Page | 9
5)
Remove the terminal block cover on the rear panel of UPS. Then connect the
wires according to the following terminal block diagrams: (Connect the earth
wire first when making wire connection. Disconnect the earth wire last when
making wire disconnection!)
NOTE 1:
Make sure that the wires are connected tightly with the terminals.
NOTE 2:
Please install the output breaker between the output terminal and the
load, and the breaker should be qualified with leakage current protective
function if necessary.
6)
Put the terminal block cover back to the rear panel of the UPS.
Warning:
(Only for standard model)
o
Make sure the UPS is not turned on before installation. The UPS should not be
turned on during wiring connection.
o
Do not try to modify the standard model to the long-run model. Particularly, do
not try to connect the standard internal battery to the external battery. The
battery type and voltage may be different. If you connect them together, it
maybe causes the hazard of electric shock or fire!
Warning:
(Only for long-run model)
o
Make sure a DC breaker or other protection device between UPS and external
battery pack is installed. IF not, please install it carefully. Switch OFF the battery
breaker before installation.