DETECT
IAQ
2
Swegon reserves the right to alter specifications. 20220705
Installation
DETECT IAQ should ideally be mounted between 1.5
to 1.8 m above the floor on the surface of a wall using
screws, see figure 1.
The installation position needs to be selected with care to
eliminate fault factors that can affect the measurement.
The sensor should not be exposed to sunlight, draughts or
temperature differences caused by external walls.
DETECT IAQ Da CO
2
-TEMP-MB is installed in a ventilation
duct.
Figure 1. Recommended installation in a room or duct.
1,5-1,8 m
DETECT IAQ Da CO
2
-TEMP-MB
DETECT IAQa CO
2
-TEMP-MB
DETECT IAQ OCSa CO
2
-TEMP-MB
Figure 2. Dimensions, DETECT IAQa CO
2
-TEMP-MB and
DETECT IAQ OCSa CO
2
-TEMP-MB.
87 mm
86 mm
< 33 mm
Figure 3. Dimensions, DETECT IAQ Da CO
2
-TEMP-MB.
46 mm
106 mm
111 mm / Ø 10 mm
102 mm
Dimensions
0 m
6 m
6 m
5 m
35°
35°
10,8 m
Vertical
0 m
2 m
2 m
5 m
1,8 m
Coverage for PIR detection in
DETECT IAQ OCSa CO
2
-TEMP-MB
Horizontal