

1 FLASH

0V

No recharge current (V recharge < 12V) (test performed every 10s)

2 FLASHES

0V

Battery not connected (test performed every 12 hours)

3 FLASHES

0V

Low battery voltage (V battery < 10.5V) (test performed every 10s)

4 FLASHES

0V

Faulty battery – Internal resistor higher than 2.5 Ohm (test performed every 12 hours)

5 FLASHES

0V

No anomaly

OFF

OPEN

To reset an anomaly, remove its cause first, wait 10 seconds and then give an input to terminal no.3 or no.5.

Installation:

 when supplied, the sounder is in stand-by condition until input 3 “sounder control” is tur-

ned out and turned on again. This prevents the sounder from sounding during installation.

Attention: 

if battery is out of charge (voltage is lower than 10.5V), in case of alarm, the sounder operates 

for 3 seconds only, in order to avoid a deeper discharge.

Usual sounder working: the microprocessor continuously tests the battery voltage. If the battery is out of 
charge (voltage is lower than 10.5V), the sounder sounds for 3 seconds only. Vice versa, the flash keeps 
on working as usual. If voltage decreases under 9.5V, the sounder produces no acoustic alarm and the 
flash does not work to avoid a deeper battery discharge.

Maintenance:

During battery replacement, it is advisable to disconnect the recharge too (Terminal no.2). By proceeding 
so, the complete sounder test will start immediately.
After 30 seconds from power supply reception, the microcontroller performs the battery test. Such test is 
then repeated every 2 hours. If an alarm occurs during the first 30 seconds, the battery anomaly notice 
stays until the following test (which will be performed after 2 hours). If the flashing light activates when 
an anomaly is detected, it will flash fast.
If battery voltage decreases under 10.5V, the LED flashes fast when the sounder is in alarm status or the 
Alarm System ON/OFF mode is enabled.

Summary of Contents for ECO 800

Page 1: ...the sound of security ECO 800 EXTERNAL SOUNDER ...

Page 2: ...ock tamper devices are series connected and in case of tampering attempt they provide the corresponding notice by opening the contact between the two TAMPER terminals ECO 800 LS ECO 800 LSX description technical features as per ECO 800 ECO 800 X models with double micro anti foam anti stock device against hard hits TECHNICAL FEATURES Voltage Nominal voltage of battery recharge 13 0 13 8 V Minimum ...

Page 3: ...ture From 25 C to 70 C Environmental class Class IV IP degree IP 34 Relative working humidity 20 at 100 of relative humidity Size mm 245x250x80 HxLxD Weight ECO 800 3 066 gr ECO 800 X 3 013 gr ECO 800 LS 3 048 gr ECO 800 LSX 2 995 gr Standards compliance INCERT T031 2014 EN50131 4 2009 DIAGRAM 1 MAXIMUM ACOUSTIC PRESSURE AT 1 M ECO 800 LSX DIP8 IN ON POSITION Angle dB A 1 m 15 102 6 45 103 2 75 10...

Page 4: ...ng the screws provided 7 Battery must have UL94 HB flammability rate 8 Power supply must be of SELV type Attention not to have condensation in the sounder it is important to avoid any air flow inside the duct To such purpose once the sounder is connected seal the hole using some silicon or any other plaster This operation prevents condensation from forming inside the sounder condensation mostly ap...

Page 5: ...the sound of security 5 PICT 3 PICT 4 CONNECTION WITH 2 CONTACTS IN TENSION PICT 5 PICT 6 CONNECTION WITH 1 CONTACT IN TENSION ...

Page 6: ...SH BEHAVIOUR ON default setting Not connected or 0V Flashing 12V Blocked OFF Not connected or 12V Flashing 0V Blocked Chart 6 CONTROL PANEL ON OFF INDICATION DIP 4 TERMINAL 5 FLASH BEHAVIOUR ON OFF ON default setting 12V All LEDs flash 3 times Not connected or 0V All LEDs stay on for 4 seconds then switch off OFF 12V All LEDs flash 3 times and 1 LED keeps on flashing Not connected or oV All LEDs s...

Page 7: ... ned out and turned on again This prevents the sounder from sounding during installation Attention if battery is out of charge voltage is lower than 10 5V in case of alarm the sounder operates for 3 seconds only in order to avoid a deeper discharge Usual sounder working the microprocessor continuously tests the battery voltage If the battery is out of charge voltage is lower than 10 5V the sounder...

Page 8: ...1 04 MANUAL ECO800 ENG REV 04 1472638042 WARRANTY All Sylco products are granted against factory or material defects In order to improve design and quality of the products Sylco reserves the right to modify the products without prior notice All faulty or defective products must be returned to the supplier Certified for Belgium Compliant to T031 standards MADE IN ITALY ...

Reviews: