3.2 Cooker hood function
The cooker hood function balances the air flows when the
cooker hood is used. This will help to prevent house nega-
tive pressure and improves fume extraction capability. The
ventilation boost level during the function can be defined.
The function starts automatically when the damper in a
Swegon CASA cooker hood is opened or when a cooker
hood defined IO is active.
The function and the air flows can be commisioned
from the menu
Settings
/
(1234)/Smart functions/Cooker
hood boost.
Cooker hood function
Home state Compensation
Boost state Compensation
10%
Hood boost
0%
Roof fan
30%
In use
Commissioning mode
Choose commissioning mode.
The ventilation unit’s fans
run at the selected speed and functions, such as anti-freeze
protection and heat exchanger by-pass, are disabled.
Open the cooker hood damper.
Define the cooker hood air flows
in order to adjust
function values.
Home state Compensation.
Adjust the Home mode
compensation value so that the supply and e
cooker hood air flows are in balance. Compensation
increases supply air flow. (If roof fan compensation is
selected, the extract air flow is first reduced).
Boost state Compensation.
Fine tune Boost mode
compensation value if necessary.
Hood boost
adjusts the ventilation level during the func-
tion, for example, to achieve sufficient discharge velocity
or odour extraction.
Choose
Roof fan
when using a cooker hood which is
connected to the roof fan. Compensation is achieved by
slowing the extract air fan.