background image

14

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

1.

Spark ignitor will not light
pilot after repeated
triggering of ignitor button.

2.

Pilot will not stay lit after
carefully following the
lighting instructions.

3.

Pilot burning, no gas to
burner, Valve knob “ON,”
Wall Switch “ON.”

4.

Frequent pilot/burner outage
problem.

CORRECTIVE ACTION

SYMPTOM

A.

Defective ignitor
(no spark at electrode).

B.

Defective or misaligned electrode
at pilot (spark at electrode).

C.

Gas supply pressure errant.

D.

Pilot orifice plugged.

A.

Defective pilot generator
(thermogenerator).

A. 

 Damper closed or Damper Switch

defective.

B.

Wall switch or wires defective.

C.

Thermopile may not be generating
sufficient millivoltage.

D.

Plugged burner orifice.

A.

Pilot flame may be too low or
blowing (high) causing the pilot/
valve safety to drop out.

Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor.

Using a match, light pilot. If pilot lights, turn off pilot and
trigger the ignitor button again. If pilot lights, an improper
gas mixture caused the bad lighting and a longer purge
period is recommended. If pilot will not light – check gap at
electrode and pilot - should be 

¹⁄₈

" to have a strong spark. If

gap measures 

¹⁄₈

", replace pilot

 (Figure 9 ).

Check inlet gas pressure. It should be within the limits as
marked on the rating plate.

Clean or replace pilot orifice.

Check pilot flame, it must impinge on thermogenerator

(Figure 9 )

. Clean and/or adjust pilot for maximum flame

impingement on thermogenerator. Ensure that the connec-
tion between the valve and thermogenerator are tight and
secure.

Ensure damper control lever is locked in the open position,
all the way to the right.  If the damper control lever is locked
in the open position troubleshoot through Steps B., C. and
D. below.  If the main burner will still not light, determine if
the damper switch is defective and replace if necessary.

Check wall switch and wires for proper connections. Jumper
wire across terminals at wall switch, if burner comes on,
replace defective wall switch. If okay, jumper wires across
wall switch wires at valve, if burner comes on, wires are
faulty or connections are bad.

Check thermopile with millivolt meter. Take reading at ther-
mopile terminals of gas valve. Should read 325 millivolts
minimum with optional wall switch “OFF.” Replace faulty
thermopile if reading is below specified minimum.

Check burner orifice for stoppage and remove.

Clean and/or adjust pilot flame for maximum flame impinge-
ment on thermogenerator 

(Figure 9 )

.

POSSIBLE CAUSES

Note: 

Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in

the “ON” position.

Important:

 Valve system troubleshooting should only be accomplished by a qualified service technician.

Summary of Contents for STANDARD SERIES and

Page 1: ...LO SION MAY RESULT CAUSING PROPERTY DAM AGE PERSONAL INJURY OR LOSS OF LIFE POURVOTRES CURIT Nepasentreposerniutiliser d essencenid autrevapeursouliquidesinflammables dans le voisinage de cet appareil...

Page 2: ...vides safe efficient operation External electri cal power is required to operate these units GENERAL INFORMATION Note Installation and repair should be per formedbyaqualifiedserviceperson Theappli an...

Page 3: ...SURED ENVIRONMENTS PRESSUREWITHINTHEHOMEISLESS THAN PRESSURES OUTSIDE SIGNIFI CANT NEGATIVELY PRESSURED ENVI RONMENTS CAUSED BY WEATHER HOME DESIGN OR OTHER DEVICES MAYIMPACTTHEOPERATIONOFTHESE APPLIA...

Page 4: ...pliance area clear and free from combustible materials gasoline and other flammable liquids Honeywell Electronic Gas Valve WARNING FIREPLACES EQUIPPED WITH OPTIONAL ACCESSORY DOORS SHOULDBEOPERATEDONL...

Page 5: ...ance and call a qualified service technician The control lever snaps into place at either extreme of its range of motion When locked in position all the way to the right the damper is open When locke...

Page 6: ...LECTRICAL POWER BEFORE SERVICING THE APPLIANCE Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer ed...

Page 7: ...on Procedure Inspecting Cleaning Burner Logs and Controls Check Flame Patterns and Flame Height Inspecting Cleaning Pilot and Burner Checking Vent System Appliance Checkout Replacing Rockwool Ember Ma...

Page 8: ...re 12 Spread along the front edge of the front burner Do not use more than is necessary When properly positioned the rockwool will unevenly cover approximately 85 of the gap between the front burner a...

Page 9: ...tch Attachment Only Limit Switch BK WHT BK BK BK SIT Millivolt Wiring Diagram For Wall Switch Attachment Only If any of the original wire as supplied must be replaced it must be replaced with Type AWM...

Page 10: ...s go to the next step 7 Push in gas control knob slightly and turn counterclockwise to PILOT 8 Push in control knob all the way and hold in Immediately light the pilot by triggering the spark ignitor...

Page 11: ...Ne touchez aucun commutateur lectrique Ne vous servez d aucun t l phone dans votre difice Appelezimm diatementvotrecompagniedegazenutilisantlet l phone du voisin S il vous est impossible de contacter...

Page 12: ...use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has...

Page 13: ...aire inspecter l appareil et remplacer toute pi cedusyst meder glageoucommandedugazquia t sous l eau 1 ARR TEZ Lisez les consignes de s curit au verso de cette plaque 2 Tournez l interrupteur mural la...

Page 14: ...essure It should be within the limits as marked on the rating plate Clean or replace pilot orifice Check pilot flame it must impinge on thermogenerator Figure 9 Clean and or adjust pilot for maximum f...

Page 15: ...surements Must Be Taken While The Igniter Is Powered When Measured Voltage At Connections Use Care To Assure Terminals Are Not Damaged Replace Valve Replace Valve 24 Volt Hot End View Of Control Harne...

Page 16: ...he description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions concerning the installation or ap plication of this syst...

Page 17: ...RCL is designed to operate with all millivolt ignition systems as well as electronic ignition systems It may be installed with use for either natural or propane gas appliances The RCL offers ease of...

Page 18: ...4001 1 74L8801 1 11 Bag of Rockwool 88L53 1 88L53 1 12 Limit Switch 62L1601 1 62L1601 1 13 Damper Switch 82L5901 1 82L5901 1 GAS CONTROLS ELECTRONIC Natural Propane No DESCRIPTION Part No Qty Part No...

Page 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE REPLACEMENT PARTS 24 22 20 3 4 5 6 7 2 1 31 30 10 REF 10 21 25 26 23 33 9 8 11 32 c b a d e 13 12 27...

Page 20: ...25 007M REV G 07 2004 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consul...

Reviews: