Trouble shooting: 

 

Fault 

Possible problem 

Recommended action 

Control Mode does not fit to 
damper drive shaft when 
Control Mode is correctly 
positioned 
 

Damper shaft not in ‘damper 
closed’ position 

Damper shaft has an ‘indication 
groove’ which is parallel to damper 
blades. Damper must be in closed 
position before fitting Control mode. 

Control Mode does not 
operate electrically  

ExPro not correctly fitted 

Refer to Page 3. 

Mode wired incorrectly / No power 

Refer to above wiring diagram 

STS activated 

Replace STS. 

Control Mode operated, but 
limited or no movement of 
damper blades evident 

 

Damper/Control Mode positions not 
synchronised 

Remove Control Mode. Check 
damper closed (see indication 
Groove on damper shaft), and 
Control Mode released. Refit Control 
Mode. 

Obstruction impeding damper 
blade 

Check visually, remove obstruction. 
If necessary, remove Control Mode 
and operate damper drive shaft with 
14mm A/F spanner. 

Over tightening of M5 x 80mm 
screw. (3 position only) 

Loosen screw to 5Nm torque. 

  

 

 

 

 

To isolate from main power supply, the system must incorporate a device, which disconnects the phase 
conductors, with at least 3mm contact gap. 

 
Special Conditions of Safe Use 

1.

 

The associated spring return failsafe actuator must be suitably rated ATEX certified for the hazardous 
atmosphere into which it is to be installed.  

2.

 

The equipment must be suitably bonded to a common earth point and continuity to be checked upon 
installation. 

3.

 

The equipment must not be subjected to charging mechanisms stronger than manual rubbing. 

4.

 

The minimum ignition energy of dust atmospheres into which the equipment is installed is to be >1mJ 

 
Please refer to Schischek data sheets or website for further information 

LNNN00315 – REV 5 

Swegon Air 
Management are 
ISO9001 & ISO 
14001 certified 

 

 

 

 

Summary of Contents for Actionair A60

Page 1: ... inspection programme 5 Installation see below 6 Maintenance Cleaning Dampers are supplied in two casing and blade material options 1 Galvanised Steel casing and 430 Stainless steel blades only suitable for installation in dry filtered systems 2 316 Stainless steel casing and blades and drive more suited for corrosive conditions but even this will rapidly corrode and fail if not properly maintaine...

Page 2: ...andard on the damper flanges unless otherwise stated at 150mm maximum centres Matching hole positions are necessary on mating coaming duct flanges Apply approved fire resistant sealant gasket to mating flanges and position damper Bolt A60 square rectangular dampers using suitable steel bolts minimum M8 diameter and minimum M6 diameter on A60 circulars Important For insulation lengths please refer ...

Page 3: ...central hole Remove sharp edges Push the ExPro TT through the duct and ensure that both screws are used to hold it securely in position The ExPro TT cable must not be shortened and care must be taken not to damage it 14 Electrical Connection and Final Operational Test The unit must be wired as described in the Application and Wiring section 17 When power is available the unit must be checked for e...

Page 4: ... mounting dimensional date Schischek 5 10Nm Schischek 15Nm Actuator mounting brackets riveted to damper casing Figure 6 Screw Washer Pointer 2 spacers ExPro TT Actuator mounting plate Damper drive shaft ExPro TT Safety Temperature Sensor c w 1mtr halogen free cable Test button Figure 7 Figure 8 ...

Page 5: ...Application wiring Important Please fully read the Schischek data sheets provided with every actuator For 5 10 actuators 10Nm 3 sec 90 must be selected For 15Nm actuators 3 sec 90 must be selected Make sure that 1 cycle per minute is not exceeded ...

Page 6: ...ruction impeding damper blade Check visually remove obstruction If necessary remove Control Mode and operate damper drive shaft with 14mm A F spanner Over tightening of M5 x 80mm screw 3 position only Loosen screw to 5Nm torque To isolate from main power supply the system must incorporate a device which disconnects the phase conductors with at least 3mm contact gap Special Conditions of Safe Use 1...

Reviews: