24
7.7.1 Expected Output
PRRLssAAAAAsXT1...T
n
s[DC4]
Data:
P
= DMP protocol identifier
ddddd=RRL replaced by the 5-digit DNIS, therefore
increasing the length by two.
s
= Spaces
AAAA = Account code
X
= DMP serial format identifier
T
1
-T
n
= Alarm information
Examples:
P011ss12345sA00081EASTsSMOKE[DC4]
P011ss12345sA00085555116NORTH OFFICE PRI15S.
WEST BUILDING[DC4]
The above two automation signals are both DMP
serial 1 format. The 15th character in the above exam-
ples will determine if the received format is serial 1 or
serial 3. If the 15th digit is anything but an uppercase
"Z", the DMP format is serial 1. If you look at the signal
below, you will see that the 15th digit is an uppercase
"Z"; therefore, the signal is serial 3 format.
P011ss12345sZa\61\t"BU\z 0232"FRONT DOOR\a
03OFFICE\u0568"JOHN SMITH\[DC4]
NOTE:
The position of the DMP serial format iden-
tifier can change, depending on the line card num-
ber length.
7.8
FBI Super Fast Format
This DTMF format consists of 4-digit account codes,
2-digit zone codes, 1-digit zone type codes, and 1-
digit event codes. The zone codes will be converted
into 3-digit decimal codes by the DRL2E.
The following are the zone type codes used by this
format:
NOTE:
Option [A1] enabled will output the FBI RS-
232 protocol.
Example:
Alarm string - 1234B001
FBI RS-232 Option on
Automation: J0111234B001[14]
FBI RS-232 Option Off
Automation: 1011 1234B001[14]
7.9
ITI Format
The ITI format covers ITI panel models RF Com-
mander, Caretaker Plus, SX-V, SX-IVB, UltraGard 5000
(Pro 5000), Commander III and Commander 2000
Simon. In order to receive the ITI format, the hand-
shake 0E must be programmed. Upon a cold boot,
the fifth handshake (option [86]) is programmed as 0E
hex.
7.9.1 RF Commander/Commander III:
Sensor# Printed out as
00-16
ALARM
80
ALARM
81
ALARM
82
ALARM
83
PHONE TEST
84
OPEN USER X
85
CLOSE USER X
86
SILENT DURESS
87
FORCE ARMED
90
AC FAILURE
91
LOW CPU BAT
92
ALM TAMPR LOOP
93
AUTO PHONE TEST
94
TROUBLE
95
CPU BACK IN
7.9.2 Caretaker Plus
77
ALARM TAMPER
78
TROUBLE
79
NO ACTIVI ALM
80
ALARM
81
ALARM
82
ALARM
83
PHONE TEST
84
OPEN USER X
85
CLOSE USER X
86
ALARM SILENT DURESS
87
FORCE ARMED
88
TROUBLE
92
ALARM TAMPER LOOP
93
AUTO PHONE TEST
7.9.3 SX-V
Sensor# Printed out as
01
BAD SENSOR #
02-76
ALARM
77
TAMPER KEYPAD
80
ALARM
81
ALARM
82
ALARM
83
PHONE TEST
84
OPEN USER
85
CLOSE USER
86
SILENT DURESS
87
FORCE ARM
90
AC FAILURE
91
LOW CPU BAT
92
ALM TAMPR LOOP
93
AUTO PHONE TEST
94
RECEIVER TROUBLE
95
CPU BACK IN
FBI Event
Code
ConvertedEvent Code
Fire
1
A
Panic
2
A
Burglary
3
A
MedicaL
4
A
Auxiliary
5
A
Bypass
6
B
Inactive
7
A
Eight
8
A
Nine
9
A
Zero
0
A
Opening
B
O
Closing
C
C
Abort
D
T
Restore
E
R
Trouble
F
T
Summary of Contents for MLR2E