4. Commissioning

The kitchen must have separate general 
ventilation. The general ventilation in the 
kitchen must not be routed via the cooker 
hood damper when the cooker hood's duct 
is connected to the ventilation unit's separate 
extract air duct.

The basic air flow setting is made (damper 
closed) by opening the existing hole in the 
damper. On delivery, all the holes for basic air 
flow are sealed. See the control curve for basic 
ventilation in the “Technical data” section.

The air flow is obtained by measuring the 
pressure differential across the control damper 
inside the cooker hood and then reading the 
air flow that corresponds to the control 
position. Measure the pressure in the hole 
next to the control damper arm as shown in 
the diagram to the right. There is a rubber 
bushing with a hole to read the air flow in the 
cooker hood’s accessory bag.

Measured pressure differential

Measured pressure differential

The measurement of the air flow for boosted 
ventilation is also performed via the hole in 
the damper. After measurement, the hole can 
be blanked off with the extra plugs included 
in the delivery.

Ventilation balance

 

It is important that the home’s ventilation 
is balanced when the cooker hood is used, 
as the excess extract air that passes via the 
hood causes negative pressure in the home. 
Balancing occurs automatically when the 
cooker hood is connected to a Smart ventila-
tion unit. The function is taken in use and also 
controlled via a SMART ventilation unit. 

Operation with power roof ventilator 

Swegon CASA cooker hoods can be used to 
control a power roof ventilator, equipped with 
an EC-fan.

Connect the EC-power roof ventilator’s 
control cable to the cooker hood using the 
supplied connector  
(see the Electrical wiring diagram, item 8).

The default factory setting is for the cooker 
hood to control the power roof ventilator as 
a boost function with three speeds, except 
the OFF position. Use of the OFF-position is 
programmed from the cooker hood. When 
the OFF function is used, all the speed indica-
tion signal lamps go out and the power roof 
ventilator is set to the OFF position when the 
fan speed button  is pressed a fourth time.

Commissioning the OFF position

•  Long press both the fan speed selector 

and damper control buttons (   +   ) => 
the centre signal lamp for speed indication 
is on indicating that the control mode is 
activated.

•  The OFF position is indicated by a flash-

ing LED. Change the selection with the 
fan speed selector and damper control 
buttons:

 

- fan speed 

OFF

 

    right-hand signal lamp flashes     

 

- fan speed 

ON

 

    left-hand signal lamp flashes

•  Acknowledge the selection with a long 

press of the cooker hood’s lighting button

.

Summary of Contents for CASA Smart Sensor

Page 1: ...P_Hoods_l u 2020 12 22 K SIKIRJA HANDBOK FI SE Blues Salsa Samba Tango Jazz Swegon CASA Smart H NDBOK HANDBOOK NO EN...

Page 2: ...or the cooker manufacturer Always consult your local fire consultant prior to instal lation if the relative space is smaller than 500 mm between the cooker hood and the hob Replacement air Ensure suf...

Page 3: ...sories 44 7 1 External control functions 44 7 2 Safera safety technology 44 7 3 Twist fan unit 44 7 4 ILVA transformer unit 44 7 5 Ext out relay for 230 V 44 8 Technical data 45 8 1 Capacity for captu...

Page 4: ...used for controlling ventilation units equipped with Smart control technology EC power roof ventilator Swegon CASA cooker hoods can be used to control a power roof ventilator equipped with an EC fan...

Page 5: ...on is balanced when the cooker hood is used as the excess extract air that passes via the hood causes negative pressure in the home Balancing occurs automatically when the cooker hood is connected to...

Page 6: ...on shows which mode is being set NOTE The fan speeds for the operating modes can only be set in the order low to high for example the Away mode speed cannot be higher than the Home mode speed Increase...

Page 7: ...ting is switched on and off with a button The factory default of the lighting output is 75 5 1 2 3 4 The lighting output can be regulated with a long press on the button the brightness then changes Pr...

Page 8: ...erial and manufacturing faults is limited to the repair or 7 Accessories POWER 24 VDC EXT OUT NO NO CONTROL max 30 V 5 A replacement of the defective product unless compulsory legislation states other...

Page 9: ...3141 3 2017 75 48 l s Odour capture Airflow rate l s according to EN13141 3 2017 75 48 l s 30 40 50 60 70 80 90 10 15 20 25 30 35 40 Odour capture Airflow rate l s according to EN13141 3 2017 75 51 l...

Page 10: ...0 10 100 Airflow rate l s Pressure drop Pa Salsa Airflow rate l s Pressure drop Pa LWA 20 LWA 30 LWA 40 LWA 50 1 10 100 10 100 Tango Airflow rate l s Pressure drop Pa LWA 20 LWA 30 LWA 40 LWA 50 1 10...

Page 11: ...20 40 60 80 100 120 140 160 180 200 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Air flow rate l s Pressure differential Pa Air flow rate l s Pressure differential Pa Open holes in the damper 1 2 3 4 5 6...

Page 12: ...or EC power roof ventilator 0 10 VDC 4 Ext in control of damper and lighting with potential free contact signal 5 Ext out damper position signal normally open Connector in accessory bag POWER 24 VDC...

Page 13: ......

Page 14: ......

Reviews: