Button lock/unlock
To LOCK buttons press and hold + and then – and hold both of them for 5 seconds
To UNLOCK buttons press and hold + and then – and hold both of them for 5 seconds.
Press MODE
Change on manual mode or automatic mode
Hold MODE for 5 seconds
Change to cool mode heating mode ventilation
Press FAN
Change the fan speed low medium high automatic
Hold FAN for 5 seconds
Manual callendar programming Monday – Friday, Saturday, Sunday 6 settings per day
BMS Functions
• Setting/Reading work parameters Work/Stop conditions
• Weekly program
• Temperature
• Fan speed
• Heating, ventilation, cool mode Antifreeze mode
SOLANO RANGE
ium
-
;
14.
Panel intelligent - programmable controller manual
Panel Intelligent controls actuators/valves and automatically regulates fan’s speed depending on the required room temperature.
The lower temperature in the room the higher air output is set. Fans speed changes automatically for lower rate, when temperature in a
room gets closer to desired one.
Functions
Panel INTELLINGENT is designed for the Smith’s products
• Weekly thermostat (5/1/1 days)
• Automatic or manual 3-step fan speed adjustment.
• Control room temperature (by opening/closing the vale, or
by adjusting air volume automatically).
• Antifreeze mode- protection against dropping room
temperature be-low critical level +5/-15°C.
• Possibility to connect external NTC temperature sensor.
• BMS communication by MODBUS protocol
SOLANO RANGE
1
Power supply
230VAC/50Hz
2
Temperature setting range
5°C 40°C
3 Temperature working range
-10°C 60°C
4
IP class
20
5
Temperature sensor
Internal / external NTC (optional)
•
•
•
•
•
•
Prędkość pracy
żeniowe
Ustawienia ręczne
6 stref czasowych na dobę
Tryb chłodzenie
Blokada ustawień
Panel description
SOLANO RANGE
1
Power supply
230VAC/50Hz
2
Temperature setting range
5°C 40°C
3 Temperature working range
-10°C 60°C
4
IP class
20
5
Temperature sensor
Internal / external NTC (optional)
•
•
•
•
•
•
Prędkość pracy
żeniowe
Ustawienia ręczne
6 stref czasowych na dobę
Tryb chłodzenie
Blokada ustawień
SOLANO RANGE
1
Power supply
230VAC/50Hz
2
Temperature setting range
5°C 40°C
3 Temperature working range
-10°C 60°C
4
IP class
20
5
Temperature sensor
Internal / external NTC (optional)
•
•
•
•
•
•
Prędkość pracy
żeniowe
Ustawienia ręczne
6 stref czasowych na dobę
Tryb chłodzenie
Blokada ustawień
1. Fan Speed: LOW, MED, HI and AUTO
2. ROOM TEMP or NTC EXTERNAL SENSOR TEMP
(measured temperature)
3. Anti-freeze indication
4. Automatic programmable mode
5. Manual mode
6. 6 Time Zones for each day
7. Cooling mode
8. Heating mode
9. Ventilation mode
10. Buttons lock
11. SET TEMP. (desired room temperature)
12. ON/OFF status time zones
13. MODE
Press shortly to select manual or automatic mode
Press and hold for 3s and select cooling, heating or
ventilation mode
14. FAN
Press shortly and select fan speed: Low, Med, High or Auto
15. ON/OFF INTELLIGENT Panel
Technical parameters
1
Power supply
230VAC/50Hz
2
Temperature setting range
5°C 40°C
3
Temperature working range
-10°C 60°C
4
IP class
20
5
Temperature sensor
Internal/external NTC (optional)
WARNING!
RISK OF ELECRICAL SHOCK. Disconnect power supply before making any electrical connections. Contact with
components carrying hazardous voltage can cause electrical shock and may result in severe personal injury
Dimensions
Setting menu
When Panel Intelligent is switched off, press and hold MODE for 5
seconds
To change option use MODE button
To change value use +/- buttons.
Setting
menu
Option
Value
1
Temperature calibration
–9°C ~ +9°C
2
Fan status
C1: Thermostatic mode | C2: Continuous mode
3
Temperature sensor
0: Internal Sensor | 1: External Sensor NTC (optional)
4
Antifreeze
0: Off | 1: On
5
Antifreeze range
+5°C ~ +10°C
6
BMS speed
0-2400 / 1-9600 / 2-19200
7
Modbus ID
1~247 (01~F7)
No.
Setting
Parameters
1
Working Mode
RS485 Semi-duplex; PC or main controller is master; thermostat is slave
2
Interface
A(+),B(-), 2 wires
3
Baud Rate
0-2400 / 1-9600 / 2-19200
4
Byte
9 bits in total: 8 data bit + 1 stop bit
5
Modbus
RTU Mode
6
Transmission
RTU (Remote Terminal Unit) format (please refer to MOBUS instruction)
7
Thermostat address
1-247: (0 is broadcast address and stand for all thermostat without response)
SOLANO RANGE
-
;
SOLANO RANGE
-
;
SOLANO RANGE
e
-
;
SOLANO RANGE
ion
-
;
SOLANO RANGE
-
;
SOLANO RANGE
-
;
SOLANO RANGE
w
-
;
SOLANO RANGE
-
;
SOLANO RANGE
-
;
1
2
3
4
5
6
7
8
9
10
230V/50Hz
N
L
High Med.
Low
FAN
N
RS485
A/+ B/-
External NTC
(optional)
VA
LV
E
MODE
FAN
138
94
36.5