Superior SSDVPF-CNE-B Installation Instructions Manual Download Page 9

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

9

Figure 10

 

REMOVE

CARDBOARD

BEFORE USING

REMOVE

CARDBOARD

BEFORE USING

Pressure Relief Plates

Remove Cardboard Before 

Using Appliance

DETAILED INSTALLATION STEPS

TYPICAL INSTALLATION SEQUENCE

The typical sequence of installation is outlined 

below.    However,  each  installation  is  unique 

and  may  result  in  variations  to  the  steps 

described. 

See the Page numbers references in the follow-

ing steps for detailed procedures.

Step 1

.   (Page  9)  Construct  the  appliance 

framing. Position the appliance within 

the  framing  and  secure  with  nailing 

flanges.

Step 2

.   (Page  12)  Route  gas  supply  line  to 

appliance location.

Step 3.

   (Page 13) Install the vent system and 

exterior termination.  

Step 4

.   (Page 25)  Field Wiring 

.25

 

a.

 Millivolt Appliances – Install the 

OFF/ON  burner  control  switch  and 

bring  in  electrical  service  line  for 

forced  air-circulating  blower  (op-

tional equipment).

.25

 

b.

 Electronic Appliances  –  Connect 120 

VAC electrical power to the appliance 

receptacle. 

Step 5

.   (Page 26) Install blower kit (optional 

equipment).

Step 6.

   (Page 27) Make connection to gas 

supply.

Step 7

.    (Page 28) Verify appliance operation. 

Step 8.

   (Page 28) Install the logs, decorative 

volcanic stone and glowing embers.

Step 9

.   (Page 30) Install glass door assem-

blies.

Step 10

.  (Page 30) Adjust burner primary air 

shutter  to  achieve  proper  flame  ap-

pearance.

Step 11.

  (Page 31)  Install the decorative trim 

and hoods.

Step 12.

  (Page 32)

 Attach Safety in Operation 

Warnings.

The appliance is shipped with all gas controls 

and components installed and pre-wired. 

1.  Remove the shipping carton.  Remove the 

shipping  pad,  exposing  the  front  glass 

door.

2.  Open  the  two  latches  (located  under  the 

firebox floor) securing the glass door. Re-

move the door by tilting it outward at the 

bottom and lifting it up. Set the door aside 

protecting it from inadvertent damage. See 

Removing Glass Panels on Page 30.

2.

 Remove the top louvered panel and locate 

the pressure relief plates.

3. Lift the pressure relief plates and remove 

the cardboard from beneath each plate (be 

careful not to damage the white gasket). 

See 

Figure 10

.

*   NOTE:  INSTALLATION  DIAGRAMS  AND 

INSTRUCTIONS SHOW THE FRONT OF THE 

APPLIANCE AS THE SIDE WHICH HAS VALVE 

ACCESS, EXCEPT WHERE NOTED.

Step 1. FRAMING

Frame these appliances as illustrated in Figures 

12 and 13 on Pages 10 and 11.  All framing 

details must allow for a minimum clearance to 

combustible  framing  members  as  shown  in 

Table 6 on Page 8.

If the appliance is to be elevated above floor 

level,  a  solid  continuous  platform  must  be 

constructed below the appliance. 

Headers  may  be  in  direct  contact  with  the 

appliance  top  spacers  but  must  not  be  sup-

ported by them or notched to fit around them.  

All construction above the appliance must be 

self-supporting. 

 DO NOT

 use the appliance for 

structural support.

 

Side Nailing Flanges

The  fireplace  should  be  secured  to  the  fram-

ing  at  the  side(s)  of  the  appliance  using  the 

factory-provided  nailing  flanges.  Install  the  8 

nailing flanges as shown in Figure 11 using the 

existing screws. Position the fireplace within 

the framing. When required, the tabs may be 

bent 90 degrees by hand or with the assistance 

of a hammer. Use  wood screws to secure the 

nailing flanges to the framing. See Table 6 on 

Page  8  for  clearances  of  framing  members 

to cabinet parts. The nailing flange itself can 

directly contact framing.

Floor Nailing Tabs - 

Secure the fireplace to the 

floor as shown in  Figure 11. 

Figure 11 - 

Nailing Flanges

Remove these screws and use them 

when installing nailing flanges.

Nailing Flanges

Turn nailing tabs down and secure to floor with 

8d nails or other appropriate fasteners on both 

sides of appliance which do not have viewing 

glass panels.

SSDVST Shown (SSDVPF - No nailing 

flanges on end with glass panel)

       WARNING 

Failure  to  position  the  parts  in 

accordance with these diagrams 

or failure to use only parts specifi-

cally approved with this appliance 

may result in property damage or 

personal injury.

       AVERTISSEMENT 

Risque  de  dommages  ou  de 

blessures  si  les  pièces  ne  sont 

pas  installées  conformément  à 

ces schémas et ou si des pièces 

autres que celles spécifiquement 

approuvées avec cet appareil sont 

utilisées.

Summary of Contents for SSDVPF-CNE-B

Page 1: ...de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par...

Page 2: ...e installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is re...

Page 3: ...y be required due to excessive lint from carpeting bed ding material etcetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Remarque...

Page 4: ...e reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National F...

Page 5: ...rer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the StandardforInstallationinMobileHomes CAN CSA Z240 MH Series in Canada C...

Page 6: ...54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12...

Page 7: ...cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3...

Page 8: ...owing exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the t...

Page 9: ...plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONSSHOWTHEFRONTOFTHE APPLIANCEASTHESIDEWHICHHAS...

Page 10: ...108 679 11 3 8 267 289 7 178 5 1 8 130 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Lou...

Page 11: ...uance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louv...

Page 12: ...torand1 2inchshutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 foradditionalrequirementsfor installations in the state of Massachusetts in the USA The gas supply line sho...

Page 13: ...1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz...

Page 14: ...0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9...

Page 15: ...4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or...

Page 16: ...ections see Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm at...

Page 17: ...ori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a...

Page 18: ...4 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet total...

Page 19: ...geandsealboththe inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner...

Page 20: ...ey are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer SV4 5HT 2 Terminati...

Page 21: ...hes mm Termination Kit Only 6 to 9 1 4 152 to 235 TerminationKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination...

Page 22: ...5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior...

Page 23: ...meters Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio F...

Page 24: ...nner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull a...

Page 25: ...es 43 and 44 b Optional Wall Switch Wall Thermostat OrRemoteControlReceiver Installsnap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures...

Page 26: ...x Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch...

Page 27: ...that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pi...

Page 28: ...al tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installe...

Page 29: ...ers as it is being installed c Asafinalcheckforcorrectlogsetplacement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate...

Page 30: ...ld be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR Only doors certified with the appliance shall be use...

Page 31: ...lly clockwise Propane fully counter clockwise Settings are shown for each burner Air Shutter Adjusting Rod Air Shutter Adjusting Arms Orifice Increase Shutter Opening In This Direction Decrease Shutte...

Page 32: ...ur liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisis...

Page 33: ...flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Co...

Page 34: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 35: ...th the re quirements of the CAN CSA B149 1 Installation code Laconversiondevra treeffectu e conform ment aux recommanda tions des autorit s provinciales ayant juridiction et conform ment aux exigences...

Page 36: ...rimary air opening setting NOTE Each model has two burners and 2 Orifices Pilot Orifice Pilot Assembly Igniter Assembly Retaining Clip Flare Nut Note If the igniter is damaged a replacement kit is ava...

Page 37: ...S NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion...

Page 38: ...38 NOTES...

Page 39: ...39 39 NOTES...

Page 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Reviews: