background image

 

4- OPERATION 

4.1-  START-UP 

Before starting up the unit, be sure to check that the following 
items are in compliance: 

1.  The electrical installation and ventilation; 

2.  The  blower  access  door  is  in  place  and  the  blower  rail 

locking screws are well tightened; 

3.  The  blower  speed  adjustments  for  heating  and  air 

conditioning  are  appropriate  and  in  accordance  with  the 
specifications in this manual; 

4.  The  thermostat  of the  room  is  in  heating mode  and  is  set 

higher than the ambient temperature; 

5.  The breakers on front panel are set on 

the “ON” position

To start the unit, turn the main electrical switch on. 

 

4.2-  LEGACY OPERATING SEQUENCE 

The  blower  motor  is  a  true  variable  speed  motor  designed  to 
deliver constant CFM.  Constant CFM is valid for systems with 
total external static pressure between 0.1 and 0.8 inches water 
column. 

4.2.1-  Continuous fan 

 

Thermostat closes circuit R to G. 

 

Blower runs at continuous fan airflow. 

4.2.2-  Cooling mode 

 single stage 

 

If  indoor  temperature  is  above  temperature  set  point  and 
humidity  is  below  humidity  set  point,  thermostat  closes 
circuits R to G, R to Y/Y2 and R to O. 

 

NOTE: For single stage systems, do not use the Y1 terminal. 

 

 

Furnace delivers single stage cooling airflow. 

4.2.3-  Cooling mode 

 two stage 

 

First stage (low) cooling: Thermostat closes circuits R to G, 
R to O, and R to Y1. 

 

Furnace delivers low stage cooling airflow. 

 

Second stage (high) cooling: Thermostat closes circuits R 
to G, R to O, R to Y1 and R to Y/Y2. 

 

Furnace delivers high stage cooling airflow. 

4.2.4-  Cooling mode 

 dehumidification 

 

 

If  indoor  temperature  is  above  temperature  set  point  and 
humidity  is  above  humidity  set  point,  thermostat  closes 
circuits R to G, R to Y/Y2 and R to O and humidistat opens 
circuit R to DH. 

 

The furnace delivers airflow which is approximately 80% of 
the nominal cooling airflow to increase the latent capacity of 
the system. 

4.2.5-  Electrical heating mode 

 modulating thermostat 

The thermostat sends a heating demand in the form of a pulse 
width  modulated  wave  that  varies  between  5  and  100%.  The 
heating unit will apply this power ratio to the maximum available 
power.  The  electrical  elements  will  modulate  to  the  required 

power and the fan will adjust itself automatically in order to reach 
the required temperature rise. 

4.2.6-  Heat pump heating mode 

 modulating thermostat, 

outdoor unit single stage 

 

Thermostat closes circuits R to G and R to Y/Y2. 
 

NOTE: For single stage systems, do not use the Y1 terminal. 

 

 

Furnace delivers single stage heat pump heating airflow. 

4.2.7-  Heat pump heating mode 

 modulating thermostat, 

outdoor unit two stage 

a.  First stage (low) heating: Thermostat closes circuits R 

to G and R to Y1. 

b.  Furnace delivers low stage heating airflow. 

c. 

Second  stage  (high)  heating: Thermostat  closes  R to 
G, R to Y1 and R to Y/Y2. 

d.  Furnace delivers high stage heating airflow. 

 

WARNING 

 

E

LECTRICAL SHOCK OR UNIT DAMAGE HAZARD

 

 

Failure  to  carefully  read  and  follow  this  WARNING  could 
result  in  equipment  malfunction,  property  damage, 
personal injury and/or death. 

 

Disconnect  power  to  unit  before  removing  or  replacing 
connectors or servicing motor.  Wait at least five (5) minutes 
after disconnecting power before handling. 

4.3-  AIRFLOW VERIFICATION 

Verify the airflow by taking readings of the following points, while 
the elements are in heating mode: 

a.  Total amperage of all the heating elements; 

b.  Voltage at the furnace; 

c. 

