The ventilation system’s settings in connection with
commissioning and servicing are made from the pass-
word-protected “Settings” menu on a Smart control
panel. To open the menu, enter code 1234. (The code
can be changed). In conjunction with commissioning,
you always need to set at least the air flow and carry
out any adjustments to the Smart sensor if fitted.
Settings
Airflow adjustments
IO controls
Smart functions
Heating / Cooling
Defrost settings
Reset factory settings
Change service code
3.1 Air flows
Sizing curves for air flows are set out in the section
“Technical data”. A qualified person should set the ven-
tilation unit’s and the ventilation equipment’s air flows
with the help of measurement equipment so that they
correspond with the ventilation plan.
All basic air flows must be set so that the ventila-
tion unit operates correctly!
Enter the settings in the
commissioning protocol.
In new homes, there is still construction moisture and the
house initially requires higher ventilation in order to remove
the moisture from the building. A great deal of moisture
in the home manifest itself in the form of moisture on cold
surfaces. We recommend that in new houses to use higher
volumes of air at first to remove moisture.
It is recommended in order to improve the efficiency of
the ventilation to use an automatic moisture sensor or to
actively use the ventilation unit’s boost speed, if there is a
sauna, pool or equivalent moisture producer in the home.
3. Commissioning
3.1.1 Setting the basic air flows
Before you start to adjust the air flows, ensure that the
filters are clean and that there are no foreign objects or
debris inside the ventilation unit.
Choose commissioning mode when the ventilation
unit’s fans run at the speed being set and functions that
can disrupt the setting, such as anti-freeze protection,
are disabled.
Airflow adjustments
Commissioning mode
Home (exhaust)
Away (supply)
Away (exhaust)
Boost (supply)
Boost (exhaust)
Travelling (supply)
Max Smart boost (supply)
50%
35%
38%
90%
92%
35%
82%
Control type
Fan control
Home (supply)
48%
Adjust the control functions for the operating modes
Home
,
Away
and
Boost
so that the air flow rates ac-
cording to the ventilation plan are reached.
Fill in your entered settings in the commissioning report.
3.1.2 Travelling
You can reduce ventilation unit’s power consumption
by using the “Travelling” function, when the home is
empty for long periods, among others by reducing the
ventilation. Set the supply air flow to “Travelling” mode.
The extract air flow is determined automatically based
on the basic air flows.
3.1.3 Maximum automatic boost
Automatic functions boost the ventilation as required all
the way up to the maximum automatic boost. The func-
tions can be limited by reducing the value.
3.2 Commissioning external equipment
External equipment can be connected to the ventila-
tion unit’s configurable I/O connections (connection
Important
Set the air flows in accordance with national
regulations when you commission the ven-
tilation system. The system should be com-
missioned by a qualified person, and the air
flows must not be changed on one’s own
responsibility, since doing so could disrupt
the way the ventilation system operates.
!
!
Important
The functions described in this instruction
apply to the ventilation unit and control
panels with software version 1.12 and later.
In older control panels they only apply to
basic functions.
!
!
Setting the air flows
https://serviceportal.swegon.com/fi//docs/PROvideo1_EN