Sven Smart RM 2000 User Manual Download Page 17

Eng

SMART RM 2000/3000 2U

(II) Mute Switch

Press and hold this button for 1 second, the UPS will mute the alarm after a short beep. Press and hold this button for another 1 second,
the UPS will restore the alarm function after a short beep.

(III) On-Line/Booster and Buck LED

When the unit is in the AC normal mode, this green LED indicator will always be on.  It will be off when the unit is off. When the auto-
matic voltage regulator (AVR) is operating, this LED will blink.

(IV) On-Battery LED

The On-battery LED will be constantly illuminated and the UPS will beep once every 10 seconds until the unit reaches low battery warn-
ing or the unit returns to AC normal. 

(V) Overload LED

When the unit senses an over-current condition on the output, this yellow LED will be lit and an alarm will sound continuously to indicate
an overload condition. If this condition happens, refer to the "Troubleshooting" section for recovery process. 

(VI) Weak Battery/Internal Fault LED

When the battery goes bad, weak or becomes disconnected, this red LED will light indicating that the battery is not usable and must be
replaced. The alarm will sound 3 beeps every 1 minute if the battery is bad or disconnected. The alarm will sound 1 beep on every 1 sec-
ond if the battery is in low battery condition. The LED and alarm will remain in these states until the battery is replaced. Please follow this
procedure if this should happen:
STEP 1: Charge the UPS for approximately 8 hours.
STEP 2: Test the battery by turns the UPS OFF and back ON again.
STEP 3: If the LED lights and alarm sounds again, the battery must be replaced. Please contact your agent for more information.
This red LED will also light when the unit has an internal fault. This red LED will be off when all functions are normal.

(VII) Load LEDs 

The four LEDs indicate the load percentage on the UPS output. Each LED indicates 25% of UPS capacity. When all four LEDs are lit,
the UPS is fully loaded.

(1) AC Input Socket 

For 220V version, included is one standard IEC320 male socket.

(2) Input Circuit Breaker

The Circuit Breaker protects equipment plugged into the outlet against short circuits or system overload. The UPS will trip the breaker
when loads exceed the UPS's capacity. If the circuit breaker is tripped, unplug at least one piece of equipment from the outlet and reset
the breaker by pressing the button back into place.
If the AC input current is greater than the circuit breaker's regulated currency, the UPS's rear panel circuit breaker may tripped. 
If the breaker is tripped, the UPS will attempt to operate the load by using its internal power source. If the UPS detects an overload con-
dition and the breaker is tripped,  turn off the UPS and decide which equipment can be left unprotected without causing any damage. Find
the input circuit breaker on the rear panel and reset the breaker by pressing the button back into position. Then restart the UPS.

Note:

Generally the over-current accidents happen when there is an overload condition.

(3) Output Circuit Breakers

6 battery output sockets and 1 bypass output sockets equipped with a breaker respectively to protect against being over current on the
output. Circuit breaker is tripped when overload conditions happen.

(4) The additional socket outlet (Eurosocket).

The additional socket outlet of the general type. It is connected in parallel the basic target sockets.

(5) Battery Back and Surge Protection Outlets

IEC 320 female socket for 220V series. These provide instantaneous back-up power protection for your equipment and supplies tempo-
rary, uninterrupted, operation for your equipment during the utility power failure.

(6) RJ11/45 Phone/Network Surge Suppression

The RJ45/11 provides protection against the telephone and data line corruption. Plug either a 10 Base-T network cable or single tele-
phone line into UPS's «IN» jack. Plug the telephone line or the network cable from your equipment into UPS's «OUT» jack.

NOTE: 

This connection is not required to operate the UPS. 

(7) EPO Port

Emergency Power off (EPO) port enables user to turn off UPS immediately via a remote cable. This will allow connected loads to imme-
diately be de-energized from remote location, with out switching to battery operation. 

(8) USB/RS-232 Port

This port can connect a USB or RS-232 cable to the computer. Using the software «Power Saving Plus II» to automatically saves files
and safely shuts down the computer if the utility power fails.

NOTE: 

This connection is optional and not needed to use the UPS. The UPS works properly without a connection.

(9) SNMP Slot (Ready), SNMP card (Optional)

Built-in expansion slot for a SNMP CARD for network management/monitor.

NOTE: 

The SNMP Card is optional. The UPS can operate properly without a SNMP Card.

17

Summary of Contents for Smart RM 2000

Page 1: ...smart RM 2000 3000 2U SVEN POWER Smart RM 2000 3000 2U...

Page 2: ...SVEN SVEN Company Ltd 2006 http www sven ru 2...

Page 3: ...SMART RM 2000 3000 2U 1 4 2 4 3 4 4 Smart 4 5 4 5 1 5 5 2 5 5 3 5 5 4 5 5 5 6 5 6 6 5 7 6 5 8 6 6 7 7 9 8 10 3...

Page 4: ...1 Smart Smart 19 2U Smart 2 3 1 1 2 1 3 2 4 RJ 45 USB 1 5 RJ 45 RS 232 1 6 7 1 8 1 9 1 10 2 http www sven ru 4 SMART VR 50 60 RJ 45 USB EPO SNMP 4...

Page 5: ...SMART RM 2000 3000 2U 5 5 1 5 2 5 3 8 5 4 0 7 0 8 0 7 0 8 5 1 2 3 4 1 2 3 4 1 2 3 4...

Page 6: ...5 5 1 10 2 4 10 5 6 Smart RM 2000 1400 Smart RM 3000 2100 5 7 10 Base T IN OUT 5 8 8 15 30 6 30 45 3 6 110 3 125 4 30 135 110 10 120...

Page 7: ...SMART RM 2000 3000 2U 6 I 5 4 10 II III 7...

Page 8: ...IV 10 V VI 1 1 4 6 2 3 VII 25 1 IEC 320 2 3 4 5 IEC 320 6 RJ 45 RJ 11 10 Base T 7 EPO Emergency Power Off EPO Smart 8 RJ 45 USB USB 9 SNMP Card SNMP 8...

Page 9: ...SMART RM 2000 3000 2U 7 9 1 2 3 1 2 3 1 2 1 2 1 2 3 1 2 3 1 2 1 8 2 3 10...

Page 10: ...8 10 2000 3000 2000 1400 3000 2100 220 50 60 154 261 200 236 3 5 3 5 3 6 RISC 100 10 1120 12 7 4 12 7 6 8 85 10 90 USB SNMP 6 IEC 320 15 25o 20 90 633 x 435 x 88 30 15 37 14...

Page 11: ...SMART RM 2000 3000 2U UPS APH AVR 1 2 SVEN 1 2 3 4 25 50 75 100 158 204 5 204 233 5 233 300 5 0 II III IV V X X X X X X X X AVR X X X 4 a 10 X X X X X X X 1 X X X X X X 3 a 2 110 X X X 4 a 2 125 11...

Page 12: ...t RM 2000 3000 2U UPS vertical horizontal placement assembling into wallmount Please read this operation manual before using the unit and retain this operation manual in safe place for future referenc...

Page 13: ...xpressly approved by the party responsible for compliance could void the user s authority to operate the equipment UL WARNING STATEMENT See the Safety Instructions and Installation section in page 14...

Page 14: ...stic indication and control RJ45 port for standard USB Plug Play communication interface USB Optional Telephone RJ11 surge protection EPO Emergency Power Off Port Built in expansion slot for a SNMP CA...

Page 15: ...mine the total power needs of the equipment you wish to protect with the UPS The power requirements of your equipment should be less than or equal to the capac ity of the UPS Please refer to the UPS o...

Page 16: ...The UPS will then run a 10 second self test routine This provides a convenient means of testing the UPS s battery Self test feature During a utility power outage the UPS will emit one beep once every...

Page 17: ...least one piece of equipment from the outlet and reset the breaker by pressing the button back into place If the AC input current is greater than the circuit breaker s regulated currency the UPS s rea...

Page 18: ...attery LED is illumi nated and the UPS is not oper ating The UPS is shut down and the battery is discharged from an extended power out age The UPS will return to normal opera tion when the power is re...

Page 19: ...0 sec DC Mode On X X X On X Internal fault On X On X X 1 beeps every 1 sec Low battery On X X X On Constant On Battery fail On X X On X 3 beep every 2 sec Overload 110 On X X On X 4 beep severy 1 sec...