10 FOOT RULE
All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above the
highest point where it passes through the roof
and must be at least 2 feet above the high
-
est point of the roof that is within a horizontal
distance of 10 feet (see Figure 17).
Figure 17 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc. may make direct contact with sides and top
around the fireplace face. It is important that
combustible materials do not overlap the face
itself. Brick, glass, tile or other noncombustible
materials may overlap the front face provided
they do not obstruct essential openings like
louvered slots or any other opening. When
overlapping with a noncombustible facing
material, use only noncombustible mortar or
adhesive.
VENTING INSTALLATION
Continued
30E-8DM
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
MINIMUM
HEIGHT
14.5 FT.
MINIMUM
UP TO
6FT. MAX.
UP TO
6FT. MAX.
HEIGHT
14.5 FT.
MIN. HEIGHT
OF 22 FT. (WITH
2 ELBOW SETS)
MAX. HEIGHT OF
50 FT.
MAX. HEIGHT
50 FT.
(ANY SYSTEM)
30E-8DM
Figure 18 - Typical Residential Installations
10'
2' Min.
10'
3' Min.
2' Min.
3' Min.
Level of
Flue Gas
Outlet