8. Commissioning form
Function
Factory setting
Setting value
Fan speeds
Away, supply air fan
50 %
Away, extract air fan
50 %
Home, supply air fan
65 %
Home, extract air fan
65 %
Boost, supply air fan
80 %
Boost, extract air fan
80 %
Travelling, supply air fan
50 %
Maximum automatic boost, supply air fan
80 %
Smart settings
A
+
, Home limit
900 ppm
A
+
, Away limit
600 ppm
Cooker hood function, compensation (home)
20 %
Cooker hood function, compensation (boost change)
0 %
Cooker hood function, boost of cooker hood
0 %
Fahood function, operation of roof fan
Not used
Central vacuum function, compensation
20 %
Air flows | NOTE! All the fan modes should be preset.
Project planning values
Setting value
Supply air, total
l/s m
3
/h
l/s m
3
/h
Away
Home
Boost
Extract air, total
l/s m
3
/h
l/s m
3
/h
Away
Home
Boost
Ventilation unit data |
Write down the data on the ventilation unit identification plate for reference when the
need arises to contact a service company.
Preset by:
Date:
Important
The supply air flow must be 2–10 % lower than the extract air flow.
Remember to explain the use of the item of optional equipment and how to service it to the
user/caretaker!
!