Superior WRT4820WS Installation And Operation Instructions Manual Download Page 15

The duct system must be installed respecting 

the following:

1. Remove the plates closing up the 8” dia. 

holes on top of the fireplace.  Then, cut 

the insulation and remove the plate under 

the insulation in order to obtain two 8” dia. 

openings.  Fix the adaptors on the fireplace 

openings by turning clockwise (

Figure 20

)

.

2. Maintain at least a 2” (50 mm) clearance 

between the ducts and any combustible 

material; the required hole size is 13”  x  13” 

(330 mm x 330 mm).

  Exception #1:  For the grills, the fram-

ing can be 10-3/4” x 10-3/4” (275 mm 

x 275 mm) to provide the clearance as 

required by the integral spacers on the 

double outlet duct system.

3. The maximum number of elbows in a run 

of duct is two.

4.  Maintain at least 6-1/2” (160 mm) clearance 

from the outlet grill framing to a combustible 

ceiling, side wall or mantel.

5.  When traversing a combustible wall or floor, 

a firestop must be installed at the wall or 

floor penetration.  The hole size must be 

13” X 13” (330 mm x 330 mm).

6.  Do not connect the hot air ducts to a central 

heating system.  Malfunction of the heating 

system’s blower will cause the fireplace to 

overheat.  A furnace duct is only single wall 

and not double wall as is required for the 

WRT4820WS fireplace hot air exhaust.  

7. Use only IHP grills and components as 

described in this manual. Other grills or 

registers, for example, may be too restrictive 

and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they 

will overheat.

9. Do not use tees or any other components 

than the ones specifically listed here.

10. Never allow the ducting to pitch down as 

hot air will be trapped creating a fire hazard.  

Never route the ducting downwards

.

11. The hot air outlet grills must be installed with 

the louvers pointing downwards in order to 

prevent overheating adjacent ceilings.

12. Always install the two outlet grills when using 

the double hot air outlet kit and blocking the 

upper louver of the fireplace.

CENTRAL FORCED AIR KIT (NOT TESTED 
UNDER EPA CERTIFICATION)

The knock-outs provided on the back and on 

the sides of the WRT4820WS fireplace allow 

the connection of insulated flexible pipe which 

enables you to heat adjacent rooms up to 50 

feet from the fireplace.

The ducting system must be installed as de-

scribed below:

A) Remove the knock-out and cut the insulation. 

In the back, there may be another knock-out 

to remove under the insulation.

B) Fix the adaptor at the back and/or the side 

of the fireplace by twist-locking the adaptor 

to the fireplace. You can use more than one 

outlet on the fireplace 

(

Figure 23

)

.

C) Attach the 5” flexible pipe, using the collars 

provided. Important: Make sure that the 

plastic wrapping around the flexible pipe 

will not be in contact with the fireplace using 

aluminum tape.

D)  Route the flexible pipe to the chosen location. 

The ducting system can be installed either 

in an upper room or in a lower room.

E) Attach the flexible pipe to the fan, using the 

collars 

(

Figure 24

)

.

F)  Fix the back draft damper to the fan outlet.

G)  Attach a flexible pipe to the fan / flexible pipe 

adaptor (square to round) and stretch it up 

to the location where the heat is required.

H) At that point, the flexible pipe can be attached 

to any air distribution grill. 

I) Install the blower heating and cooling ther-

mostat (HCTW) in that part of the house to 

be heated by the hot air duct. The thermostat 

can be switched to a cooling thermostat and 

installed in the same room as the unit. This 

thermostat will turn on the blower when 

the room where the fireplace is located 

becomes too hot.

This option requires electricity. Make sure that 

the connections to the fan have been made 

according to the local codes and comply with 

their requirements (see instruction provided 

with the thermostat).

Figure 23

Figure 24

Adaptor

Insulation

Blower

Tightening Collar

Aluminium Tape

Flex 5” Diameter

Insulated

Flexible

pipe

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Summary of Contents for WRT4820WS

Page 1: ...Hot Do not touch The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appli ance Severe burns may result Carefully supervise ch...

Page 2: ...place unat tended while it is burning WARNING Always ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the ma...

Page 3: ...tion consult the local authorities to obtain your buildingpermitandcheckyourlocalbuilding codes Installthefireplaceonlyasdescribed in these instructions and using only IHP components This fireplace ha...

Page 4: ...these materials may overheat the fireplace causing damage to the unit a fire or even possibly ignit ing a chimney fire if the chimney is creosoted Burningunapprovedfuel resultinginexcessive pollutants...

Page 5: ...void smoking problems SMOKING CAUSES AND TROUBLESHOOTING Toreducethelikelihoodofsmokingwhenopen ing the door set the combustion air controls to the left before opening the door Your fireplace hasbeend...

