6. The chimney must extend at least three (3) feet (915 mm) above its 

point of contact with the roof and at least two (2) feet (610 mm) higher 
than any wall, roof or building within ten (10) feet (3m) of it 

(

Figure 

27

)

7. If the chimney extends higher than five (5) feet (1,500 mm) above 

its point of contact with the roof, it must be secured using a roof 
brace.

8. A rain cap must be installed on top of the chimney. Failure to install 

a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the 

chimney will go through to provide a 2” (50 mm) clearance between 
the chimney and any combustible materials.  Do not fill this 2” space 
with insulation or any other combustible material.

10. Portions of the chimney which may extend through accessible spaces 

must be enclosed to avoid contact with combustible materials or 
damage to the chimney.

11.When offsets are used, the pipe may not penetrate a ceiling or floor 

unless it is running vertical (no 30° offsets).

THE CHIMNEY SYSTEM

Chimney Installation Notes

1.  Always install an interior chimney as it will provide better performance.  

In areas with continuous temperatures below 0° F (- 18° C), the use of 
an exterior chimney increases the likelihood of operating problems such 
as low draft, high rate of creosoting, and poor start-up characteristics.  
Exterior chimneys are also prone to down drafting and flow reversal.  
Installations, which are located on lower floors in the house, such as 
in a basement, in combination with outside chimney, are especially 
prone to flow reversal. If interior installation is impossible, install an 
AC chimney enclosed in an insulated chase.

2.  The fireplace model WRT4820WS may be installed only with Security 

Chimneys International Ltd 6” diameter chimney systems.

3. A chimney venting a fireplace shall not vent any other appliance.

4.  The minimum chimney height is 12 feet (3.7 m). In altitude, add 18” 

(450 mm) to the chimney for every 2,000 feet (600 m) above sea 
level.

5. 

All chimney installations must include at least one support.

  The 

maximum length of chimney that can be supported by the fireplace 
is 26 feet (8 m).  

NOTE:

 2" clearance to combustibles around chimney components required.

NOTE:

 Blown or fill type insulation materials must not be in contact with 

the fireplace or in the enclosure frame as described in ‘’Enclosure’’ section.

NOTE:

 Local codes may not require firestopping at the ceiling levels for 

outside chase installations. However, it is recommended for safety and 

the reduction of heat loss.

Figure 27

two (2) feet Min.

three (3) feet Min.

ten (10) feet

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17

Summary of Contents for WRT4820WS

Page 1: ...Hot Do not touch The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appli ance Severe burns may result Carefully supervise ch...

Page 2: ...place unat tended while it is burning WARNING Always ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the ma...

Page 3: ...tion consult the local authorities to obtain your buildingpermitandcheckyourlocalbuilding codes Installthefireplaceonlyasdescribed in these instructions and using only IHP components This fireplace ha...

Page 4: ...these materials may overheat the fireplace causing damage to the unit a fire or even possibly ignit ing a chimney fire if the chimney is creosoted Burningunapprovedfuel resultinginexcessive pollutants...

Page 5: ...void smoking problems SMOKING CAUSES AND TROUBLESHOOTING Toreducethelikelihoodofsmokingwhenopen ing the door set the combustion air controls to the left before opening the door Your fireplace hasbeend...

Page 6: ...or to Cleaning The Chimney Before starting to clean your chimney we recommend that you remove the top baffle to avoid creosote dust collection at the top of the baffle Follow these steps to set the to...

Page 7: ...oor may need to be adjusted to be com pletelyairtight Thegaskets air tightnesscanbe adjustedusingtheadjustmentscrewlocatedon the right side of the fireplace facade An Allen key 1 8 not supplied will b...

Page 8: ...pport is needed The WRT4820WS fireplace may be installed directly on the floor or on a raised base for proper guidelines refer to Hearth Extension Requirements and a minimum of 6 8 2 m measured from t...

Page 9: ...he clean face kit to allow hot air flow that wouldnormallycomeoutofthetoplouver ANY OTHER INSTALLATION MAY RESULT IN THE FIREPLACE OVERHEATING AND POTENTIALLY CAUSE A FIRE See Gravity Kit section on P...

Page 10: ...lace must be covered with a non combustible material tile marble stone etc See Figures 9 and 10 Cold climate INSTALLATIONS Climates where temperatures will fall below 32 F 0 C The heating performance...

Page 11: ...hoto graphs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesare subjecttochangeordiscontinuance without notice All framing dimensi...

Page 12: ...4 m Level Outside Base Insulation Thermal Barrier Solid Continuous Surface NOTE It is recommended that the chase walls and floor be insulated in the same manner using the same insulation as the rest...

Page 13: ...an not overlay on the fireplace front black steel faceofthefireplace seeFigures16and17 Non combustible materials such as brick stone or ceramic tile can project in front of and onto the fireplace faci...

Page 14: ...tem forward of the WRT4820WS fireplace not flush it will be necessary to purchase two adjustable lengths H8951 When installing the double outlet system the hotairoutletscanbeinstalledinthesameroom as...

Page 15: ...henusing the double hot air outlet kit and blocking the upper louver of the fireplace CENTRAL FORCED AIR KIT NOT TESTED UNDER EPA CERTIFICATION The knock outs provided on the back and on the sides of...

Page 16: ...must not draw air from the attic from the basement or garage D The air intake should be installed where it is not likely to be blocked by snow or exposed to extreme wind and away from automobile exha...

Page 17: ...creasesthelikelihoodofoperatingproblemssuch as low draft high rate of creosoting and poor start up characteristics Exterior chimneys are also prone to down drafting and flow reversal Installations whi...

Page 18: ...ween the roof and the flashing with roofing pitch see Figures 30 and 31 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof usi...

Page 19: ...line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install a fires...

Page 20: ...13 16 122 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95...

Page 21: ...1 8 x 30 3 4 45 283 mm x 518 mm 11 1 8 x 20 3 8 S 2100 HT6000 AC 6 dia 30 327 mm x 881 mm 12 7 8 x 34 11 16 30 380 mm x 972 mm 15 x 38 1 4 Table 5 Figure 36 Drywall Insulated Wall Insulated Wall Radia...

Page 22: ...th the support CHIMNEY MODEL MAXIMUM HEIGHT OF SUPPORTED CHIMNEY OFFSET SUPPORT ROOF SUPPORT ASHT HT6103 6 dia 28 feet 8 54 m 29 feet 8 84 m S 2100 HT6000 6 dia 18 feet 5 49 m 20 feet 6 1 m AC 6 dia 4...

Page 23: ...ix it in place using the 3 metal screws supplied Figure 39 FIREPLACE 1 Clearance Insulated Elbow ASHT or HT6103 3 Screws Insulation Pad Cover High Temp Cement Firestop Tubinox or Projet SS Stainless S...

Page 24: ...o 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1 H8953 Wall radiation shield 8 I D 7B26ZR H8952 Optional installation accessories uNot...

Page 25: ...n 2 PR SR3026 Blower 250 CFM for central forced air kit BISZY BISZY Blower variable speed control with decora tive wall plate for BISZY VRUW VRUW Thermo disk on off blower control for BISZY VTU VTU Bl...

Page 26: ...REPLACEMENT PARTS WRT4820WS 1 8 15 16 17 20 10 14 12 11 13 20 22 23 24 21 25 26 30 19 2 3 4 5 6 7 PA I N T 18 28 29 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 26...

Page 27: ...ll Radiation Shield 30 6RSMI30 6RSMI30 Uninsulated Wall Radiation Shield 30 6RSM30 6RSM30 Attic Radiation Shield H0487 Roof Flashings Flat Roof Flashing 6FR 6FR 1 12 7 12 5 30 6FAR 6FAR 8 12 12 12 30...

Page 28: ...No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Length 6 Dia 6LL36 6LL36 48 Length 6 Dia 6LL48 6LL48 Adjustable Length 7 to 11 6 Dia 6L7A 6L7A Split Base Tee 6...

Page 29: ...normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burnin...

Page 30: ...See Page 25 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at p...

Reviews: