TABLE 3
Electric furnace FEM, ECM ½ HP motor, air flow tables
15
AC / HP SIZE
Adjustment
BLUE wire position
A/C size
(TONS)
CFM
▼
AC/HP CFM ADJUST
BLACK wire position = (NOM)
CFM
▼
AC/HP CFM ADJUST
BLACK wire position = (LO)
CFM
▼
AC/HP CFM ADJUST
BLACK wire position = (HI)
36
3,0
1200
1080
1320
30
2,5
1000
900
1100
24
2,0
800
720
880
18
1,5
600
540
660
COOLING OR HEAT PUMP HEATING MODE (WITH HP-EFF SELECTED
▲
)
24 VAC (R) input on G, Y/Y2 and O (for cooling)
▼
In Cooling - Dehumidification mode (with Jumper
J1
remove), with no 24 VAC input to DH, the CFMs are reduced by 15%.
▼
The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 only (Y/Y2 not powered)
▲
SYSTEM TYPE select to HP-EFF corresponds to 400 CFM/TONS - HP-COMFORT corresponds to 350 CFM/TONS
AC / HP SIZE
Selection
BLUE wire position
A/C size
(TONS)
CFM
∆
CONTINUOUS FAN
YELLOW wire position = (LO)
CFM
∆
CONTINUOUS FAN
YELLOW wire position = (MED)
CFM
∆
CONTINUOUS FAN
YELLOW wire position = (HI)
36
3,0
600
960
1200
30
2,5
500
800
1000
24
2,0
400
640
800
18
1,5
300
480
600
CONTINUOUS FAN
24 VAC (R) input on G only
∆
CFM's when AC/HP CFM ADJUST at NOM position. CFM's 10% lower or higher if AC/HP CFM ADJUST at LO or HI position.
HEAT KW/CFM
adjustment
RED wire position
POWER
(Kw)
CFM
First stage
24 VAC on W1*
CFM
Second stage
24 VAC on W1 and/or W2*
20
20
500
1000
18
18
450
900
15
15
400
800
ELECTRIC HEATING MODE
24 VAC (R) input on W1 and/or W2 only
* Remove the Jumper
J2
when a 2 stages thermostat is used
ON / OFF DELAY
Adjustment
WHITE wire position
ON-Delay
Time
OFF-Delay
% CFM - Time
0 / 90
0 sec.
100% - 90 sec.
30 / 90
30 sec.
100% - 90 sec.
0 / 0
0 sec.
0 sec.
ENH
30 sec.
70 % - 150 sec.
ON & OFF DELAY FOR COOLING AND HEAT PUMP HEATING MODE
No adjustment
required
ON-Delay
Time
OFF-Delay
% CFM - Time
-
0 sec.
50% - 60 sec.
DELAY PROFILE FOR ELECTRIC HEATING MODE
Summary of Contents for FEM15-E230V1M-A
Page 12: ...12 FIGURE 9 Diagramme électrique ...
Page 17: ...17 COMPOSANTES ET PIÈCES DE REMPLACEMENT ...
Page 18: ...18 LISTE DE PIÈCES Vue explosée B50081 Rev B ...
Page 31: ...12 FIGURE 9 Electrical Diagram ...
Page 36: ...17 COMPONENTS AND REPLACEMENT PARTS ...