Page 6: ...or to Cleaning The Chimney Before starting to clean your chimney we recommend that you remove the top baffle to avoid creosote dust collection at the top of the baffle Follow these steps to set the to...

Page 7: ...oor may need to be adjusted to be com pletelyairtight Thegaskets air tightnesscanbe adjustedusingtheadjustmentscrewlocatedon the right side of the fireplace facade An Allen key 1 8 not supplied will b...

Page 8: ...pport is needed The WRT4820WS fireplace may be installed directly on the floor or on a raised base for proper guidelines refer to Hearth Extension Requirements and a minimum of 6 8 2 m measured from t...

Page 9: ...he clean face kit to allow hot air flow that wouldnormallycomeoutofthetoplouver ANY OTHER INSTALLATION MAY RESULT IN THE FIREPLACE OVERHEATING AND POTENTIALLY CAUSE A FIRE See Gravity Kit section on P...

Page 10: ...lace must be covered with a non combustible material tile marble stone etc See Figures 9 and 10 Cold climate INSTALLATIONS Climates where temperatures will fall below 32 F 0 C The heating performance...

Page 11: ...hoto graphs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesare subjecttochangeordiscontinuance without notice All framing dimensi...

Page 12: ...4 m Level Outside Base Insulation Thermal Barrier Solid Continuous Surface NOTE It is recommended that the chase walls and floor be insulated in the same manner using the same insulation as the rest...

Page 13: ...an not overlay on the fireplace front black steel faceofthefireplace seeFigures16and17 Non combustible materials such as brick stone or ceramic tile can project in front of and onto the fireplace faci...

Page 14: ...tem forward of the WRT4820WS fireplace not flush it will be necessary to purchase two adjustable lengths H8951 When installing the double outlet system the hotairoutletscanbeinstalledinthesameroom as...

Page 15: ...henusing the double hot air outlet kit and blocking the upper louver of the fireplace CENTRAL FORCED AIR KIT NOT TESTED UNDER EPA CERTIFICATION The knock outs provided on the back and on the sides of...

Page 16: ...must not draw air from the attic from the basement or garage D The air intake should be installed where it is not likely to be blocked by snow or exposed to extreme wind and away from automobile exha...

Page 17: ...creasesthelikelihoodofoperatingproblemssuch as low draft high rate of creosoting and poor start up characteristics Exterior chimneys are also prone to down drafting and flow reversal Installations whi...

Page 18: ...ween the roof and the flashing with roofing pitch see Figures 30 and 31 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof usi...

Page 19: ...line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install a fires...

Page 20: ...13 16 122 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95...

Page 21: ...1 8 x 30 3 4 45 283 mm x 518 mm 11 1 8 x 20 3 8 S 2100 HT6000 AC 6 dia 30 327 mm x 881 mm 12 7 8 x 34 11 16 30 380 mm x 972 mm 15 x 38 1 4 Table 5 Figure 36 Drywall Insulated Wall Insulated Wall Radia...

Page 22: ...th the support CHIMNEY MODEL MAXIMUM HEIGHT OF SUPPORTED CHIMNEY OFFSET SUPPORT ROOF SUPPORT ASHT HT6103 6 dia 28 feet 8 54 m 29 feet 8 84 m S 2100 HT6000 6 dia 18 feet 5 49 m 20 feet 6 1 m AC 6 dia 4...

Page 23: ...ix it in place using the 3 metal screws supplied Figure 39 FIREPLACE 1 Clearance Insulated Elbow ASHT or HT6103 3 Screws Insulation Pad Cover High Temp Cement Firestop Tubinox or Projet SS Stainless S...

Page 24: ...o 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1 H8953 Wall radiation shield 8 I D 7B26ZR H8952 Optional installation accessories uNot...

Page 25: ...n 2 PR SR3026 Blower 250 CFM for central forced air kit BISZY BISZY Blower variable speed control with decora tive wall plate for BISZY VRUW VRUW Thermo disk on off blower control for BISZY VTU VTU Bl...

Page 26: ...REPLACEMENT PARTS WRT4820WS 1 8 15 16 17 20 10 14 12 11 13 20 22 23 24 21 25 26 30 19 2 3 4 5 6 7 PA I N T 18 28 29 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 26...

Page 27: ...ll Radiation Shield 30 6RSMI30 6RSMI30 Uninsulated Wall Radiation Shield 30 6RSM30 6RSM30 Attic Radiation Shield H0487 Roof Flashings Flat Roof Flashing 6FR 6FR 1 12 7 12 5 30 6FAR 6FAR 8 12 12 12 30...

Page 28: ...No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Length 6 Dia 6LL36 6LL36 48 Length 6 Dia 6LL48 6LL48 Adjustable Length 7 to 11 6 Dia 6L7A 6L7A Split Base Tee 6...

Page 29: ...normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burnin...

Page 30: ...See Page 25 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at p...

Reviews: