10. Damper installation 
All installations shall be carried out in accordance with the 
relevant Marine/Offshore Authority requirements.  
The damper should be installed in accordance with Insulation 
details that represent a typical installation.  
Please refer to the relevant notified body certificates for 
insulation lengths located on Actionair website: 

https://www.actionair.co.uk/products/a60-marine-damper

 

Bolt holes provided as standard on the damper flanges (unless 
otherwise stated) at 150mm maximum centres. Matching hole 
positions are necessary on mating coaming/duct flanges. 
Apply approved fire-resistant sealant/gasket to mating flanges 
and position damper. 
Bolt A60 square/rectangular dampers using suitable steel bolts 

minimum M8 diameter and minimum M6 diameter on A60 
circulars.

Important: 

For insulation lengths 

** 

please refer to the relevant notified body certificates located on 

Actionair website: 

https://www.actionair.co.uk/products/a60-marine-damper

 

 

Multiple Damper Assemblies 

Tested and approved to a size of either; 
(2x1) 2080mm x 1000mm  

or (1x2) 1000mm x 2080mm  
 

 

Figure 1  

Figure 2  

 

Figure 3  

Figure 4  

Summary of Contents for Actionair A60

Page 1: ... inspection programme 5 Installation see below 6 Maintenance Cleaning Dampers are supplied in two casing and blade material options 1 Galvanised Steel casing and 430 Stainless steel blades only suitable for installation in dry filtered systems 2 316 Stainless steel casing and blades and drive more suited for corrosive conditions but even this will rapidly corrode and fail if not properly maintaine...

Page 2: ...andard on the damper flanges unless otherwise stated at 150mm maximum centres Matching hole positions are necessary on mating coaming duct flanges Apply approved fire resistant sealant gasket to mating flanges and position damper Bolt A60 square rectangular dampers using suitable steel bolts minimum M8 diameter and minimum M6 diameter on A60 circulars Important For insulation lengths please refer ...

Page 3: ...central hole Remove sharp edges Push the ExPro TT through the duct and ensure that both screws are used to hold it securely in position The ExPro TT cable must not be shortened and care must be taken not to damage it 14 Electrical Connection and Final Operational Test The unit must be wired as described in the Application and Wiring section 17 When power is available the unit must be checked for e...

Page 4: ... mounting dimensional date Schischek 5 10Nm Schischek 15Nm Actuator mounting brackets riveted to damper casing Figure 6 Screw Washer Pointer 2 spacers ExPro TT Actuator mounting plate Damper drive shaft ExPro TT Safety Temperature Sensor c w 1mtr halogen free cable Test button Figure 7 Figure 8 ...

Page 5: ...Application wiring Important Please fully read the Schischek data sheets provided with every actuator For 5 10 actuators 10Nm 3 sec 90 must be selected For 15Nm actuators 3 sec 90 must be selected Make sure that 1 cycle per minute is not exceeded ...

Page 6: ...ruction impeding damper blade Check visually remove obstruction If necessary remove Control Mode and operate damper drive shaft with 14mm A F spanner Over tightening of M5 x 80mm screw 3 position only Loosen screw to 5Nm torque To isolate from main power supply the system must incorporate a device which disconnects the phase conductors with at least 3mm contact gap Special Conditions of Safe Use 1...

Reviews: