54
EXTRA FIREPLACE SWITCH
Operation
An extra fireplace contact (return-spring-loaded pressure switch) can be installed near the fireplace.
The fireplace function causes temporary positive pressure in the building, making it easier to light a fire in the fireplace.
Use the Premium panel for enabling the function from the menu
Installation and service/Functions/Fireplace function.
The code for access to the Installation and service menu is 1234.
CARBON DIOXIDE SENSOR
Operation
If the carbon dioxide content exceeds 900 ppm (factory setting) the ventilation unit fans will begin operating at Boost speed.
Use the Premium panel for enabling the function from the menu
Installation and service/Functions/Boost.
The code for access to the Installation and service menu is 1234.
HUMIDITY SENSOR
Operation
If the humidity exceeds the humidity sensor’s limit setting, the ventilation unit fans will begin operating at Boost speed, and continue to
operate at that speed until the humidity drops below the limit value.
Use the Premium panel for enabling the function from the menu
Installation and service/Functions/Boost.
The code for access to the Installation and service menu is 1234.