Page | 18
06:
Bypass mode enable/disable.
INTERFACE
SETTING
Parameter 3: Enable or disable Bypass function.
You may choose the following two options:
ENA:
Bypass mode
enable.
DIS: Bypass mode disable (Default).
07:
Bypass voltage range setting.
INTERFACE
SETTING
Parameter 2 & 3: Set the acceptable high voltage
point and acceptable low voltage for bypass mode.
Press the Down key or Up key to set.
HLS: Bypass high voltage point.
For
208/220/230/240 VAC
models:
235-264: setting the high voltage point from
235Vac to 264Vac
(Default: 264Vac).
For
110/115/120/127 VAC
models:
125-132: setting the high voltage point from
115Vac to 132Vac
(Default: 132Vac).
LLS: Bypass low voltage point.
For
208/220/230/240 VAC
models:
184-225: setting the low voltage point from
184Vac to 225Vac
(Default: 195Vac).
For
110/115/120/127 VAC
models:
98-115: setting the low voltage point from
98Vac to 115Vac
(Default: 98Vac).
08:
Autonomy limitation setting.
INTERFACE
SETTING
Parameter 3: Set the backup time on battery mode
for general outlets.
0-999:
setting the backup time in minutes from
0-999 for general outlets on battery mode.
0:
When setting as “0”, the backup time will be
only 10 seconds.
999:
When setting as
“999”,
the backup time setting
will be disabled
(Default).