Superior SSDVPF-CNE-B Installation Instructions Manual Download Page 25

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

25

Figure 43 - 

Millivolt Wiring Diagram

Field Wired

Factory 

Wired

TH

TP

TH

TP

 

 

 

 

* Optional 

Control Switch

Thermopile

Schematic
Representation
Only

•  If any of the original wire as supplied must be 

replaced, it must be replaced with Type AWM 

105 C - 18 gage wire.

*  Optional Kits Installed - ON/OFF  wall switch, unit mounted burner ON/OFF switch, wall thermostat or 

remote control.receiver. 

HT

PT

HT

PT

*

* Twist wires together to operate unit 

solely by manipulating the gas valve 

control knob; or connect wires to 

optional control switch (wall switch, 

remote control or wall thermostat to 

operate unit.

CAUTION:  Label all wires prior to disconnec-

tion when servicing controls. Wiring errors can 

cause improper and dangerous operation. 

ATTENTION:  Au moment de l'entretien des 

commandes, étiquetez tous les fils avant de 

les débrancher.  Des erreurs de cáblage peu-

vent entraîner un fonctionnement inadéquat 

et dangereux.

Verify proper operation after servicing.

S'assurer que l'appareil fonctionne adé-

quatement une fois l'entretien terminé.

       

CAUTION

Ground supply lead must be con-

nected to the wire attached to the 

green ground screw located on the  

outlet box.   See 

Figure 46

. Failure to 

do so will result in a potential  safety 

hazard.    The  appliance  must  be 

electrically grounded in accordance 

with local codes or, in the absence of 

local codes, the National Electrical 

Code, ANSI/NFPA 70-latest edition. 

(In Canada, the current CSA C22-1 

Canadian Electrical Code).

Step 4. FIELD WIRING

Refer to Section A for millivolt appliances and 

Section  B  for  electronic  appliances.  The  gas 

valve is set in place and pre-wired at the factory 

on both models.

A. Millivolt Wiring 

(See Figure 43)

:

 

1. Install and wire in the burner control switch.  

Install either 

"

a" 

or

 "b"

 below, NOT BOTH 

(installing both may result in improper burner 

operation).

a.

 

Optional OFF/ON Switch 

- Install the OFF/

ON burner control switch (rocker switch) 

as shown in Figures 43 and 44

b.

 

Optional Wall Switch, Wall Thermostat 

Or Remote Control Receiver -

 Install snap 

bushing  (provided  in  Electrical  Outlet 

Kit - See Figure 44) into control switch 

knock-out in side panel (see Figures 12 

and 13 on Pages 10 and 11).  Wire the 

optional control switch within the millivolt 

control circuit (as shown in Figure 43) 

using  the  15  feet  of  2  conductor  wire 

supplied (route wires through the snap 

bushing to the optional control switch).  

Mount the optional control switch or wall 

thermostat in a convenient location on a 

wall near the fireplace. 

   

CAUTION: Do not connect optional control 

switch to 120V power supply.

2. Install the junction box and receptacle outlet 

to the left of the valve in the front (for optional 

blower kit).  See junction box and receptacle 

outlet  as  explained  in  steps  1-11  for  (B) 

Electronic Wiring (on this page).

Gas

Valve

Control Compartment 

Access panel

OFF/ON 

Switch

TP TH

TH

Install OFF/ON Switch

(millivolt models)

1. Connect the 2 wires (provided in Electrical 

Outlet Kit) to the TP/TH and TH terminals 

on valve.  

2. Pass the 2 wires through the opening where 

OFF/ON switch will be installed (left of piezo, 

below valve).

3.  Connect  the  two  wires  to  the  OFF/ON 

Switch.

OFF/ON 

Switch

Connect 

wires to 

terminals

4.  Press the OFF/ON switch into bracket as 

shown below (it will snap into place).

               

Figure 44

B.  Electronic  Wiring   

(See  Figures  45  and 

46)

Notes:

   The electronic appliance must be connected 

to the main 120 VAC power supply.

•   The junction box can be installed in any of the 

4 outside corners of the control compartment 

(it can be found factory installed in the right 

front corner viewed from the valve access side  

(where it should be reinstalled if an optional 

blower kit is installed). 

1.

 Route a 3-wire, 120 VAC, 60 Hz, 1 ph power 

supply to the location on appliance where 

junction box is to be installed.

2.

 Open the control compartment access panel 

(see Control Compartment Access Instruc-

tions on Page 27)

3.

 Remove the junction box/outlet receptacle 

assembly by removing the securing screw at 

the front right corner of the unit. See Figure 

45

4.

 Remove  the  outlet  receptacle  from  the 

junction box by removing the two securing 

screws.

Summary of Contents for SSDVPF-CNE-B

Page 1: ...de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par...

Page 2: ...e installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is re...

Page 3: ...y be required due to excessive lint from carpeting bed ding material etcetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Remarque...

Page 4: ...e reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National F...

Page 5: ...rer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the StandardforInstallationinMobileHomes CAN CSA Z240 MH Series in Canada C...

Page 6: ...54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12...

Page 7: ...cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3...

Page 8: ...owing exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the t...

Page 9: ...plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONSSHOWTHEFRONTOFTHE APPLIANCEASTHESIDEWHICHHAS...

Page 10: ...108 679 11 3 8 267 289 7 178 5 1 8 130 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Lou...

Page 11: ...uance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louv...

Page 12: ...torand1 2inchshutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 foradditionalrequirementsfor installations in the state of Massachusetts in the USA The gas supply line sho...

Page 13: ...1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz...

Page 14: ...0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9...

Page 15: ...4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or...

Page 16: ...ections see Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm at...

Page 17: ...ori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a...

Page 18: ...4 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet total...

Page 19: ...geandsealboththe inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner...

Page 20: ...ey are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer SV4 5HT 2 Terminati...

Page 21: ...hes mm Termination Kit Only 6 to 9 1 4 152 to 235 TerminationKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination...

Page 22: ...5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior...

Page 23: ...meters Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio F...

Page 24: ...nner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull a...

Page 25: ...es 43 and 44 b Optional Wall Switch Wall Thermostat OrRemoteControlReceiver Installsnap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures...

Page 26: ...x Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch...

Page 27: ...that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pi...

Page 28: ...al tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installe...

Page 29: ...ers as it is being installed c Asafinalcheckforcorrectlogsetplacement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate...

Page 30: ...ld be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR Only doors certified with the appliance shall be use...

Page 31: ...lly clockwise Propane fully counter clockwise Settings are shown for each burner Air Shutter Adjusting Rod Air Shutter Adjusting Arms Orifice Increase Shutter Opening In This Direction Decrease Shutte...

Page 32: ...ur liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisis...

Page 33: ...flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Co...

Page 34: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 35: ...th the re quirements of the CAN CSA B149 1 Installation code Laconversiondevra treeffectu e conform ment aux recommanda tions des autorit s provinciales ayant juridiction et conform ment aux exigences...

Page 36: ...rimary air opening setting NOTE Each model has two burners and 2 Orifices Pilot Orifice Pilot Assembly Igniter Assembly Retaining Clip Flare Nut Note If the igniter is damaged a replacement kit is ava...

Page 37: ...S NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion...

Page 38: ...38 NOTES...

Page 39: ...39 39 NOTES...

Page 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Reviews: