Page | 17
03:
Output frequency setting.
INTERFACE
SETTING
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is
50Hz.
BAT 60:
presents output frequency is
60Hz.
If
converter mode enable
, you may choose the
following
output frequency
:
CF 50:
presents output frequency is
50Hz.
CF 60:
presents output frequency is
60Hz.
04:
ECO enable/disable.
INTERFACE
SETTING
Parameter 3: Enable or disable ECO function.
You
may choose the following two options:
ENA:
ECO mode
enable.
DIS: ECO mode disable (Default).
05
: ECO voltage range setting.
INTERFACE
SETTING
Parameter 2 & 3: Set the acceptable high voltage
point and low voltage point for ECO mode.
Press the Down key or Up key.
HLS: High loss voltage in ECO mode.
For
208/220/230/240 VAC
models, the setting range
are from
+7V to +24V
of the nominal voltage
(Default:
+12V).
For
110/115/120/127 VAC
models, the setting range is
from
+3V to +12V
of the nominal voltage
(Default:
+6V).
LLS: Low loss voltage in ECO mode.
For
208/220/230/240 VAC
models, the setting range is
from
-7V to -24V
of the nominal voltage.
(Default: -
12V).
For
110/115/120/127 VAC
models, the setting range is
from
-3V to -12V
of the nominal voltage
(Default: -6V).