60
FIRE DAMPER - FD
UPGRADE
TO ELECTRIC
ACTUATOR
Manual
R25 <-> Belimo
100x200 to 800x600
The blade must be closed before replacement the
mechanism.
NOTE
: Use Kit C (FD-A-KTC) to upgrade to
electric actuator!
* Before replacing the mechanism, the damper
blade must be closed.
* Find the screw and remove the cover!
1. Find the 2 hex screws located on the board of
mechanism, unscrew them and remove manual
mechanism.
2. Find the 2 hex screws located on the
transition board (B), unscrew them and replace
FA transition plate (A) with BE transition plate.
NOTE
: Pay attention to the position of indication
cut (C) on the BE transition plate.
3. Insert the rubber plug into the opening for
the thermal fuse. Install the Belimo actuator and
fasten it with screws (2 hexagon screws M6x55).
4. Drill hole (ø16 mm) for the fuse of Belimo
mechanism and fix it with self-tapping screws.
NOTE
: Install the thermal fuse in a place where
it will not interfere with the operation of the
damper blade !
Test the operation of the damper blade!
1
4
3
2
A
B
C
REPLACEMENTS