Supply air temperature.  The point of the reading must not 
be affected by radiant heat from the elements; 

d.  Return air temperature. 

 

From  these  readings,  one  can  arrive  at  an  approximate 
calculation  of  the  average  airflow.    To  do  that,  the  following 
formula should be used: 
 
 

 

0.82 x amps. x volts 

Liter/s=  ------------------------- 
 

 

Diff. temperature ˚C

 

 
 

 

3.1 x amps. x volts 

CFM =  ------------------------ 
 

 

Diff. 

temperature ˚F

 

4.3.1-  Supply air temperature rise test 

1.  Operate the unit at maximum power for at least 10 minutes; 

2.  Measure the air temperature in the return air plenum; 

3.  Measure the air temperature in the largest trunk coming off 

the supply air plenum, just outside the range of radiant heat 

from the heat exchanger.  0.3 m (12”) from the plenum of 

the main take-off is usually sufficient; 

4.  Calculate the temperature rise by subtracting the return air 

temperature from the supply air temperature. 

Summary of Contents for SUPXX-M240V12

Page 1: ...echnician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KE...

Page 2: ...7 3 2 3 DELAYS Menu 7 3 2 4 SYSTEM Menu 7 3 2 5 AUTO BACKUP Menu 7 4 OPERATION 9 4 1 START UP 9 4 2 OPERATING SEQUENCE 9 4 2 1 Continuous fan 9 4 2 2 Cooling mode single stage 9 4 2 3 Cooling mode two...

Page 3: ...plain to you the following items i The main disconnect switch or circuit breaker ii The air filter and how to change it check monthly and clean or replace if necessary f Before calling for service be...

Page 4: ...he supply duct shall be installed on the top of the unit Care should be taken not to damage the wires inside while cutting the opening Install the filter rack that is supplied with the unit It is also...

Page 5: ...lower Move all wires from the two pole terminal to the three pole terminal following the corresponding colors as shown in Figure 4 The breaker and the supply conductors must be sized by adding the amp...

Page 6: ...quired that prevents the operation of the electric elements and the heat pump at the same time Refer to the instructions provided with the thermostat or the Fossil Fuel kit for the proper wiring of th...

Page 7: ...CIENT CFM TON This parameter allows to modify the CFM per TON with more precision DEHUM ON STATE This parameter defines if the dehumidification will be active high or active low DEHUM RATIO This param...

Page 8: ...DELTA T BACK COOLING HP DEHUM RATIO AC Y1 RATIO BACK SYSTEM RATIO MAX PWR FURNACE MODEL RESET SYSTEM BACK COOLING HP AC HP TONS AC COMFORT EFF CFM TON DEHUM ON STATE INSTALLER AUTO BACKUP BACK TROUBLE...

Page 9: ...varies between 5 and 100 The heating unit will apply this power ratio to the maximum available power The electrical elements will modulate to the required power and the fan will adjust itself automati...

Page 10: ...the obstruction and the elements should restart after a few minutes 5 MAINTENANCE WARNING ELECTRICAL SHOCK HAZARD Turn OFF power to the furnace before any disassembly or servicing Failure to do so ca...

Page 11: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 12: ...2 7 2 3 2 7 2 3 2 7 2 3 2 7 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 8...

Page 13: ...13 Figure 10 Furnace dimensions...

Page 14: ...14 Figure 11 Electrical diagram Modulating ECM SUPREME...

Page 15: ...15 Figure 12 Exploded view Modulating SUPREME...

Page 16: ...30kw 1hp ECM 30 B03811 27 Motor ass y ECM 1 2 hp prog Supreme 10 25kw 1 2hp ECM 31 B03813 18 Motor ass y ECM 1 hp prog Supreme 20 30kw 1hp ECM 32 B04415 Electronic blower kit Supreme 10 33 B04414 Elec...

Reviews: