background image

 

 
 

 

 
 

www.actionair.co.uk 
[email protected] 

11. Control Modes (3 positions) 

(Refer to figure 8) 

Two sizes of Control Modes are utilised - 5.10Nm & 15Nm. 
Correctly sized Control Modes are designed to fit only to the 
relevant sized damper. (See ‘Control Mode Standard 

Parameters’ figure) (Refer to figure 5) 
Remove transit plate from damper mounting plate and recycle. 
Mount actuator to damper mounting brackets & secure with 
screw & washer provided - 5Nm Max. (Refer to figure 6) 
Its important to fit the 2 spacers provided. (Refer to figure 6) 
Never operate the manual override (shaft) when actuator is 

connected to power supply. 
Actuators will only work if Safety temperature sensor (ExPro TT) 

is properly connected. (Refer to figure 7) 

*IMPORTANT* - please ensure damper blades are in the fully 
closed position prior to mounting actuators. Failure to do so 

may damage drive shafts and render the damper inoperable. 

12. Mechanical Operation check 
As an interim check, the damper should be manually reset and 
released using the manual reset key provided, (refer to Control 

Mode label) to ensure that correct mechanical operation is 
achieved. This feature may be used for system commissioning 

when electrical power is unavailable. Note however, the ExPro TT 
is not operable without electrical power, and the damper will 

not close automatically should a temperature rise or fire occur.

 

13. Safety Temperature Sensor (ExPro TT) Installation (When not 

affixed to damper casing, 210mm wide casing option only) 
Select a suitable position for the ExPro TT on the duct as follows: 

Deck Installations – Must be anywhere below the damper.  
Bulkhead installations – Ideally this should be anywhere in the top 

half of the duct. 
Position the self-adhesive ExPro TT drilling template label 

provided in the appropriate position on the duct. 
Using a 2.5mm dia bit, drill the two ExPro TT fixing holes. 

Using a 10mm dia drill, drill the central hole. 
Remove sharp edges. 

Push the ExPro TT through the duct and ensure that both screws 
are used to hold it securely in position.  

The ExPro TT cable must not be shortened, and care must be 
taken not to damage it. 
14. Electrical Connection and Final Operational Test 
The unit must be wired as described in the Application and 

Wiring section 17. When power is available, the unit must be 
checked for electrical operation. Power on to motor open, power 

off to spring close. The unit must also be checked by moving 
and holding the test switch on the ExPro TT to confirm that the 

damper closes. When pressure is removed from the switch the 
damper will re-open. This may be done after the initial 

installation test, to provide periodic operation of the damper to 
simulate actual fail-safe closure under fire conditions.  

Schischek actuators are equipped with a universal supply unit 
working at a voltage range from 24 to 230 VAC/DC. The supply 

unit is self-adjustable to the connected voltage! The safety 
operation of the spring return function works if the supply voltage 

is cut. For electrical connection inside hazardous areas, an   EEx-
e terminal box, certified in accordance with ATEX is required (E.G 

ExBox XNNN00578) 

 

 
 

 
 

 
 

 
 

 

 

Electrical ATEX (Ex) rated as below  

Fail-safe is by means of an ExPro-TT which operates at 72 °C, or 
if power supply is interrupted. 

A manual test button (Refer to figure 7) allows periodic 
operation of the damper for testing purposes, simulating actual 

fail-safe release under fire conditions. 
The associated electrical Control Modes are available in one 

Universal version with 24 – 230V AC/DC supply.  

 

ExMax ATEX classification; 

Explosion proof Zone 1, 2, 21 & 22 gas & dust PTB-certified 
II 2(1) G Ex d [ia] llC T6 

ll 2 G Ex d ia llC T6 
ll 2 D Ex tD A21 IP66 T80 oC 

ATEX 94/9/C, IEC-Ex 

RedMax ATEX classification; 

Explosion proof Zone 2 & 22 gas & dust PTB-certified 
II 3(1) G Ex nC [ia] llC T6 

ll 3 G Ex nC ia llC T6 
ll 3 D Ex tD A22 IP66 T80 oC 

ATEX 94/9/EC 
IEC-Ex 

InMax 

actuators are IP66 classified  

NOT ATEX classified and only for use in safe areas 

 
 

 

 
 

 
 

 
 

 
 

 
 

 
 
 

15Nm 

 
  5.10 Nm 

Figure 5 

Summary of Contents for Actionair A60

Page 1: ... inspection programme 5 Installation see below 6 Maintenance Cleaning Dampers are supplied in two casing and blade material options 1 Galvanised Steel casing and 430 Stainless steel blades only suitable for installation in dry filtered systems 2 316 Stainless steel casing and blades and drive more suited for corrosive conditions but even this will rapidly corrode and fail if not properly maintaine...

Page 2: ...andard on the damper flanges unless otherwise stated at 150mm maximum centres Matching hole positions are necessary on mating coaming duct flanges Apply approved fire resistant sealant gasket to mating flanges and position damper Bolt A60 square rectangular dampers using suitable steel bolts minimum M8 diameter and minimum M6 diameter on A60 circulars Important For insulation lengths please refer ...

Page 3: ...central hole Remove sharp edges Push the ExPro TT through the duct and ensure that both screws are used to hold it securely in position The ExPro TT cable must not be shortened and care must be taken not to damage it 14 Electrical Connection and Final Operational Test The unit must be wired as described in the Application and Wiring section 17 When power is available the unit must be checked for e...

Page 4: ... mounting dimensional date Schischek 5 10Nm Schischek 15Nm Actuator mounting brackets riveted to damper casing Figure 6 Screw Washer Pointer 2 spacers ExPro TT Actuator mounting plate Damper drive shaft ExPro TT Safety Temperature Sensor c w 1mtr halogen free cable Test button Figure 7 Figure 8 ...

Page 5: ...Application wiring Important Please fully read the Schischek data sheets provided with every actuator For 5 10 actuators 10Nm 3 sec 90 must be selected For 15Nm actuators 3 sec 90 must be selected Make sure that 1 cycle per minute is not exceeded ...

Page 6: ...ruction impeding damper blade Check visually remove obstruction If necessary remove Control Mode and operate damper drive shaft with 14mm A F spanner Over tightening of M5 x 80mm screw 3 position only Loosen screw to 5Nm torque To isolate from main power supply the system must incorporate a device which disconnects the phase conductors with at least 3mm contact gap Special Conditions of Safe Use 1...

Reviews:

Related manuals for Actionair A60