VENTING INSTALLATION
Continued
CHASE INSTALLATIONS
Instructions for chase installations are included with chase style ter-
mination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. We suggest that terminations be
separated at least 24", center to center and stacked at a vertical height
differenceof18"(seeFigure16).
Note:
If a decorative shroud is to be installed, contact manufacturer
for specifications.
24" Min.
24" Min.
18"
Min.
Figure 16 - Multiple Chase Installation
10'
2' Min.
10'
3' Min.
2' Min.
3' Min.
Level of
Flue Gas
Outlet
Figure 17 - 10 Foot Rule
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above highest point where it passes through roof and
must be at least 2 feet above highest point of the roof that is within
ahorizontaldistanceof10feet(seeFigure17).
FINISHING FIREPLACE
Combustiblematerials,suchaswallboard,sheetrock,drywall,ply
-
wood, etc., may make direct contact with sides and top around fire-
place face. It is important that combustible materials do not overlap
face itself. Brick, glass, tile or other noncombustible materials may
overlap front face provided they do not obstruct essential openings
such as louvered slots. When overlapping with a noncombustible
facing material, use only noncombustible mortar or adhesive.
Storm Collar Installation (SC1)
Place storm collar over pipe and slide down until it is snug against
openedgeoflashing(seeFigure14).UseSC1forallroundtermina
-
tions. Apply waterproof caulk around perimeter of collar to provide
a proper seal.
Figure 14 - Storm Collar
Chimney
Pipe
Waterproof
Caulk
Storm
Collar
Flashing
Terminations/Spark Arrestor
Fireplace system must be terminated with listed round top or chase
terminations. In any case, refer to installation instructions supplied
with termination. Terminations approved for this fireplace are RT-
8DMandRLT-8DMthatcanbeusedforlashingorchaseandET-
8DM,ETO-8DM,ETL-8DMandETLO-8DMforchasestyletermination
only. Figure 18 shows an RLT-8DM round top termination.
CAUTION: Do not seal openings on the rooftop
lashing.Followtheinstallationinstructionsprovided
with the termination being used.
Terminations with 16" slip pipe sections are available. RTT-8DM,
RTTL-8DM and RLTT-8DM are approved for flashing installations.
When needed, these adjustable terminations may be used in combi-
nation with pipe assembly to achieve correct chimney height.
Note:
In the rare instance there is a problem with side driven rain or
windorchimneyisnotdraftingproperly,anADS-8DM(Anti-Draft
Shield)canbeusedwithroundterminations.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
RLT-8DM
Level of Flue
Gas Outlet
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
Figure 15 - Termination
Overlap
Shingles Top
and Sides
Flue Pipe
of RLT-8DM
Inside Inner
Pipe of
Chimney